12. Test run

12.1. Checking before getting test run

1 Check to see whether there are refrigerant leakage, and slack of power or transmission cable.
Confirm that 500 V megger shows 1.0 M or more between power supply terminal block and ground. Do not operate in the case of 1.0 M or less.
NOTE: Never carry out megohm check over terminal control board. Otherwise the control board would be broken.
Immediately after mounting the unit or after leaving it turned off for an extended length of time, the resistance of the insulation between the power
2
supply terminal board and the ground may decrease to approx. 1.0 M as a result of refrigerant accumulating in the internal compressor.
If the insulation resistance is more than 1.0 M , turning on the main power supply and energizing the crankcase heater for more than 12
hours will cause the refrigerant to evaporate, increasing the insulation resistance.
Check to see whether both gas and liquid valves are fully open.
3
NOTE: Be sure to tighten caps.
Check the phase sequence and the voltage between phases.
4
NOTE: If the phase sequence is reversed, an error (4103) may occur when a test run is made, causing the unit to stop.
If a transmission booster is connected:
Turn transmission booster power on the before turning the outdoor unit's power on.
5
NOTE 1: If the outdoor unit's power is turned on first, refrigerant system connection data may not be recognized normally.
NOTE 2: If the outdoor unit's power is turned on first, reset the outdoor unit's power after turning the transmission booster power on.
Turn on universal power supply at least 12 hours before getting test run in order to carry current to crank case heater. If current-carrying hours are too
6
short, it may result in a malfunction of compressor.

12.2. Test run method

A Display panel
B Control panel
C Cooling/Heating select button 3, 4
D Check code indicator (see note 1)
E Test run remaining time indicator (see note 3)
F ON/OFF LED (lights up in operation)
Turn on universal power supply at least 12 hours before getting started
1
power supply must be left on for at least 12 hours (with the crank case heater turned on). If a transmission booster is connected, turn transmission
booster power on the before turning the outdoor unit's power on.
2 Press [TEST RUN] button twice
3 Press [Cooling/Heating] select button
4 Press [Cooling/Heating] select button to change from cooling to heating operation, and vice versa
5 Press [Wind] adjust button
6 Press [Up/Down Wind] or [Louver] button to change wind
7
Make sure that indoor unit fans operate normally.
8 Make sure that interlocking devices such as ventilator operate normally if any.
9 Press [ON/OFF] button to cancel test run
NOTE 1: If check code is displayed on remote controller or remote controller does not operate normally, see page 35 or further.
NOTE 2: Test run automatically stops operating after two hours by activation of timer set to two hours.
NOTE 3: During test run, test run remaining time is displayed on time display section.
NOTE 4: During test run, temperature of liquid pipe in indoor unit is displayed on remote controller room temp. display section.
NOTE 5: When pressing [Wind] adjust button, depending on the model, "This function is not available" may be displayed on remote controller. However,
it is not a malfunction.
NOTE 6: If the outdoor temperature is low, the unit may not operate for up to 4 hours.
34
CENTRALLY CONTROLLED
CHECK
A
CLOCK
˚C
STAND BY
INDOOR UNIT
DEFROST
ADDRESS NO
B
TEMP.
REMOTE CONTROLLER
PAR-F25MA
C
Operation procedure
displaying "TEST RUN" on display panel.
make sure that air is blowing out.
make sure that air blow is changed.
Make sure that horizontal or downward blow is adjustable.
Stop operation.
ON/OFF –
1Hr.
ON OFF
˚C
FILTER
CHECK MODE
ERROR CODE
TEST RUN
NOT AVAILABLE
OA UNIT ADDRESS NO
CLOCK
ON OFF
FILTER
CHECK
TIMER SET
TEST RUN
G Indoor unit liquid pipe temperature indicator (see note 4)
H ON/OFF button 9
I Test run indicator
J Wind adjust button 6
K Test run button 2
L Air blow adjust button 5
displaying "HO" on display panel for about two minutes. The universal
D
E
F
G
H
I
J
K
L
make sure that warm or cold air is blowing out.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents