6. Space required around unit

6.1. Individual installation

Basic space required
A space of at least 250 mm is necessary at the back for inlet air. Taking
servicing, etc. from the rear into account, a space of about 450 mm
should be provided, the same as at the front.
C
<Top view>
A 250 mm or more
B 450 mm or more
C Front (outside of machine room)
D Top discharge (open in principle)
E Front inlet (open in principle)
F Rear inlet (open in principle)
When inlet air enters from right and left sides of unit
B
C
D
A L
or more
1
B L
or more
2
C Front
D No restrictions on wall height (left and right)
Note:
Wall heights (H) of the front and the back sides shall be within
overall height of unit.
When the total height is exceeded, add the "h" dimension of the
figure above to L
and L
in the table above.
1
2
Model
L
L
1
PUHY-400
450
250
PUHY-500
D
A
E
B
<Side view>
A
B
C
A
<Side view>
2
When unit is surrounded by walls
C
A L
or more
1
B L
or more
F
2
C Front
D Front panel
E Rear panel
Note:
Wall heights (H) of the front and the back sides shall be within
height of front panel and rear panel.
If the panel height is exceeded, add the "h" dimension of the
figure above to L
1
Model
L
1
PUHY-400
450
PUHY-500
Example: When h is 100
The L
dimension becomes 450+100 = 550 mm.
1
When there is an obstruction above the unit
A
B
A 45° or more
B 300 mm or more
C Front
D 1000 mm or more
E Air outlet guide (procured at the site)
F Rear
A
B
C
D
A
<Side view>
and L
in the table above.
2
L
2
250
D
C
When there is little space
up to an obstruction
B
E
E
F
7