Power Distribution Unit - HP Integrity rx8620 Site Preparation Manual

Site preparation guide, fourth edition - hp integrity rx8620 server
Hide thumbs Also See for Integrity rx8620:
Table of Contents

Advertisement

Power Distribution Unit

The server may ship with a power distribution unit (PDU). There are two 60A PDUs available for the HP
Integrity rx8620 Server. Each PDU is mounted horizontally between the rear columns of the server cabinet.
The 60A PDUs are delivered with an IEC-309 60A plug.
1
The 60A NEMA
PDU has four 20A circuit breakers and is constructed for North American use. Each of the
four circuit breakers has two IEC
The 60A IEC PDU has four 16A circuit breakers and is constructed for International use. Each of the four
circuit breakers has two IEC-320 C19 outlets providing a total of eight IEC-320 C19 outlets.
Each PDU is 3U high and is rack-mounted in the server cabinet.
Documentation for installation will accompany the PDU. The documentation can also be found at the external
Rack Solutions Web site at http://www.hp.com/racksolutions. This PDU might be referred to as a Relocatable
Power Tap outside HP.
The PDU installation kit contains the:
PDU with cord and plug
Mounting hardware
Installation instructions
1. The acronym NEMA stands for National Electrical Manufacturers Association.
2. The acronym IEC stands for International Electrotechnical Commission.
Chapter 1
2
-320 C19 outlets providing a total of eight IEC-320 C19 outlets.
System Specifications
Power Distribution Unit
11

Advertisement

Table of Contents
loading

Table of Contents