WSC 106 MH S AR ™ CompactSmoke Installation instruction For firmware version from 1.09 (Version 2505) Save this installation instruction to the end-user. The latest version of this document can always be found on our website. +44 (0) 1536 614 070 info.uk@windowmaster.com +353 1903 9455 info.ie@windowmaster.com...
Page 2
1 Safety information ................................ 3 Safety ................................3 Mains ................................. 3 Back-up batteries .............................. 3 Application ................................. 3 Cable routing and electrical connection ......................3 Commissioning ..............................3 2 Structure of the smoke panel ............................4 3 Max numbers of actuators per motor line and panel ....................4 4 Accessories and spare parts ............................
Page 3
Safety information Safety Only allow appropriately trained, qualified and skilled personnel to carry out installation work. Reliable operation and the avoidance of damage and hazards are only guaranteed if installation and settings are carried out carefully in accordance with these instructions. There may be personal danger by electrically operated windows: - the forces occurring in the automatic mode can be such that parts of the body could get crushed - when opened, actuators (spindles) could protrude into the room...
Page 4
Structure of the smoke panel The WSC 106 contains a power supply unit (SMPS) type WCA 1P2, and a main card type WSA 1SS with input, output, and auxiliary supply (AUX). The main card type WSA 1SS allows connections of 1 motor line and 1 keypad. ®...
Page 6
Smoke detector WSA 311 Rain sensor WLA 331 Rain/wind speed sensor WLA 330 End of line motor module WSA 514 End of line smoke detector module (10kΩ resistor), 10 pcs. WSA 501 Cable glands for WSC 106 WSA 134 Cables for smoke ventilation – see separate data sheet for further information WLL 8xx Comfort keypad for 1 window or 1 window group WSK 110 0A0B...
Page 7
Cable monitoring 24 VDC standard actuators with end of line module and smoke detectors are monitored. ® Actuators with MotorLink and break glass units are monitored by data communication. Back-up batteries are monitored by cyclic measuring LED message OK, fault and alarm Green all OK Yellow...
Page 8
Installation Cable routing For cable routing we recommend the use of fire protected cables retaining their function E90 or E30. See also chapter 8 “Cable dimensioning” in this instruction. However, this must be agreed with the Engineer or, if necessary, with the local fire protection department. Do not reduce the cable cross sections specified in the cable lengths table.
Page 9
Cable dimensioning Maintaining the cable functions According to valid national regulations. The cable network for smoke ventilation systems (“Cable system“) ends normally at the interface (junction box) for the actuator! The flexible, heat resistant connection cable of actuator is part of the system component‚ electric actuator and is not a part of the electrical installation! We recommend in all cases to discuss the type of cable routing with the competent firefighting authorities.
Page 10
Furthermore, when using a 5-core cable, the distance between ”–” and ”Com” must be the same as the distance between ”+” and ”Com”. Meaning if L2 e.g. is being used as ”Com” L1 and L3 must be used for ”+” and ”-”. ®...
Page 11
Cable plan for connection to WSC 106 The above plan shows the WSC 106 with 24 VDC standard actuators connected. Description of card and mains connection The panel includes a power supply unit (SMPS) and a main card. 10.1 Mains connection and power supply (WCA 1P2) WCA 1P2 - 150W SMPS unit The power supply is located under the main card.
Page 12
10.2 Main card WSA 1SS The WSA 1SS contains the following: - 1 motor line for 24 VDC ® standard or MotorLink actuators - 1 input for keypads for comfort ventilation - 1 input for break glass units - 1 input for smoke detector - output for alarm signal - output for fault signal to Fire Alarm System...
Page 13
MotorLink ® actuators Examples with actuators per motor line Ex. 1: 4 pcs. WMX 823-1 Ex. 2: 2 pcs. WMU 883-2 Ex. 3: 2 sets of 3 pcs. WMU 826-3 ® Allowed actuator combinations on a MotorLink motor line The motor line can be connected to one of the below shown combinations. -1 (single): one window with one single window actuator.
Page 14
An end of line motor module (WSA 514) is not to be connected when pyrotechnic gas generators or electromagnetic releases are connected, but the cables are still being monitored. Max 12 pyrotechnic gas generators or max. 10 electromagnetic releases can be connected to the smoke panel. IMPORTANT an auto configuration is not to be carried out when pyrotechnic gas generators nor electromagnetic releases are connected! When DIP switch 8 is changed from ON to OFF and neither pyrotechnic gas generators nor electromagnetic...
Page 15
Example: A smoke zone and connected components; 1 break glass unit type WSK 501 / 502 and 1 break glass unit type WSK 503 / 504, 2 smoke detectors WSA 311, 1 resistor WSA 501 and 1 comfort keypads. When there is no smoke detector connected to the WSK 501 / 502 a 10 kΩ resistor must be connected to the break glass unit on terminal 7 and 8.
Page 16
Connection of different types of smoke detectors to CompactSmoke™ Smoke detector type WSA 300 WSA 311 Hekatron Hekatron MSD 523 SSD 521/a (max 5 pcs) (WSA 200 6101) X6.1 L1 In In + Connect to WSA 1SS X6.2 Com - Com - Connect to WSK In +...
Page 17
Solid state output for transmission of fault signal to 3 part systems e.g., Fire Alarm System Data Normally closed. Open = Fault Solid state output for transmission of fault signal to 3 party systems. A fault must last min 20 seconds before the relay indicates a fault. Data Max.
Page 18
Shows the status of the panel = alarm Yellow = fault Green fast flickering = all OK (CPU working), Green constant = CPU communication stopped (possible reset or contact WindowMaster) Close / open all windows. When pressed together right after power has been connected or when pressed ↓...
Page 19
Grace time periods: MotorLink™ actuators: 30 sec. after the windows were closed with a safety signal (0% max opening command) or a reset after alarm 24V standard actuators: Safety signal: 2 min after the windows were closed with a safety signal (0% max opening command) Reset after alarm: 30 sec after the windows were closed with a reset after alarm.
Page 20
13.1.4 Local output The outputs on the panel are pre-configured with the function as shown below. X7 Fire alarm active signal X8 Any error on the panel Fault detection via LED 14.1 Fault detection on the smoke panel In case of error on the panel, the yellow diode on the main card will blink and via blink sequence indicate an error message. Depending on the type of error, the message will consist of 2 or 3 blink sequences, separated by a second pause.
Page 21
Error message 1. Blink sequence 2. Blink sequence 3. Blink sequence Number Number Number Error on Error on or error type Error type of blinks of blinks of blinks Closed ring – this version does not allow break glass units connected in a closed ring, check connection of break glass units, and disconnect the ring and re-configure Problem on X5 (break glass unit) –...
Page 22
15.1.1 Fuses – 6.3A slow An ”Battery status” error can also be triggered if the battery-fuse (6.3A slow) is blown. Additionally, a “motor line status” error will be triggered if the motor line-fuse (6.3A slow) is blown. The battery-fuse is located in the bottom right above the connection to the back-up battery.
Page 23
16.6 Break glass unit WSK 50x a) Open the door and press the black Open button. Check that the actuators open through to the fully open position. b) Check that the red alarm LED (also in the panel) is ON; at the same time a permanent acoustic signal sounds (door contact on the break glass unit is pressed!).
Page 24
The smoke ventilation panel will signal fault on the batteries if the battery voltage is below 17 VDC. Within the framework of the service, they must be replaced after the specified maximum 4-year operating period. Dispose of used batteries according to the National regulation. CAUTION: RISK OF EXPLOSION IF BATTERIES ARE REPLACED BY AN INCORRECT TYPE.