Chapter 6 Troubleshooting

Troubleshooting via LED displays

Two LEDs, SP and NET LED, are used to monitor the PD-01 communication status.
Possible LED displays of NET LED:
LED
OFF
Red, flickering (rapid
blinking)
Red, blinking
Red ON
Green, blinking
Green ON
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
Indication
No Power Supply
Invalid PROFIBUS address
set via switch
Communication link to
PROFIBUS, but No cyclical
data exchanged, or
Extended user parameter
error
No connection to
PROFIBUS
"Master" is in "Stop" mode,
and cyclical process data
exchange in progress, but
set-points invalid (control
word = 0)
Cyclic data exchange in
progress and OK
Corrective Actions
Verify that the power supply of PD-01.
Check whether the power supply is
connected and that power is applied to
the PD-01 through the connector.
Check whether the switch value is
valid, valid value of slave is within
1-125. Set the valid value and re-power
User parameter are sent by master
(from GSD file), for example, if d_state
is set 1, ensure the data in Data Output
1 ~ Data Output 1 + dout_len are
continuous addresses. Otherwise,
PD-01 will not be able to pass the
Parameterization check.
1. Verify that network installation is OK.
2. Verify that PLC is working.
3. Verify that switch address setting is
correct.
Turn the KEY of PLC to RUN mode,
and send the control command to
PD-01.