ELECTRICAL
Wiring
Connections
I_kWARNING_ Fire hazard.
Incorrect voltage
can cause
a fire or seriously
damage
the motor
and voids the war-
ranty. The supply
voltage
must be within
±10% of the
motor
nameplate
voltage.
NOTICE:
Dual-voltage
motors
are factory
wired
for
230 volts. If necessary,
reconnect
the motor
for 115
volts, as shown.
Do not alter the wiring
in single volt-
age motors.
Install, grotmd,
wire, and maintain
your pump
in com-
pliance
with the National
Electrical
Code (NEC) or the
Canadian
Electrical
Code
(CEC), as applicable,
and
with all local codes
and ordinances
that apply. Consult
your local building
inspector
for code information.
Motor wires connect here.
-Power supply wires connect here.
230 Volt: Connect 2 hotwires (black and red)
here and cap the white (neutral) wire. It does
not matter whichwire goes to which screw.
115 Volt: Connect one hot wire (black or red)
to one of these screws (it doesn't matter
which one). Connect the white (neutral) wire
to the other screw. Cap any remaining
black or red wires.
prevent strain
on the terminal screws.
green (or bare copper) ground wire
to the green ground screw.
31870398
Figure
I 0 - Pressure switch wiring
Connection
Procedure
1. Connect
the ground
wire first as shown
in Figure 10.
The ground wire must be a solid copper
wire at least
as large as the power
supply wires.
2. There must be a solid metal connection
between
the
pressure
switch
and the motor
for motor
grounding
protection.
If the pressure
switch
is not connected
to the motor, connect
the green ground
screw in the
switch
to the green ground
screw under
the motor
end cover. Use a solid copper
wire at least as large
as the power
supply wires.
3. Connect
the ground
wire to a grounded
lead in a ser-
vice panel, to a metal underground
water pipe, to a
metal well casing at least ten feet (3M) long, or to a
ground
electrode
provided
by the power
company
or the hydro authority.
4. Connect
the power
supply
wires
to the pressure
switch
as shown
in Figure 10.
RECOMMENDED
FUSING
AND
WIRING
DATA
Pump
Model
390.2511
Motor
Horse-
power
1/2
Volts
115
230
Max.
Load
Amperes
10.4
5.2
Branch*
Delayed
Fuse
Rating
Amps
15.0
15.0
Distance in Feet From
Motor to Meter
0
51
101
201
to
to
to
to
50
100
200
300
Wire Size
14
14
10
8
14
14
14
14
* Time delayed fuses are recommended