Modbus/BSAP Configuration
1.
Raven EDGE/GPRS for Cingular - User Guide, version 2.31
Automation and Telemetry
FIGURE 1.

Configuring the Raven

You can use either Wireless Ace, direct serial communication, or Telnet to configure your modem
using AT commands (page 50).

Configuring the Raven at the Polling Host for Modbus on UDP

This section covers a Polling Host with standard Modbus, variations may need additional AT com-
mands.
Configure the listening/device ports for the host and remotes.
The destination port for the modem at the host needs to match the device port in use on all the
modems at the remote sites. For example, if the remote modem's device port (see below) is
"12345", then the Modbus host modem's S53 destination port should be set to "12345".
In Wireless Ace, select Misc in the side menu.
Wireless Ace: Destination Port
FIGURE 2.
Take note of (or set) the Device Port setting in *DPORT to configure the remote modems.
33