INSTALLATION
Continued
4.
If installing bottom mounting screw into
hollow or solid wall, install wall anchor.
Follow steps 1 through 4 under Attach-
ing To Wall Anchor Method, page 8. If
installing bottom mounting screw into
wall stud, drill holes at marked loca-
tions using 9/64" drill bit.
5. Replace heater onto mounting bracket.
6. Place spacer between bottom mount-
ing hole and wall anchor or drilled hole.
7. Hold spacer in place with one hand.
With other hand, insert mounting screw
through bottom mounting hole and
spacer. Place tip of screw in opening
of wall anchor or drilled hole.
8. Tighten screw until heater is firmly secured
to wall. Do not over tighten. Note: Do not
replace front panel at this time. Replace
front panel after making gas connections
and checking for leaks. (see page 10).
Figure 12 - Installing Bottom Mounting
Screw
CONNECTING TO GAS
SUPPLY
WARNING: This appliance re-
quires a 3/8" NPT (National Pipe
Thread) inlet connection to the
pressure regulator.
WARNING: A qualified ser-
vice person must connect heater
to gas supply. Follow all local
codes.
CAUTION: Never connect heater
to private (non-utility) gas wells.
This gas is commonly known as
well-head gas.
IMPORTANT: Check gas line pressure be-
fore connecting heater to gas line. Gas line
pressure must be no greater than 14 inches
of water. If gas line pressure is higher,
heater regulator damage could occur.
107294
CAUTION: Use only new,
black iron or steel pipe. Inter-
nally-tinned copper tubing may
be used in certain areas. Check
your local codes. Use pipe 3/8"
diameter or greater to allow
proper gas volume to heater. If
pipe is too small, undue loss of
pressure will occur.
Installation must include an equipment
shutoff valve, union, and plugged 1/8" NPT
tap. Locate NPT tap within reach for test
gauge hook up. NPT tap must be upstream
from heater (see Figure 13).
IMPORTANT: Install an equipment shutoff
valve in an accessible location. The equip-
ment shutoff valve is for turning on or
shutting off the gas to the appliance.
3/8" NPT
Pipe Nipple
Ground Joint Union
Equipment
Shutoff
Valve *
From
Gas Meter
(4" W.C. to
10.5" W.C.
Pressure)
3" Min.
Figure 13 - Gas Connection
* A CSA/AGA design-certified equipment shutoff valve with 1/8" NPT tap is an acceptable
alternative to test gauge connection. Purchase the optional CSA/AGA design-certified
equipment shutoff valve from your dealer. See Accessory, page 18.
9
OWNER'S MANUAL
Apply pipe joint sealant lightly to male
threads. This will prevent excess sealant
from going into pipe. Excess sealant in pipe
could result in clogged heater valves.
CAUTION: Use pipe joint seal-
ant that is resistant to liquid pe-
troleum (LP) gas.
Install sediment trap in supply line as shown
in Figure 13. Locate sediment trap where it
is within reach for cleaning. Locate sedi-
ment trap where trapped matter is not likely
to freeze. A sediment trap traps moisture
and contaminants. This keeps them from
going into heater controls. If sediment trap
is not installed or is installed wrong, heater
may not run properly.
IMPORTANT: Hold pressure regulator with
wrench when connecting it to gas piping
and/or fittings
Pressure
Regulator
Heater
Cabinet
Tee Joint
Reducer
Test
Bushing to
Gauge
1/8" NPT
Connection *
1/8" NPT
Plug Tap
Tee Joint
Sediment
Pipe Nipple
Trap
Cap
Continued