Dimensional Specifications / Power Connection Terminals; Model Transfer Switches - GE Zenith Controls ZTS Specification

Zts series automatic transfer switches
Table of Contents

Advertisement

Ampere
Poles
Height
Rating
(A)
40, 80
2, 3
24 (61)
100, 150
4
24 (61)
225
2, 3
46 (117)
260, 400
4
46 (117)
2, 3
66 (168)
600
4
74 (188)
2, 3
74 (188)
800, 1000, 1200
4
74 (188)
1600
3
90 (229)
2000
4
90 (229)
3
90 (229)
3000
4
90 (229)
3
90 (229)
4000
4
90 (229)
Application Notes:
1. Metric dimensions (cm) and weights (Kg) shown in parenthesis adjacent
to English measurements in inches and pounds.
2. Includes 1.25" door projection beyond base depth. Allow a minimum of 3"
additional depth for projection of handle, light, switches, pushbuttons, etc.
3. All dimensions and weights are approximate and subject to change
without notice.
4. Special enclosures (NEMA 3R, 4, 12, etc.) dimensions and layout may differ.
Consult the
Zenith factory for details.
GE
5. Normal and emergency may be ordered inverted on any switch.
The load may be inverted 600-1200 amps. Consult the factory for details.
6. Special lug arrangements may require different enclosure dimensions.
For certified drawings, contact the
Zenith factory.
GE
7. Packing materials must be added to weights shown. Allow 15% additional
weight for cartons, skids, crates, etc.
8. Add 4" in height for removable lifting lugs.
9. Lug adapters for 3000-4000 amp limits may be staggered length for ease
of entrance. Consult the
GE
Zenith factory for details.
10. Ventilation louvers on both sides of enclosure at 3000 and 4000 amps.
One must be clear for airflow with standard cable connections.
AL-CU UL Listed Solderless
Screw-Type Terminals for
External Power Connections
Switch
Normal,
Switch
Size
Emergency,
Size
Amps
& Load Terminals
Amps
& Load Terminals
Cables/
Wire
Cables/
Pole
Ranges
40-150
1
#8 to 3/0
800/1000
AWG
/1200
225
1
#4 AWG to
1600
600 MCM
260
1
#4 AWG to
2000
600 MCM
400
1
#4 AWG to
3000
600 MCM
600
2
#2 AWG to
4000
600MCM

Dimensional Specifications / Power Connection Terminals

Model Transfer Switches

ZTS
NEMA 1 Enclosed
Width
Depth
(B)
(C)
18 (46)
11.13 (28)
18 (46)
11.13 (28)
24 (61)
14.13 (36)
24 (61)
14.13 (36)
24 (61)
19.75 (50)
30 (76)
19.75 (50)
30 (76)
19.75 (50)
40 (102)
19.75 (50)
30 (76)
48 (122)
36 (91)
48 (122)
30 (76)
48 (122)
36 (91)
48 (122)
40 (102)
60 (152)
46.5 (118)
60 (152)
Normal
Emergency,
Notes:
*
Line and load terminals are located in rear and arranged for bus bar connection.
Wire
Terminal lugs are available at additional cost. Contact factory for more details.
Pole
Ranges
4
#2 AWG to
1. Special terminal lugs and neutral bars are available at additional cost. Contact factory and advise cable sizes
600 MCM
and number of conductors per pole.
2. Fully rated neutral provided on 3 phase, 4 wire system.
3. Normal and emergency may be ordered inverted on any switch. Load may be inverted 600-1200 amps. Consult the factory for details.
*
4. Lug adapters for 3000-4000 amp units may be staggered length for ease of entrance. Consult the factory for details.
5. Special lug arrangements may require different enclosure dimensions. For certified drawings, contact the
Weight
Reference
Open
NEMA 1
Figure
Type
A
21 (10)
57 (26)
A
24 (11)
60 (27)
A
70 (32)
165 (75)
A
75 (34)
170 (68)
B
165 (75)
380 (172)
B
185 (84)
430 (195)
B
190 (86)
455 (206)
B
210 (95)
540 (245)
C
345 (156)
1010 (458)
C
450 (204)
1160 (526)
C
465 (211)
1130 (513)
C
670 (304)
1395 (633)
C
770 (349)
1595 (723)
C
1025 (465)
1850 (839)
C
B
A
Figure A
Application Notes
1 – 7
1 – 7
1 – 8
1 – 8
1 – 8
1 – 10
1 – 10
C
B
A
Figure B
Figure C
Zenith factory.
GE
ZTS Series
es:
P
age 9
PB-5066

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ZTS and is the answer not in the manual?

Table of Contents