Example Of External Connection - Hitachi BRD-E2-30K Operation Manual

Dynamic braking unit (brd series)
Table of Contents

Advertisement

4.3

Example of External Connection

Figure 4.1 shows an example of a connection of a motor control system containing only one
dynamic braking unit.
Always use discharging resistors equal to or more than the resistance specified. If the
resistance is insufficient, the dynamic braking unit may be damaged.
To prevent overheating and burning during any malfunction of the dynamic braking unit, devise
a circuit to shut off the primary power of the inverter by connecting this circuit to the alarm
contact terminals (AL1 and AL2).
Figure 4.2 shows the connection of a thermal relay and Table 4.2 shows a list of applicable
wires.
400V class
Power supply
200V class
To the dynamic braking unit
To terminals of the external
resistor (when a 3-element
thermal relay is used)
(Note 2)
Inverter
Figure 4.1 External connection example
Figure 4.2 Connection of a Thermal Relay
- 6 -
(Note 1)
Motor
Dynamic braking unit
(Main unit)
Note 1: Select relay RY according to the coil (Mg)
and contact (RY) specifications.
Note 2: R0, T0 terminals depend on inverter model.
To the dynamic braking unit
To terminals of the external
resistor (when a 2-element 3-
terminal thermal relay is used)
Connection to the alarm terminal section
Thermal relay
(Usually closed (b contact) and
opens when it is working)
External
resistor
Thermal relay