Main Floor - Tie-In Claytile Flue
24"
9
8
7
5
4
6
3
Cleanout
Door
2
1
The Glow Boy Series Multi-Fuel Inserts may be installed in either a masonry or factory built fireplace.
Installing Pellet Inserts into Factory Built or Masonry Fireplaces:
The insert must be tested and meet the requirements of UL1482 (US) and or ULC8628 (CAN) when
Tested in a masonry fireplace built per ULC S628.
The factory-built fireplace must be listed per UL127 or ULC8610.
Clearances obtained from the masonry fireplace tests are also relevant for installation in factory-built
fireplaces.
Installation must include a full height listed chimney liner meeting type HT requirements (2100D F)
per UL1777 (US) or ULC 8635 (CAN). The stainless steel liner must be securely attached to the insert
flue collar and the chimney top.
Means must be provided to prevent room air passage to the chimney cavity of the fireplace. This may
be accomplished by sealing the damper area around the chimney liner.
The airflow within and around the fireplace shall not be altered by the installation of the insert (i.e. no
louvers or outlet ports are blocked), unless specifically tested as such for each factory-built fireplace
manufacturer and model line.
NOTE: using a louvered faceplate (surround) complies with this requirement.
Alteration of the fireplace in any manner is NOT permitted with the following EXCEPTIONS:
1.
External trim pieces which do not affect the operation of the fireplace my be removed
Providing they can be stored on or within the fireplace for re-assembly, if the insert is
removed.
2.
The chimney damper may be removed to install the chimney liner.
Circulating air chambers (i.e. in a steel fireplace liner or metal heat circulator) shall not be blocked.
Glow Boy Pellet & Biomass
F
I
F
I
REESTANDING
NSTALLATION
REESTANDING
NSTALLATION
1 "PL" Pipe Adapter
2
"PL" Clean Out Tee & Cap
3
"PL" Length of Pipe
4
"PL" 90D Elbow
5
"PL" Wall Thimble
6
Single Wall Stainless Steel
Clean Out Tee & Cap
7
Dripless Connection
8
"All Fuel" Stainless Steel
Flex Liner or "PL" Venting
9
Roof Flashing
Liner Support
10
Storm Collar
11
Vertical Rain Cap
12
Hi Heat Insulation
Tube of RTV Silicone
Roll of Foil Tape
3/8" Stainless Self-Tapping
Screws x 27
F
I
F
I
IREPLACE
NSERT
IREPLACE
NSERT
. . . C
'
. . . C
'
ON
T
ON
T
Main Floor - Class A Tie-In
1
Pipe Adapter
2
Clean Out Tee & Cap
3
3 x 60" (15') Pipe Length
4
Tee Support Bracket
"PL" Adjustable length
5
"PL" to Class A Adaptor
6
Class A Fittings
7
Ceiling Support / Firestop Spacer
8
Roof Flashing
9
Storm Collar
10
Vertical Rain Cap
11
Lengths of Pipe
Tube of RTV Silicone
Roll of Foil Tape
3/8" Stainless Self-Tapping
Screws x 27
I
I
NSTALLATION
NSTALLATION
www.glowboystoves.com
10
9
8
11
7
6
5
3
4
1
2
Outside Air
Intake
20
20

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Glow boy igb

Table of Contents