Command Word
Bit-mapped drive control command word (drive parameter number FA00). This is the
location where run/stop, etc. commands are written. An example command word can
be found in Table 1. Because the format of this command word depends on the drive
manufacturer's specifications, please refer to your specific drive's Serial
Communications Manual for the exact structure of this word.
Using the example command word in Table 1, some representative command words
that can be used to control your drive via the Profibus network are:
0xC400 ..........Profibus command valid, Profibus frequency valid, drive run forward
0xC600 ..........Profibus command valid, Profibus frequency valid, drive run reverse
0xC000 ..........Profibus command valid, Profibus frequency valid, drive stop
0xE000 ..........Profibus command valid, Profibus frequency valid, reset drive fault
Although the above examples all show Profibus command and frequency valid, input
(status) data can always be monitored from the network regardless of the settings of
bits 14 and 15 in the command word.
Table 1 : Example Command Word Format (S9 Drive)
Bit
15
Command source
14
Frequency command source
13
Fault reset
12
Emergency OFF command
11
Coast stop command
10
Run / stop command
9
Forward / reverse selection
8
Jog command
7
DC injection braking
6
Accel / decel #1/#2 selection
5
Reserved
4
Reserved
3
Preset speed 4
2
Preset speed 3
1
Preset speed 2
0
Preset speed 1
Function
0
Local
Local
N/A
N/A
N/A
Stop
Forward
N/A
N/A
#1
--
--
OFF
OFF
OFF
OFF
21
1
Network
Network
Reset
EOFF
Coast stop
Run
Reverse
Jog
DC injection cmd.
#2
--
--
ON
ON
ON
ON

Advertisement