Lenovo ThinkSystem Micro DataCenter 18U User Manual
Lenovo ThinkSystem Micro DataCenter 18U User Manual

Lenovo ThinkSystem Micro DataCenter 18U User Manual

Rack cabinet

Advertisement

Quick Links

ThinkSystem Micro DataCenter 18U Rack
Cabinet
User Guide
Machine Type: 7D2C and 7D2P

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ThinkSystem Micro DataCenter 18U and is the answer not in the manual?

Questions and answers

Summary of Contents for Lenovo ThinkSystem Micro DataCenter 18U

  • Page 1 ThinkSystem Micro DataCenter 18U Rack Cabinet User Guide Machine Type: 7D2C and 7D2P...
  • Page 2 First Edition (February 2020) © Copyright Lenovo 2020. LIMITED AND RESTRICTED RIGHTS NOTICE: If data or software is delivered pursuant to a General Services Administration (GSA) contract, use, reproduction, or disclosure is subject to restrictions set forth in Contract No.
  • Page 3: Table Of Contents

    Trademarks ....Chapter 6. Hardware removal, Index ....37 installation and conversion ..19 © Copyright Lenovo 2020...
  • Page 4 ThinkSystem Micro DataCenter 18U Rack Cabinet User Guide...
  • Page 5: Safety

    Vor der Installation dieses Produkts die Sicherheitshinweise lesen. Prima di installare questo prodotto, leggere le Informazioni sulla Sicurezza. Les sikkerhetsinformasjonen (Safety Information) før du installerer dette produktet. Antes de instalar este produto, leia as Informações sobre Segurança. © Copyright Lenovo 2020...
  • Page 6: Safety Statement

    • Always install stabilizer brackets on the rack cabinet. • Always install the heaviest devices in the bottom of the rack cabinet. • Always install servers and optional devices starting from the bottom of the rack cabinet. R003 ThinkSystem Micro DataCenter 18U Rack Cabinet User Guide...
  • Page 7 2. Remove the signal cables from the connectors. 4. Attach signal cables to other devices. 3. Remove all cables from the devices. 5. Connect power cords to their sources. 6. Turn ON all the power sources. © Copyright Lenovo 2020...
  • Page 8 Do not connect a power cord from a device that is installed in one rack cabinet to a power device that is installed in a different rack cabinet. R009 CAUTION: ThinkSystem Micro DataCenter 18U Rack Cabinet User Guide...
  • Page 9 Pack the rack cabinet in the original packaging material, or equivalent. Also, lower the leveling pads to raise the casters off the pallet and bolt the rack cabinet to the pallet. © Copyright Lenovo 2020...
  • Page 10 ThinkSystem Micro DataCenter 18U Rack Cabinet User Guide...
  • Page 11: Chapter 1. Introduction

    See this documentation to learn about specification details and installation instructions of ThinkSystem Micro DataCenter 18U Rack Cabinet. ThinkSystem Micro DataCenter 18U rack cabinet is a 18U cabinet designed for Micro DataCenter servers. Figure 1. ThinkSystem Micro DataCenter 18U Rack Cabinet The cabinet comes with a limited warranty.
  • Page 12 ThinkSystem Micro DataCenter 18U Rack Cabinet User Guide...
  • Page 13: Chapter 2. Specifications

    Chapter 2. Specifications See this section for information about ThinkSystem Micro DataCenter 18U rack cabinet. Dimension and weight Dimension • Length: 1200 mm (47.24 inch) • Width: 607 mm (23.9 inch) • Height: 976.5 mm (38.44 inch) Weight 106.5 kg (234.8 lbs) Supported servers and configurations See this section for information about the servers that are supported by the rack cabinet.
  • Page 14 ThinkSystem Micro DataCenter 18U Rack Cabinet User Guide...
  • Page 15: Chapter 3. Parts Listing

    Chapter 3. Parts Listing Figure 2. Rack cabinet components Table 1. Rack cabinet components Rack cabinet frame Removable and reversible door Removable side panel Hardware box (see “Hardware box” on page Removable side panel Shipping bracket © Copyright Lenovo 2020...
  • Page 16 20 M6 screws One combination wrench Ten C-type flange nuts One socket wrench 20 G-type cage nuts One spud socket wrench Ten cage nuts 15 cable ties One cage nut tool Two bolt-down brackets ThinkSystem Micro DataCenter 18U Rack Cabinet User Guide...
  • Page 17: Chapter 4. Move The Rack Cabinet

    WARNING: Failure to follow these instructions could result in equipment damage, severe injuries, or death. Before moving the rack cabinet, complete the following steps: 1. Unlock and open both doors by pulling up the handle and turning it clockwise. © Copyright Lenovo 2020...
  • Page 18 Figure 4. Opening the door 2. Remove the four shipping brackets that secure the cabinet to the pallet. Figure 5. Removing shipping brackets Two options are available when moving the cabinet: ThinkSystem Micro DataCenter 18U Rack Cabinet User Guide...
  • Page 19: Casters

    Casters S037 CAUTION: The weight of this part or unit is more than 55 kg (121.2 lb). It takes specially trained persons, a lifting device, or both to safely lift this part or unit. Complete the following steps to move the cabinet to the designated site: Step 1.
  • Page 20: Crane Lifter

    • Make sure that more than two people are handling the cabinet while sliding it down from the ramp board. • Do not stand in the path of the cabinet. Crane lifter ThinkSystem Micro DataCenter 18U Rack Cabinet User Guide...
  • Page 21 Attention - Drop hazard. Complete the following steps to lift and move the cabinet to the designated site: Step 1. Remove the four plugs from the four corners on the top of the cabinet frame. Figure 9. Lifting the rack cabinet Step 2.
  • Page 22 Once the leveling foot makes firm contact with the floor, tighten the nut that fixes it. Figure 12. Tightening the nut 2. To secure the cabinet to the ground, you can install the bolt-down brackets in the hardware box (see “Hardware box” on page ThinkSystem Micro DataCenter 18U Rack Cabinet User Guide...
  • Page 23 Figure 13. Installing the bolt-down brackets Chapter 4 Move the rack cabinet...
  • Page 24 ThinkSystem Micro DataCenter 18U Rack Cabinet User Guide...
  • Page 25: Chapter 5. Managing Cables

    See this section to learn how to connect ground cable in the rack cabinet. The following grounding pins close to door frame bottom are available for grounding cable connection. Grounding cable from the cabinet frame This cable is required for grounding. © Copyright Lenovo 2020...
  • Page 26 Figure 15. Grounding cable from the cabinet frame Grounding cable from the cabinet door This is an optional grounding cable. ThinkSystem Micro DataCenter 18U Rack Cabinet User Guide...
  • Page 27 Figure 16. Grounding cable from the cabinet door Grounding cable from the side panel This is an optional grounding cable. Chapter 5 Managing cables...
  • Page 28 Figure 17. Grounding cable from the side panel ThinkSystem Micro DataCenter 18U Rack Cabinet User Guide...
  • Page 29: Chapter 6. Hardware Removal, Installation And Conversion

    Pivot the top of the panel away from the cabinet frame to remove it. Install the side panels Complete the following steps to install the side panels. P P r r o o c c e e d d u u r r e e © Copyright Lenovo 2020...
  • Page 30: Removing, Installing And Reversing The Doors

    Note: For safety, this task must be done by two people. 1. If necessary, insert the key and turn it clockwise to unlock the door. 2. Pull the lower end of the handle up and clockwise; then, open the door. ThinkSystem Micro DataCenter 18U Rack Cabinet User Guide...
  • Page 31 Figure 20. Opening the door P P r r o o c c e e d d u u r r e e Step 1. Pull up and hold both of the hinge shafts to disengage the door from the cabinet frame; then, remove the door.
  • Page 32: Install The Door

    P P r r o o c c e e d d u u r r e e Step 1. Align the door to the frame hinges, and push the shafts in to secure the door to the frame. ThinkSystem Micro DataCenter 18U Rack Cabinet User Guide...
  • Page 33 Figure 22. Installing the door A A f f t t e e r r t t h h i i s s t t a a s s k k i i s s c c o o m m p p l l e e t t e e d d 1.
  • Page 34: Reverse The Door

    P P r r o o c c e e d d u u r r e e Step 1. Pull up and hold both of the hinge shafts to disengage the door from the cabinet frame; then, remove the door. ThinkSystem Micro DataCenter 18U Rack Cabinet User Guide...
  • Page 35 Figure 25. Removing the door Step 2. Remove the screws that secure the hinges to the cabinet frame. Step 3. Rotate both hinges 180 degree, and install the hinges to the opposite side of the frame. Figure 26. Converting the cabinet frame hinges Chapter 6 Hardware removal, installation and conversion...
  • Page 36 Install the device to the equivalent location on the opposite side on the cabinet frame. Figure 28. Installing the door position monitor device Remove the device from the door, and install it to the equivalent location on the opposite side of the door. ThinkSystem Micro DataCenter 18U Rack Cabinet User Guide...
  • Page 37 Figure 29. Removing and installing the door position monitor device Step 5. Remove the screws that secure the handle to the door; then, rotate the door 180 degree while keeping the handle in the original orientation, and secure the handle to the door with screws. Figure 30.
  • Page 38 1. Close the cabinet door, and turn the door handle counterclockwise to secure it. Figure 32. Closing the cabinet door 2. If necessary, insert the key and turn it counterclockwise to lock the door. ThinkSystem Micro DataCenter 18U Rack Cabinet User Guide...
  • Page 39: Door Position Monitor Device Replacement

    See this section for replacement of the door position monitor device. Note: This component is a Third Party Option parts. Not with standing anything to the contrary, third party options are excluded from Lenovo Statement of Limited Warranty. See https://support.lenovo.com/us/en/ for details.
  • Page 40: Remove The Door Position Monitor Device

    P P r r o o c c e e d d u u r r e e Step 1. Remove the two screws that secure the door position monitor device to the cabinet frame. ThinkSystem Micro DataCenter 18U Rack Cabinet User Guide...
  • Page 41: Install The Door Position Monitor Device

    Figure 35. Removing door position monitor device Step 2. Remove the two screws that secure the door position monitor device to the bracket to remove it. Figure 36. Removing door position monitor device Install the door position monitor device P P r r o o c c e e d d u u r r e e Step 1.
  • Page 42 1. Close the cabinet door, and turn the door handle counterclockwise to secure it. Figure 39. Closing the cabinet door 2. If necessary, insert the key and turn it counterclockwise to lock the door. ThinkSystem Micro DataCenter 18U Rack Cabinet User Guide...
  • Page 43: Appendix A. Getting Help And Technical Assistance

    Appendix A. Getting help and technical assistance If you need help, service, or technical assistance or just want more information about Lenovo products, you will find a wide variety of sources available from Lenovo to assist you. On the World Wide Web, up-to-date information about Lenovo systems, optional devices, services, and support are available at: http://datacentersupport.lenovo.com...
  • Page 44: Contacting Support

    Gathering information needed to call Support If you believe that you require warranty service for your Lenovo product, the service technicians will be able to assist you more efficiently if you prepare before you call. You can also see http:// for more information about your product warranty.
  • Page 45: Appendix B. Notices

    Lenovo representative for information on the products and services currently available in your area. Any reference to a Lenovo product, program, or service is not intended to state or imply that only that Lenovo product, program, or service may be used. Any functionally equivalent product, program, or service that does not infringe any Lenovo intellectual property right may be used instead.
  • Page 46: Trademarks

    Trademarks Lenovo, the Lenovo logo, Micro DataCenter, ThinkSystem, Flex System, System x, NeXtScale System, and X Architecture are trademarks of Lenovo in the United States, other countries, or both. Intel and Intel Xeon are trademarks of Intel Corporation in the United States, other countries, or both.
  • Page 47: Index

    20, 22, 24 remove door position monitor device ThinkSystem Micro DataCenter 18U Rack Cabinet reverse Getting help grounding cable safety safety statement service and support before you call...
  • Page 48 ThinkSystem Micro DataCenter 18U Rack Cabinet User Guide...
  • Page 50 Part Number: SP47A41859 Printed in China (1P) P/N: SP47A41859 *1PSP47A41859*...

This manual is also suitable for:

7d2c7d2p

Table of Contents