Wiring Requirements

• The bonding wire at least No. 8 AWG copper wire.
Pull Copper current carrying conductors (one each: black, red, white,
green), Use either No. 6 AWG 60º C, 8 AWG 75º C, or No. 8 AWG 90º C
wire, if spa is 50 feet or less away from its power supply. Note: the ground
must be equal to or larger than the largest power conductor.
Factory Recommended G.F.C.I. Load Center Wiring
Note: Connection order may vary by pack model, please refer to
equipment pack panel for proper connection order.
Dynasty Spas Operator's Guide • www.dynastyspas.com
10

WIRING DIAGRAM

Note: The white neutral wire from the
back of the GFCI MUST be connected
to an incoming line neutral. The internal
mechanism of the GFCI requires this
neutral connection. The GFCI will not
work without it.
CAUTION!
CONNECTION ORDER
Line 1
Neutral
GND
Line 2
S-CLASS SHOWN
(from spa
system box)