Func.
Code
A146
ADD direction select
• 00 Plus (adds A145 value to output frequency)
• 01 Minus (subtracts A145 value from output
frequency)

"B" Group: Fine-tuning Functions

Func.
Code
B001
Selection of automatic restart mode
• 00 Alarm output after trip, automatic restart
disabled
• 01 Restart at 0Hz
• 02 Resume operation after frequency
matching
• 03 Resume previous freq. after freq. matching,
then decelerate to stop and display trip info
B002
Allowable under-voltage power failure time
B003
Retry wait time before motor restart
B004
Instantaneous power failure / under-voltage trip
alarm enable
• 00 Disable
• 01 Enable
B005
Number of restarts on power failure / under-
voltage trip event
• 00 Restart 16 times
• 01 Always restart
B012/
Level of electronic thermal setting
B212
B013/
Electronic thermal characteristic
B213
• 00 Reduced torque1• 01 Const. torque
• 02 Reduced torque2
B021
Overload restriction operation mode
• 00 Disabled
• 01 Enabled for accel and constant speed
• 02 Enabled for constant speed only
B022
Overload restriction setting
Name / Description
Name / Description
18
Default
Set
Value
Value
–FEF / –FU
00
Default
Set
Value
Value
–FEF / –FU
00
1.0
1.0
00
00
Rated
current of
each inverter
01
01
Rated
current x 1.5