User Inputs / Customer Inputs; Customer Inputs; Table 7 - Liebert iCOM User Manual

Intelligent communications & monitoring system
Hide thumbs Also See for Liebert iCOM:
Table of Contents

Advertisement

3.7.5

User Inputs / Customer Inputs

The user can connect and specify up to four inputs depending on unit configuration. The user
inputs/customer inputs are digital inputs that influence the operating mode of the unit depending on
the selection. The customer input configuration settings are in the Service menu under Set Alarms,
Screen 2 of 7. The choices for the customer inputs are shown in Table 7 along with their associated
reaction. A terminal strip is provided in the cooling unit to connect your contact closure to. You have
the ability to set the control to react on an open or closed contact.
NOTE
To enabled/disabled, delay activation and set event type (alarm, warn, message) see Event
Types on page 34.

Table 7

Customer inputs

Setting
Smoke
Water Alarm
C PMP Alarm
Flow Alarm
Stdby G Pmp
Stdby Unit
C-Input 1
C-Input 2
C-Input 3
C-Input 4
Rht Lockout
Hum Lockout
Rht+Hum Lock
Comp Lockout
Call Service
High Temp
Air Loss
FC Lockout
Heater Alarm
Flow AL SD
Flow AL LC
Comp Lock PD
Enable FC
HTRJ VFD
HTRJ TVSS
Reaction
Event Only
Event Only
Event Only
Event Only
Event Only
Event Only
Event Only
Event Only
Event Only
Event Only
Event + Electrical Heaters Disabled
Event + Humidifier Disabled
Event + Electrical Heaters and Humidifier Disabled
Event + Compressor(s) Disabled w/o Pump Down
Event Only
Event Only
Event Only
Event + Free Cooling Disabled
Event + Heaters Off (PeX Only)
Event + Shut Down the Unit
Event + Lockout Compressors, No Pump Down (enabled only if at
least one compressor is on; auto-reset depends on input status)
Event + Compressor(s) Disabled w/ Pump Down
Forces Free Cooling to On
Activates the HEAT REJ VFD ALARM; no other function
Activates the HEAT REJ TVSS ALARM; no other function
33