Hitachi BRD-E2-30K Operation Manual page 15

Dynamic braking unit (brd series)
Table of Contents

Advertisement

Model
E2-30K
200V class
E2-55K
EZ2-30K
EZ2-55K
400V class
EZ2-110K
Note 1:
The wire for P, RB, and N connections should be MLFC wire (flame-retardant poly-flex wire, able to withstand
voltage of 600 V).
If the distance between the dynamic braking unit and a discharging resistor is 10 meters or more, use a cable
thicker than the specified wire size. Table 4.2 shows sizes of MLFC wire.
-1) If the distance is between 10 m (not including 10 m) and 25 m, use a wire size one rank larger.
-2) If the distance is between 25 m (not including 25 m) and 50 m, use a wire size two ranks larger.
However, the cable should be up to 5 m between the braking unit and the discharging resistor.
Table 4.2 Applicable wires
Connection
Wire for P, RB, and
resistance
N connections (Note1)
8 or more
5.5mm
5 to 7.9
8mm
4 to 4.9
14mm
4 or more
14mm
3 to 3.9
22mm
2 to 2.9
38mm
17 or more
3.5mm
13 to 16.9
5.5mm
10 to 12.9
8mm
10 or more
8mm
7.5
to 9.9
14mm
6 to 7.4
22mm
6 or more
22mm
4 to 5.9
38mm
3 to 3.9
60mm
2
or more
0.75mm
2
or more
2
or more
2
or more
2
or more
2
or more
2
or more
2
or more
2
or more
2
or more
2
or more
2
or more
2
or more
2
or more
2
or more
- 8 -
SL1, SL2,
Grounding wire
MA1, MA2
2
or more
5.5mm
2
or more