Gas Supply - HouseWarmer HWDV080DV(N,P)-1 Installation Instructions And Owner's Manual

Direct vent wall furnace
Table of Contents

Advertisement

Locating Gas Supply
The gas line can enter the unit either through the floor or outside
wall. The gas line opening should be made at this time. Location
of the opening will be determined by the position of floor joists
and the valve and union used for servicing.
Recommended Gas Pipe Diameter
Pipe Length
Schedule 40 Pipe
Inside Diameter
Nat.
0-10 feet
1/2"
0-3 meters
12.7 mm
10-40 feet
1/2"
4-12 meters
12.7 mm
40-100 feet
1/2"
13-30 meters
12.7 mm
100-150 feet
3/4"
31-46 meters
19 mm
Note: Never use plastic pipe. Check to confirm whether your local
codes allow copper tubing or galvanized.
Note: Since some municipalities have additional local codes, it is
always best to consult your local authority and installation code.
The use of the following gas connectors is recommended:
— ANS Z21.24 Appliance Connectors of Corrugated Metal Tubing
and Fittings
— ANS Z21.45 Assembled Flexible Appliance Connectors of
Other Than All-Metal Construction
The above connectors may be used if acceptable by the authority
having jurisdiction. The state of Massachusetts requires that a
flexible appliance connector cannot exceed three feet in length.
Consult the current National Fuel Gas Code, ANSI Z223.1 CAN/
CGA-B149 (.1 or .2) installation code.
Page 12

GAS SUPPLY

Tubing, Type L
Outside Diameter
L.P.
Nat.
3/8"
1/2"
9.5 mm
12.7 mm
9.5 mm
1/2"
5/8"
12.7 mm
15.9 mm
12.7 mm
1/2"
3/4"
12.7 mm
19 mm
12.7 mm
1/2"
7/8"
12.7 mm
22.2 mm
19 mm
Figure 1
Installing a New Main Gas Cock
Each appliance should have its own manual gas cock.
A manual main gas cock should be located in the vicinity of
the unit. Where none exists, or where its size or location is not
adequate, contact your local authorized installer for installation
or relocation.
Compounds used on threaded joints of gas piping shall be resistant
to the action of liquefied petroleum gases. The gas lines must be
checked for leaks by the installer. This should be done with a soap
L.P.
solution watching for bubbles on all exposed connections, and if
3/8"
unexposed, a pressure test should be made.
Never use an exposed flame to check for leaks. Appliance must be
1/2"
disconnected from piping at inlet of control valve and pipe capped
or plugged for pressure test. Never pressure test with appliance
1/2"
connected; control valve will sustain damage!
A gas valve and ground joint union should be installed in the gas
3/4"
line upstream of the gas control to aid in servicing. It is required
by the National Fuel Gas Code that a drip line be installed near
the gas inlet. This should consist of a vertical length of pipe tee
connected into the gas line that is capped on the bottom in which
condensation and foreign particles may collect.
GAS SUPPLY
TEE HANDLE
FLARE SHUT OFF VALVE
CLOSE NIPPLE
TEE HANDLE
NPT GAS SUPPLY
Method of Installing a Tee Fitting Sediment Trap
FLEXIBLE GAS LINE CONNECTION
NPT NIPPLE
FLEX TUBE
FLARE FITTING
RIGID GAS LINE CONNECTION
3/8 NIPPLE
SHUT OFF VALVE
NPT UNION
Figure 2
REGULATOR
VALVE
REGULATOR
VALVE
24632-0-0508