Foster Display Case Parameter Settings Service Manual page 6

Display case service manual

Advertisement

C2PD Condenser Overheat Probe 1
Selects the probe used.
Compressor Folder (CP)
d
Defrost Mode
Selects the type of defrost used
0 = Electrical Defrost; 1 = Hot gas defrost
L on
Min. Working Time
Minimum working time for the compressor
H on
Max. Working Time
Maximum working time for the compressor
oFFt
Compressor off-time
Compressor off time if maximum working time (H on) is achieved
CoFF
Min. Down Time
Minimum down time of compressor
rAtE
Cooling Rate
Percentage of the cooling frequency in probe failure
2dlF
Compressor Difference (Not used)
Condenser Overheat Folder (OH)
AL
Alarm Temperature
Temperature at which the condenser alarm will be activated
Alt
Alarm Temperature Delay
Time in minutes that the alarm will be delayed
Sd
Shutdown Temperature
Temperature at which the cabinet turns itself off due to high condenser temperature.
Sdt
Shutdown Temperature Delay
Time delay before the cabinet shuts down due to too high condenser temperature
Net Folder (nEt)
nlD
Device Identification
CAL1 Thermostat Probe Calibration
Calibration according to factory test run.
Standard Setting Folder (SdFt)
Press OK to restore the controller to the standard settings (NOTE; not the cabinet's factory settings)
5