Installing the New Water Heater (cont'd)
Venting (cont'd)
VENTING THROUGH AN OUTSIDE WALL (cont'd)
40 AND 50 GALLON 40,000 BTU/HR MODELS (3" VENT)
SEE CHART BELOW FOR MAX. LENGTH
4' MIN.
" MIN.
15
1
⁄
2
14" MIN.
2. The total vertical and horizontal vent run cannot
exceed the maximum length with the number of 90°
elbows as specified in the tables below. If more elbows
are required the venting distance must be reduced 5
feet for every 90˚ elbow:
75 GALLON 70,000 and 75,000 BTU/HR, 50 GALLON
52,500, 55,000 and 62,500 BTU/HR and 40 GALLON
50,000 BTU/HR MODELS ONLY
3" " DIA. VENT
MAX. LENGTH (FT.)
70
65
60
55
50
45
75 GALLON 70,000 and 75,000 BTU/HR, 50 GALLON 52,500,
55,000 and 62,500 BTU/HR and 40 GALLON 50,000 BTU/HR
MODELS ONLY – OPTIONAL 4" VENT PIPING
4" " DIA. VENT
MAX. LENGTH (FT.)
110
105
100
95
90
85
ALL 40 and 50 GALLON 40,000 BTU/HR MODELS ONLY
3" " DIA. VENT
MAX. LENGTH (FT.)
115
110
105
100
95
90
"
MIN. RISE
⁄
1
8
PER FIVE FEET
NUMBER OF
90° ELBOWS*
1
2
3
4
5
6
NUMBER OF
90° ELBOWS*
1
2
3
4
5
6
NUMBER OF
90° ELBOWS*
1
2
3
4
5
6
ALL 40 and 50 GALLON 40,000 BTU/HR MODELS —
OPTIONAL 2" " VENT PIPING
2" " DIA. VENT
MAX. LENGTH (FT.)
50
45
40
35
30
25
*NOTE: Two 45° elbows are equivalent to one 90° elbow.
One 90° elbow equals 5 feet of equivalent vent length.
20'
(EXAMPLE)
3. Minimum vent length for all 40,000 BTU/HR input
models is 4 feet and 16 inches for all other models.
VENTING THROUGH AN OUTSIDE WALL WITH LOW
GROUND CLEARANCE
1. When the vent piping cannot pass through an outside
wall at a height greater than or equal to 12" above the
ground (or above snow accumulation level), then the
installation can be modified as shown below.
18
NUMBER OF
90° ELBOWS*
1
2
3
4
5
6
95' MAX.
"
MIN. RISE
⁄
1
8
PER FIVE FEET
ONE ELBOW
EXAMPLE
3" VENT PIPE
40 GALLON
40,000 BTU/HR
MODEL EXAMPLE
12" MIN. ABOVE
GROUND OR SNOW
ACCUMULATION LEVEL