Quick Links

CCESSING THE PARAMETERS
EVJ 500 Seres | Temperature/humidity and food processing co
EVJ 500 Seres | Temperature/humidity and food processing controllers
access and change the parameters:
For further information, consult the user manual p/n 114J500E4 downloadable from the
1
For further information, consult the user manual p/n 114J500E4 downloadable from the
website www.evco.it
website www.evco.it
-17.
ELECTRICAL CONNECTIONS
ELECTRICAL CONNECTIONS
Over Temp
RISK OF ELECTRIC SHOCK, EXPLOSION OR ELECTRIC ARC
Door open
RISK OF ELECTRIC SHOCK, EXPLOSION OR ELECTRIC ARC
• Various product components, including the printed circuits, run at hazardous voltage levels.
• Only use electrically insulated and suitably calibrated measuring devices and equipment.
• Various product components, including the printed circuits, run at hazardous voltage levels.
• Do not open, disassemble, repair or modify the product.
3 s
• Only use electrically insulated and suitably calibrated measuring devices and equipment.
• Before handling the product, make sure you are wearing all the necessary personal protective
• Do not open, disassemble, repair or modify the product.
equipment (PPE).
• Before handling the product, make sure you are wearing all the necessary personal protective
• Do not expose the equipment to liquids or chemicals.
• Use this device and all parts connected to it at the specified voltage only.
equipment (PPE).
• Do not use this equipment for critical safety functions.
3
• Do not expose the equipment to liquids or chemicals.
FAILURE TO FOLLOW THESE INSTRUCTIONS WILL RESULT IN DEATH OR
• Use this device and all parts connected to it at the specified voltage only.
Parameters
SERIOUS INJURY.
• Do not use this equipment for critical safety functions.
Internal Values
Alarms
FAILURE TO FOLLOW THESE INSTRUCTIONS WILL RESULT IN DEATH OR
Data Memory Reset
Parameters Restore
SERIOUS INJURY.
Haccp
RISK OF ELECTRIC SHOCK AND FIRE
• Do not use the device with loads greater than those indicated in the technical specifications.
• Do not exceed the temperature and humidity ranges indicated in the technical specifications.
FAILURE TO FOLLOW THESE INSTRUCTIONS WILL RESULT IN DEATH OR
RISK OF ELECTRIC SHOCK AND FIRE
SERIOUS INJURY.
• Do not use the device with loads greater than those indicated in the technical specifications.
• Do not exceed the temperature and humidity ranges indicated in the technical specifications.
FAILURE TO FOLLOW THESE INSTRUCTIONS WILL RESULT IN DEATH OR
5
MALFUNCTIONING OF THE EQUIPMENT
SERIOUS INJURY.
• Perform the wiring carefully, in compliance with electromagnetic compatibility and safety
requirements.
Password
• Do not operate the product with unknown or incorrect settings or data.
• Make sure the wiring is correct for the final application.
• Use shielded cables for all I/O signal and communication cables.
MALFUNCTIONING OF THE EQUIPMENT
• Minimise the length of the connections as much as possible and avoid winding the cables
around electrically connected parts.
• Perform the wiring carefully, in compliance with electromagnetic compatibility and safety
• The signal cables (analogue and digital inputs, communication and corresponding power
requirements.
supplies), power cables and power supply cables for the device must be routed separately.
• Do not operate the product with unknown or incorrect settings or data.
• Before applying the power supply, check all the wiring connections.
• Make sure the wiring is correct for the final application.
• Do not connect wires to unused terminals and/or to terminals labelled "No connection
• Use shielded cables for all I/O signal and communication cables.
"(N.C.)".
• Minimise the length of the connections as much as possible and avoid winding the cables
HANGING THE SETPOINT
FAILURE TO FOLLOW THESE INSTRUCTIONS CAN RESULT IN DEATH, SERIOUS
around electrically connected parts.
INJURY, OR EQUIPMENT DAMAGE
change the setpoint:
• The signal cables (analogue and digital inputs, communication and corresponding power
TECHNICAL SPECIFICATIONS
supplies), power cables and power supply cables for the device must be routed separately.
1
The product complies with the following harmonised standards: EN60730-1 and EN60730-2-9
• Before applying the power supply, check all the wiring connections.
-17.
Device construction:
• Do not connect wires to unused terminals and/or to terminals labelled "No connection
Device purpose:
"(N.C.)".
Type of action:
Pollution category:
FAILURE TO FOLLOW THESE INSTRUCTIONS CAN RESULT IN DEATH, SERIOUS
Over Temp
Overvoltage category:
INJURY, OR EQUIPMENT DAMAGE
Door open
Rated impulse withstand voltage:
Power supply:
TECHNICAL SPECIFICATIONS
Consumption:
Ambient operating conditions:
The product complies with the following harmonised standards: EN60730-1 and EN60730-2-9
Transportation and storage conditions:
Device construction:
Software class:
Device purpose:
Environmental front protection:
Type of action:
OTHER TECHNICAL INFORMATION
3
Pollution category:
Display properties
Overvoltage category:
Display:
Rated impulse withstand voltage:
Display resolution:
Display range:
Power supply:
Input properties (SELV)
Consumption:
Analogue Inputs:
Ambient operating conditions:
Transportation and storage conditions:
Software class:
Environmental front protection:
OTHER TECHNICAL INFORMATION
Digital input :
Display properties
Output properties
5
Display:
Digital outputs:
Display resolution:
Display range:
Input properties (SELV)
Analogue Inputs:
Serial communication port properties (SELV)
Digital input :
RS-485 serial port:
LECTING A PRE-SET PROGRAMME (EVJ 536 ONLY)
DIMENSIONS
select one of the six pre-set operating programmes (From Stop):
Output properties
1
Digital outputs:
-17.
Over Temp
Program 01
Stop
HANGING THE PRE-SET PROGRAMME (EVJ 536 ONLY)
Serial communication port properties (SELV)
INSTALLATION
RS-485 serial port:
change the pre-set programme during operation:
DIMENSIONS
1
-17.
Over Temp
Door open
3 s
3
WIRING DIAGRAM
Dripping
Dry 01
Pr3≠0
Dry 02
INSTALLATION
Dry 03
Dry 04
Dry 05
Power supply
Dry 06
17 18 19 20 21 22 23
1 2 3
4 5 6
TERMINALS
1-2
Relay output Out3 (Light)
3
No connection N.C.
mplified EU declaration of conformity
4-5-6 Relay output Out6 (Defrost)
WIRING DIAGRAM
CO S.p.A. declares that the type of radio equipment:
8-10 Relay output Out1 (Compressor)
VJ536N2VX3XXV
11-12 Relay output Out5 (Fans)
Pr3≠0
mplies with directive 2014/53/EU and directive 2011/65/EU.
12-14 Relay output Out4 (Humidification)
e full text of the EU declaration of conformity is available at the following internet address:
ps:/ /www.evco.it/en/16162-evj-500
sclaimer
17 18 19 20 21 22 23
s document is the exclusive property of EVCO. It contains a general description and/or a
scription of the technical specifications for the features offered by the products listed herein.
s document should not be used to determine the suitability or reliability of these products in
ation to specific user applications. Each user or integration specialist should conduct their
n complete and appropriate risk analysis, in addition to carrying out a product evaluation and
t in relation to its specific application or use.
ither EVCO nor any of its associates or subsidiaries shall be held responsible or liable
improper use of the information contained herein. Users can send us comments and
ggestions on how to improve or correct this publication.
1 2 3
4 5 6
CO has a policy of continuous development. Therefore, EVCO reserves the right to make
anges and improvements to any product described in this document without prior notice.
TERMINALS
1-2
Relay output Out3 (Light)
e technical data in this manual is subject to change without prior notice.
3
No connection N.C.
4-5-6 Relay output Out6 (Defrost)
CONSIDER THE ENVIRONMENT
8-10 Relay output Out1 (Compressor)
Please read this document carefully and save it.
11-12 Relay output Out5 (Fans)
12-14 Relay output Out4 (Humidification)
DISPOSAL
°c
5
60
%
Menu
WARNING
Parameters
1
1
2
Incorporated device
°c
5
60
Operating control device
%
1
2
I
4000 V
12 Vac/dc, ±10%, 50/60 Hz
10 VA maximum
-5 ... 55 °C (32 ... 131 °F) 10 ... 90 % RH non-condensing
-25 ... 70 °C (-13 ... 158 °F) 10 ... 90 % RH non-condensing
A
IP65
Setpoint 2
0
2.8" TFT graphic display, 16 colours
320 x 240 pixels
-50...99 (decimals on large display: -9.9...19.9)
10/95 %
2 analogue inputs
Analogue inputs
Pb1
Pb2
1
2
Pb3 (se Pr3=5)
2 voltage-free digital inputs (ID3 also configurable as
analogue input Pb3 with Pr3≠0)
6 relay outputs
Timer
9:55
Relay
output
Out1
5.1
5.2
Out2
hh:mm
Out3
Out4
Out5
Out6
1
2
1 TTL serial
-17.
°c
°c
5
60
5
60
%
Over Temp
Door open
111.4 (4.38)
°c
5
60
%
-17.
°c
5
Over Temp
Door open
Program 01
111.4 (4.38)
10 h
15 h
24 h
24 h
24 h
24 h
24 h
(*) = Maximum 10 A
TTL
(*)
9 10 11 12 13 14 15 16
Power supply
(*) = Maximum 10 A
TTL
(*)
9 10 11 12 13 14 15 16
2
DANGER
DANGER
4
DANGER
DANGER
6
WARNING
.
2
.
Incorporated device
Operating control device
1
4
2
I
4000 V
12 Vac/dc, ±10%, 50/60 Hz
10 VA maximum
-5 ... 55 °C (32 ... 131 °F) 10 ... 90 % RH non-condensing
Default
-25 ... 70 °C (-13 ... 158 °F) 10 ... 90 % RH non-condensing
Temperature probe
A
Humidity probe
IP65
Evaporator probe
2.8" TFT graphic display, 16 colours
320 x 240 pixels
-50...99 (decimals on large display: -9.9...19.9)
Default
Type
Compressor
SPST
2 analogue inputs
Heating
SPDT
Analogue inputs
Light
SPST
Humidification
SPST
Pb1
Fans
SPST
Pb2
Defrost
SPDT
Pb3 (se Pr3=5)
2 voltage-free digital inputs (ID3 also configurable as
analogue input Pb3 with Pr3≠0)
2
6 relay outputs
Relay
Default
output
%
Out1
Compressor
Out2
Heating
Out3
Light
Out4
Humidification
Out5
Fans
Out6
Defrost
1 TTL serial
mm (in.)
2
60
%
Pr3=0
mm (in.)
17 18 19 20 21 22 23
1 2 3
4 5 6
12-15-16 Relay output Out2 (Heating)
17-21
Digital input ID1
Digital input ID3 if Pr3=0
18-21
Probe input Pb3 if Pr3≠0
19-21
Probe input Pb2 (Humidity)
20-21
Probe input Pb1 (Temperature)
Pr3=0
22-23
Power supply input
12-15-16 Relay output Out2 (Heating)
17-21
18-21
19-21
20-21
22-23
Menu
Run
Rest
Air control
Air interval
Air time
Language
Service
1
Service
Parameters
Internal Values
Alarms
Data Memory Reset
Parameters Restore
Haccp
Parameters
Password
0
CA1
CA2
r0
rt2
rd0
rh0
1
Setpoint
20.0
0/50 °C
1
Timer
9:55
hh:mm
Load (at
Type of
250 Vac)
load
30 A
Resistive
8 A
Resistive
Default
16 A
Resistive
8 A
Resistive
Temperature probe
5 A
Resistive
Humidity probe
8 A
Resistive
Evaporator probe
Menu
Program 01
Type
Program 02
Program 04
SPST
Program 05
Program 06
SPDT
SPST
SPST
SPST
48.5 (1.91)
1
SPDT
Menu
Program 01
Run
Reset
Air control
Air interval
Air time
Language
48.5 (1.91)
Power supply
(*) = Maximum 10 A
TTL
(*)
9 10 11 12 13 14 15 16
Power supply
17 18 19 20 21 22 23
1 2 3
4 5 6
9 10 11 12 13 14 15 16
Digital input ID1
Digital input ID3 if Pr3=0
Probe input Pb3 if Pr3≠0
Probe input Pb2 (Humidity)
Probe input Pb1 (Temperature)
Power supply input
USER INTERFACE
Keys
Key...
Press onc
• Go back
• Exit a fu
• Decreas
• Move w
2
• Increas
• Move w
• Access
Active/De
• Confirm
• Access
Icons
Icon
ON...
• Cooling req
• Dehumidific
Defrost activ
Evaporator fa
• Humidificat
• Humidificat
• Dehumidific
• Dehumidific
• Heating req
• Heating dig
HACCP HACCP alarm
Energy savin
2
Maintenance
C
Temperature
F
Temperature
%
Humidity disp
• AUX functio
AUX
• AUX digital
Light relay ON
• Probe value
• Probe value
Keypad locke
Keypad unloc
2
Door switch o
Active cycle
EVJ 526 ONL
Sanitation in
device ON
Humid.: Humidification
ALARMS
Code
Description
1
Pr1
Probe error
Pr2
Pr3
Low
AL
temperature
alarm Pb1
High
AH
temperature
alarm Pb1
Low humidity
AL2
Pb2 alarm
High humidity
AH2
Pb2 alarm
Load (at
Type of
250 Vac)
load
Door open
30 A
Resistive
id
alarm
8 A
Resistive
16 A
Resistive
Condenser
COH
overheat signa
8 A
Resistive
High
5 A
Resistive
CSd
condensation
2
alarm
8 A
Resistive
Multi-purpose
iA
input alarm
Defrost
dFd
timeout alarm
Digital
HP
pressure
switch alarm
Thermal
CtH
switch 1
alarm
rtc
Clock alarm
Power failure
PF
alarm
PARAMETERS TA
Access Password: 1
Par. Description
CONFIGU
CA1 Pb1 probe offset
CA2 Pb2 probe offset
REGULAT
r0 Cooling mode se
r12 Heating different
HUMIDI
rd0 Dehumidification
rh0 Humidification di
DEFROST
d0 Defrost interval.
Evaporator temp
d2
with evaporator
d3 Defrost duration
KEYS Gr
Enable light key i
PLi
0 = Disabled; 1 =
Deactivate alarm
PSr
0 = Do not deacti
1 = Deactivate.
(*) = Maximum 10 A
TTL
(*)

Advertisement

loading
Need help?

Need help?

Do you have a question about the EVJ 500 Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Evco EVJ 500 Series

  • Page 1 17 18 19 20 21 22 23 17 18 19 20 21 22 23 s document is the exclusive property of EVCO. It contains a general description and/or a scription of the technical specifications for the features offered by the products listed herein.
  • Page 2 USER INTERFACE Keys Key... Press once... Hold down... • (From home page) Access the configuration menu • (From stand-by) Access the programming menu • Go back one level • Switch device on/off • Exit a function • Stop regulation • Decrease a value •...
  • Page 3 /www.evco.it/en/16162-evj-500 Disclaimer This document is the exclusive property of EVCO. It contains a general description and/or a description of the technical specifications for the features offered by the products listed herein. This document should not be used to determine the suitability or reliability of these products in relation to specific user applications.