Electrical Connection - Dometic RM2354 Installation And Operating Instructions Manual

Refrigerator for lp-gas and electric operation
Hide thumbs Also See for RM2354:
Table of Contents

Advertisement

TESTING LP GAS SAFETY SHUTOFF
The gas safety shutoff must be tested after the re-
frigerator is connected to the LP gas supply.
To test the gas safety shutoff, proceed as follows:
1. Start the refrigerator and switch to GAS mode.
(See start up instructions).
2. Check that the gas flame is lit and the GAS mode
indicator lamp (C) is on.
3. Close the manual gas shutoff valve at the back of
the refrigerator. (See FIG. 1).
4. Wait for one minute. The CHECK indicator lamp (E)
should be on and the GAS mode indicator lamp (C)
should be off.
5. Remove protection cover (see FIG. 1) and open the
manual gas shutoff valve. Do not change any button
positions on the control panel. Apply a non-corrosive
commercial bubble solution to the burner jet orifice.
6. No bubbles should appear at the opening of the burner
jet orifice. The presence of bubbles indicates a de-
fective gas safety shutoff, and service is required.
7. If no bubbles were present at the burner jet orifice, it
should be rinsed with fresh water. Be careful not to
damage the burner jet orifice. Replace cover and
press the main power ON/OFF button (1) OFF and
back ON. Normal operation of the burner should re-
turn. Allow the burner to operate for a minimum of 5
minutes.

ELECTRICAL CONNECTION

120 Volts AC Connection
The refrigerator is equipped with a three-prong
(grounded) plug for protection against shock hazards and
should be plugged directly into a properly grounded three-
prong receptacle. DO NOT cut or remove the grounding
prong from this plug. The free length of the cord is 2
feet. and therefore recommended that the receptacle be
located to the left side of the refrigerator (viewed from
the rear) and approximately 4-6 inches from the floor
(see FIG. 8). This allows easy accessibility through the
vent door. The cord should be routed to avoid contacting
the burner cover, flue cover, or any other components
that could damage the cord insulation.
120 Volt AC
receptacle
4 - 6"
Hole for drain water hose
FIG. 8
12 Volts DC Connection
This refrigerator model require a continuous 12 volt DC
supply to maintain the automatic energy system.
The connection is made to the positive (+) and negative
(-) terminals of the terminal block on back of the refrig-
erator. (See FIG. 1). Correct polarity must be observed
when connecting to the DC supply.
DO NOT use the chassis or vehicle frame as one of the
conductors. Connect two wires at the refrigerator and
route to the DC supply.
The distance the current must travel from the battery to
the refrigerator dictates the AWG wire size to be used.
Should the wire be too small for the distance, a voltage
drop will result.
The voltage drop affects the wattage output of the 12 volt
cartridge heater and resultant refrigerator performance.
The 12 volt DC heater is fused with a 30 amp. in-line blade
fuse.
Recommended wire sizes are shown below.
MAXIMUM TOTAL CONDUCTOR WIRE LENGTH
(In feet and meters)
Wire length
17 ft.
5 m
27 ft.
8 m
The wires from the battery to the refrigerator must be of
large enough size to handle the load. The connections
must be clean, tight and free from corrosion. If not, a
resulting voltage drop will cause a decreased cooling
capacity.
RM2354
AWG
10
8
7

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents