Installation instructions
Selecting inlet air restrictor
Note: Before installing the combustion air inlet
accessory, the appropriate inlet air restrictor must
be determined using Tables 6, 7 and 8.
Refer to Fig. 15 for mounting sequence.
B Determine the total length of the straight sections of
3" stainless steel exhaust and enter that length in line
1.
B Count the number of 90° elbows used and enter that
value in line 2.
B Count the number of 45° elbows used and enter that
value in line 3.
B For model GWH 345 ESR, enter a 1 in line 4 for
model GWH 450 ESR enter a 1 in line 5.
B Repeat steps 1 through 4 for the 3" intake pipe and
enter those values in the intake section.
B Add the totals from the Exhaust table and the Intake
table to determine the equivalent vent length. Use
this value in Table 6 to determine which restrictor
size to use.
Exhaust
1
Straight section length
2
90° elbows (qty)
3
45° elbows (qty)
4
GWH 345 ESR termination
5
GWH 450 ESR termination
6
Intake
1
Straight section length
2
90° elbows (qty)
3
45° elbows (qty)
4
GWH 345 ESR termination
5
GWH 450 ESR termination
6
7
Total equivalent vent length =
Table 6 Determining equivalent vent length (see
example in Table 7)
16
Example
Exhaust
• 10 - 3' straight sections
• 1 - 1' straight section
• 1 - 90° elbow
• 1 - GWH 450 ESR termination.
Intake
• 5 - 4' straight sections
• 2 - 1' straight sections
• 2 - 90° elbows
• 1 - GWH 450 ESR termination.
Example
__ x 1 =
____
__ x 6 =
____
__ x 3 =
____
__ x 15 =
____
__ x 12 =
____
Total:
____
__ x .5 =
____
__ x 3 =
____
__ x 1.5
____
__ x 6 =
____
__ x 3 =
____
Total:
____
____
Table 7 Determining equivalent length example
Using table 8, the following restrictors would be
required:
• GWH 450 ESR NG - restrictor 55
• GWH 450 ESR LP - restrictor 55.
Exhaust
Straight section length
90° elbows (qty)
45° elbows (qty)
GWH 345 ESR termination
GWH 450 ESR termination
Intake
Straight section length
90° elbows (qty)
45° elbows (qty)
GWH 345 ESR termination
GWH 450 ESR termination
Total equivalent vent length =
Total length 31'
Total length 22'
21
x 1 =
21
1 x 6 =
6
0 x 3 =
0
0 x 15 =
0
1 x 12 =
12
Total:
39
22 x .5 =
11
2 x 3 =
6
0 x 1.5 =
0
0 x 6 =
0
1 x 3 =
3
Total:
20
59
6 720 607 909