Installation; Adsjusting The Damper Rod (For Ervs Installed In Warm Regions); Locating And Mounting The Unit - Maytag ERV-150 Installer Manual

Ventilation systems
Table of Contents

Advertisement

6.0

Installation

I
C
NSPECT THE
ONTENTS OF THE
Inspect the exterior of the unit for shipping damage. Ensure that there is no damage to the door, door
latches, door hinges, dampers, duct collars, cabinet, etc.
Inspect the interior of the unit for damage. Ensure that the fan motor assembly, recovery core, insulation,
dampers, damper actuator and drain pan are all intact.
If the unit was damaged during shipping, contact your local distributor. (Claim must be made within
24 hours after delivery.)
Use checklist included with the unit to ensure that no parts are missing.
6.1 A
DJUSTING THE
Refer to Section 4.2 and observe the difference in the damper
position at the right in diagrams Defrost Mode 1 and Defrost Mode 2:
for Defrost Mode 1 the damper is completely closed, whereas
for Defrost Mode 2 the damper is half closed. At the factory, all ERVs
are assembled for defrost Mode 2. Therefore, if your installation
is for an ERV in a warm region (zone D as defined in Section 3),
the rod must be moved to position 1 (see figure 5).
NOTE: Before attempting to change the position of the damper
rod, place the unit on a table for easy access and remove
the recovery core.
This is a delicate operation: to avoid injury proceed carefully and use the appropriate tools.
6.2 L
OCATING AND
Choose an appropriate location for the unit:
Within an area of the house where the temperature is above 10°C /
50°F (basement, attic, furnace room, laundry room, etc.).
Away from living areas (dining room, living room, bedroom), if possible.
So as to provide easy access to the interior cabinet and to
the control panel on the right hand side of the unit.
Close to an exterior wall, so as to limit the length of the insulated
flexible duct to and from the unit.
Close to a drain. If no drain is close by, use a pail to collect
run-off.
Away from hot chimneys, electrical panel and other fire haz-
ards.
Make sure the unit is level.
Allow for a power source (110 V standard outlet).
Hang the unit to ceiling joists with the 4 chains and
springs provided (see figures 6 and 7).
B
OX
D
R
(F
AMPER
OD
OR
CAUTION
M
U
OUNTING THE
CAUTION
13
ERV
I
S
NSTALLED IN
VO0015
O00 5
NIT
VD0064
figure 7
VD0038
W
R
)
ARM
EGIONS
1
2
figure 5
figure 6

Advertisement

Table of Contents
loading

This manual is also suitable for:

Erv-210Hrv-150Hrv-210

Table of Contents