NI sbRIO-9263 Operating Instructions And Specifications

4-channel, +-10 v, 16-bit analog voltage output module

Advertisement

Quick Links

sbRIO-9263

Advertisement

loading
Need help?

Need help?

Do you have a question about the sbRIO-9263 and is the answer not in the manual?

Questions and answers

Summary of Contents for NI sbRIO-9263

  • Page 1 sbRIO-9263...
  • Page 2 OPERATING INSTRUCTIONS AND SPECIFICATIONS NI 9263E 4-Channel, ±10 V, 16-Bit Analog Voltage Output Module...
  • Page 3 National Instruments makes no electromagnetic Caution compatibility (EMC) or CE marking compliance claims for the NI 9263E. The end-product supplier is responsible for conformity to any and all compliance requirements. Caution The NI 9263E must be installed inside a suitable enclosure prior to use.
  • Page 4 NI 9263E Dimensions The following figure shows the dimensions of the NI 9263E. 73.4 (2.89) 0.0 (0.00) Figure 1. NI 9263E Dimensions in Millimeters (Inches) National Instruments Corp. © NI 9263E Operating Instructions and Specifications...
  • Page 5 Connecting the NI 9263E The NI 9263E has a 10-terminal, detachable, screw-terminal connector that provides connections for 4 analog output channels. Figure 2. NI 9263E Terminal Assignments NI 9263E Operating Instructions and Specifications ni.com...
  • Page 6 Each channel of the NI 9263E has an AO terminal and a common terminal, COM, and there is an additional COM terminal at the bottom of the connector. All of the COM terminals are internally connected to the isolated ground reference of the module. You can connect a load to each channel of the NI 9263E.
  • Page 7 Isolated DAC Short-Circuit Protection Amplifier NI 9263E Figure 4. Output Circuitry for One Channel of the NI 9263E When the module powers on, the channels output the startup voltage. Refer to the Specifications section for more information about startup voltage. Refer to the software help for information NI 9263E Operating Instructions and Specifications ni.com...
  • Page 8 In sleep mode, the system consumes minimal power and may dissipate less heat than it does in normal mode. Refer to the Specifications section for more information about power consumption and thermal dissipation. National Instruments Corp. © NI 9263E Operating Instructions and Specifications...
  • Page 9 When the module powers on, a glitch occurs for 20 µs peaking at –1.5 V. The power-down voltage peaks at 1.8 V before exponentially discharging to 0 V in 100 µs. You can add a 10 kΩ load to reduce the peak voltage. NI 9263E Operating Instructions and Specifications ni.com...
  • Page 10 0.75% Calibrated, typ (25 °C, ±5 °C) 0.03% 0.1% Uncalibrated, max (–40 to 85 °C) 2.2% 1.7% Uncalibrated, typ (25 °C, ±5 °C) 0.3% 0.25% * Range equals ±10.7 V National Instruments Corp. © NI 9263E Operating Instructions and Specifications...
  • Page 11 3 µs min 6.5 µs min 5 µs min 9 µs min 7.5 µs min 12 µs min 9.5 µs min Noise Updating at 100 kS/s ....600 µV Not updating....... 260 µV NI 9263E Operating Instructions and Specifications 10 ni.com...
  • Page 12 MTBF ..........1,732,619 hours at 25 °C; Bellcore Issue 2, Method 1, Case 3, Limited Part Stress Method Note Contact NI for Bellcore MTBF specifications at other temperatures or for MIL-HDBK-217F specifications. National Instruments Corp. © 11 NI 9263E Operating Instructions and Specifications...
  • Page 13 C Series module and connectors, visit and search by ni.com/dimensions module number. Screw-terminal wiring ...... 12 to 24 AWG copper conductor wire with 10 mm (0.39 in.) of insulation stripped from the end NI 9263E Operating Instructions and Specifications 12 ni.com...
  • Page 14 This category refers to local-level electrical distribution, such as that provided by a standard wall outlet, for example, 115 V for U.S. or 230 V for Europe. National Instruments Corp. © 13 NI 9263E Operating Instructions and Specifications...
  • Page 15 Caution Do not connect the NI 9263E to signals or use for measurements within Measurement Categories III or IV. Safety Standards This product meets the requirements of the following standards of safety for electrical equipment for measurement, control, and laboratory use when installed in a suitable enclosure: •...
  • Page 16 (IEC 60068-2-1, IEC 60068-2-2) ..–40 to 85 °C Operating humidity (IEC 60068-2-56)......10 to 90% RH, noncondensing Storage humidity (IEC 60068-2-56)......5 to 95% RH, noncondensing Maximum altitude......2,000 m Pollution Degree ....... 2 National Instruments Corp. © 15 NI 9263E Operating Instructions and Specifications...
  • Page 17 NI recognizes that eliminating certain hazardous substances from our products is beneficial not only to the environment but also to NI customers. For additional environmental information, refer to the NI and the Environment Web page at .
  • Page 18 China RoHS compliance, go to ni.com/ environment/rohs_china Calibration You can obtain the calibration certificate and information about calibration services for the NI 9263E at ni.com/calibration Calibration interval ......1 year National Instruments Corp. © 17 NI 9263E Operating Instructions and Specifications...
  • Page 19 Czech Republic 420 224 235 774, Denmark 45 45 76 26 00, Finland 358 (0) 9 725 72511, France 01 57 66 24 24, Germany 49 89 7413130, India 91 80 41190000, Israel 972 3 6393737, Italy 39 02 41309277, Japan 0120-527196, NI 9263E Operating Instructions and Specifications 18 ni.com...
  • Page 20 Taiwan 886 02 2377 2222, Thailand 662 278 6777, Turkey 90 212 279 3031, United Kingdom 44 (0) 1635 523545 LabVIEW, National Instruments, NI, ni.com, the National Instruments corporate logo, and the Eagle logo are trademarks of National Instruments Corporation. Refer to the Trademark Information at ni.com/trademarks for other National Instruments trademarks.