Drolet UL 1482 Owner's Manual page 7

Drolet epa wood stove owner's manual
Hide thumbs Also See for UL 1482:
Table of Contents

Advertisement

Clearances to any combustibles when measured directly from the floor protector to the ceiling must be a
minimum of 84" (2134 mm). Clearances to any combustibles when measured directly from the front of the
stove must be a minimum of 48" (1219 mm). The stove must also be placed so as to maintain the minimum
clearances to combustible walls specified for each type of connector used. See Table 1.3 below for all
clearance measures. Refer to Figure 1.3 for a diagram of each of the measures A through C.
Unit:
To sidewall
To back wall (B)
To corner
Single walled connector
(A)
18" (406 mm)
18" (406 mm)
(C)
12" (305 mm)
TABLE 1.3 Clearances to combustible materials
FIGURE 1.3 Clearances to combustible materials
Listed double walled
connector
18" (406 mm)
18" (406 mm)
12" (305 mm)
6