Input:
Fuels:
Gas Turndown:
Pilot Input:
Gas Inlet Pressure:
Ambient Temp. Limits*:
Downstream Temp. Limits: 1500° F
Flame Length**:
Piloting:
Flame Monitoring:
Motor:
Materials:
Emissions:
Packaging Options:
Models:
Related Information:
* Based on blower motor limitations.
** Based on parallel air flow. If mounted in a cross flow, then flame will be shorter.
CAUTION: It is dangerous to use any fuel burning equipment unless it is equipped with suitable flame sensing de-
vices and automatic fuel shut-off valves. Eclipse can supply such equipment or information on alternate sources.
1,000,000 Btu/hr. per lineal foot (962 kW/m).
Natural gas or 100% propane vapor. Call Eclipse for information on using other fu-
els.
40:1
Approximately 25,000 Btu/hr. (7.3 kW)
800,000 Btu/hr/ft. (769 kW/m):
1,000,000 Btu/hr/ft. (962 kW/m):
Gas pressure shown is a differential measured between the gas inlet and a tap on
the duct wall 10" to 20" (254 to 508 mm) downstream of the burner.
– 40° to +104° F
– 40° to +40° C
815° C
800,000 Btu/hr. (769 kW/m):
1,000,000 Btu/hr. (962 kW/m):
Integral spark-ignited pilot; ignition plug included.
Flame rod supplied. UV scanner adaptors are available. For UV scanners, Eclipse
recommends a flame monitoring system that terminates the ignition spark and
proves the pilot flame without spark prior to opening the main gas valves.
CGA requires two flame rods on burners over 36" long (914 mm). Use a flame
monitoring endplate (see Data 140-6) to mount a second flame rod on the end op-
posite the gas inlet.
Standard: 230/460/3/60 TEFC. Other motors can be supplied.
All portions of the burner exposed to flame are cast iron or #321 stainless steel.
Emissions performance depends not only on the burner,
but also other factors such as chamber temperature, chamber design, and heat load-
ing. For estimates of emissions performance in your application, call Eclipse.
Available with complete valve trains and control systems. AH burners and systems
can be supplied mounted on duct sections as specified by the customer. Call Eclipse
for information on custom packaged systems.
Model
Description
AH
Line-shape, blower mounted on rear
DAH
Line-shape, blower mounted on bottom
TAH
"I"-shape, blower mounted on rear
CAH
Cross-shape, blower mounted on rear
Blower and motor specifications
Eclipse AirHeat v1.0 - Installation Guide No. 140, 11/4/03
Nat. Gas:
2.2" w.c.
Propane:
0.9" w.c.
Nat. Gas:
3.5" w.c.
Propane:
1.3" w.c.
28"
0.71 m
46"
1.17 m
Data Sheet
Data 140-1
Data 140-2
Data 140-3
Data 140-4
Data 140-5
5.5 mbar
2.2 mbar
8.7 mbar
3.2 mbar