Pertronic FR1 Technical Manual

Pertronic residential fire control panel
Table of Contents

Advertisement

Quick Links

PERTRONIC
RESIDENTIAL FIRE
CONTROL PANEL
FH1/FR1
TECHNICAL MANUAL
Valid For FH1/FR1:
PCB Hardware
PCB Firmware
ISSUE 2.0
The content of this manual is copyright.
This document is to be used only for
operating or maintaining Pertronic Fire Alarm
This document is not to be reproduced,
photocopied or passed in part or whole to a
third party without the express, written
Pertronic Industries Limited
1.0+
1.7.0
systems.
authorisation of

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the FR1 and is the answer not in the manual?

Questions and answers

Summary of Contents for Pertronic FR1

  • Page 1 ISSUE 2.0 The content of this manual is copyright. This document is to be used only for operating or maintaining Pertronic Fire Alarm systems. This document is not to be reproduced, photocopied or passed in part or whole to a...
  • Page 2 End of Line End of line termination, normally 10KΩ Resistor used to monitor the presence and integrity of the detector circuit Light Emitting Diode Manual Call-Point Open-circuit Printed Circuit Board Short-circuit © Pertronic Industries Ltd 0017 FH1_FR1 Technical Manual Iss 2.0 20240522...
  • Page 3: Table Of Contents

    CONTENTS INTRODUCTION FH1/FR1 Single Zone Fire Alarm Panel Functional Description Specifications Operational Description 1.4.1 Installed Equipment 1.4.2 Equipment Operation 1.4.3 Hush Facility 1.4.4 Outputs for Monitoring Equipment SYSTEM FEATURES Front Panel Indication: Front Panel Controls: Zone Circuit 2.3.1 Smoke Detectors 2.3.2...
  • Page 4 Testing the Sprinkler input Exiting the TEST MODE FH1/FR1 M-VALUE DATUM ZONE 1 SPRINKLER (SPR) DIAGRAMS FH1/FR1 Main Board Layout FH1/FR1 System Diagrams PRODUCT CODES PERTRONIC SALES AND TECHNICAL SUPPORT © Pertronic Industries Ltd 0017 FH1_FR1 Technical Manual Iss 2.0 20240522...
  • Page 5 Figure 6-1: Zone M-Value Datum Figure 6-2: Sprinkler M-Value Datum Figure 7-1: FH1/FR1 PCB Layout Figure 7-2: FH1/FR1 System Connection Diagram with Indicator Device Shunt Diodes Figure 7-3: Installing Shunt Diodes in Heat Detectors Figure 7-4: Installing Shunt Diodes in Manual Call Points...
  • Page 6: Introduction

    FH1/FR1 Single Zone Fire Alarm Panel FR1 Fire Alarm FH1 Fire Alarm Note: The difference in the recommended response to a defect on the FR1 and FH1 fascias FH1/FR1 Fire Alarm PCB Figure 1-1: FR1 and FH1 Fire Alarms © Pertronic Industries Ltd...
  • Page 7: Functional Description

    Functional Description The Pertronic Residential Control Panel (FH1/FR1) is a single zone Fire Alarm system for non- brigade calling domestic applications. It has been designed in accordance with NZS4514:2009. Specifications Housing: Flush or Surface mount options Dimensions: 150 x 122 x 70...
  • Page 8: Operational Description

    The Pertronic FH1/FR1 Fire Alarm Control Panel is a compact unit designed primarily for domestic use. The Pertronic FH1/FR1 is a 2-wire system which supports on the same circuit the operation of conventional detectors, MCP’s and alerting devices. It is designed to be flush or surface mounted using the appropriate mounting housings.
  • Page 9: Outputs For Monitoring Equipment

    “normal” state once defects are cleared. Note: The defect relay is not latched.  TEST: A clean contact relay output will become active whenever the FH1/FR1 panel is in the Test mode. SYSTEM FEATURES Front Panel Indication: The front panel display consists of three indicator LEDs.
  • Page 10: Smoke Detectors

    For example, the Sprinkler (SPR) Circuit The FH1/FR1 provides a monitored circuit specifically for connecting to a sprinkler system (DBA).  The Sprinkler circuit must be terminated with a 10kΩ EOL resistor and a 1k8Ω Alarm resistor. It can detect both open and short circuit fault conditions.
  • Page 11: Hush Facility

    Operation of the Hush button essentially silences the buzzer and sounders when operated. 2.5.1 Operated for less than 0.5 seconds Any press of the Hush button for less than 0.5 seconds will be ignored by the FH1/FR1. 2.5.2 Operated for 0.5 to 5 seconds Pressing the Hush button for more than 0.5 seconds but less than 5 seconds will cause the...
  • Page 12: Operated For Greater Than 10 Seconds

    2.6.2 Exiting Test Mode To exit the TEST mode press and hold the HUSH key until a double beep is heard. The FH1/FR1 will now reset and return to the Normal state providing that no defects or alarms are present.
  • Page 13: Mains On /Off Switch

    2.11.2 Historic Defects Historic Defects are indicated in addition to current defects when the FH1/FR1 is in TEST mode. Defects are indicated by a “long flash” position code which is shown in the table below. NOTE: The historic defect information is cleared each time service personnel exit the TEST mode.
  • Page 14: Table 2-2: Defect Identification

    Multiple defects are indicated by more than one position code on the appropriate Defect NOTE: The flashing of the LEDs observed during start-up has no relationship to Defect coding. © Pertronic Industries Ltd 0017 FH1_FR1 Technical Manual Iss 2.0 20240522...
  • Page 15: Detector Compatibility

    Smoke Detectors draw a small monitoring current, which places a limit on the number of these devices that can be connected to the detector circuit. Pertronic Indicating Heat Detectors and Indicating Manual Call-Points draw minimal monitoring current so there is a higher limit on the number of these devices that can be connected to the detector circuit.
  • Page 16: Zone Loading Examples

    3 x 12 mA 36 mA 4 x IHDB-3 4 x 5 mA 20 mA 4 x PS1 4 x 10 mA 40 mA Total Zone Load 126 mA © Pertronic Industries Ltd 0017 FH1_FR1 Technical Manual Iss 2.0 20240522...
  • Page 17: Resetting After Activation

    Press HUSH ≥ 5 seconds to attempting to reset panel. exit Test Mode. (Sprinkler System must be restored to Normal for a reset to occur). Table 4-2: Panel Reset (Service personnel) © Pertronic Industries Ltd 0017 FH1_FR1 Technical Manual Iss 2.0 20240522...
  • Page 18: Test Mode

    TEST MODE The FH1/FR1 system provides a Test Mode for the use of service personnel. When the unit is in this mode the following functionality is provided:  Operation of the Test Relay to indicate that the Alarm system is being serviced ...
  • Page 19: Exiting The Test Mode

    The system will automatically exit Test Mode after 5 minutes or by pressing the HUSH button for at least 5 seconds. The Normal, Defect and Alarm LED’s will flash while the system is returning to Normal operating mode. © Pertronic Industries Ltd 0017 FH1_FR1 Technical Manual Iss 2.0 20240522...
  • Page 20: Fh1/Fr1 M-Value Datum

    FH1/FR1 M-VALUE DATUM ZONE 1 Figure 6-1: Zone M-Value Datum © Pertronic Industries Ltd 0017 FH1_FR1 Technical Manual Iss 2.0 20240522...
  • Page 21: Sprinkler (Spr)

    SPRINKLER (SPR) Figure 6-2: Sprinkler M-Value Datum © Pertronic Industries Ltd 0017 FH1_FR1 Technical Manual Iss 2.0 20240522...
  • Page 22: Diagrams

    DIAGRAMS FH1/FR1 Main Board Layout Figure 7-1: FH1/FR1 PCB Layout © Pertronic Industries Ltd 0017 FH1_FR1 Technical Manual Iss 2.0 20240522...
  • Page 23: Fh1/Fr1 System Diagrams

    FH1/FR1 System Diagrams Figure 7-2: FH1/FR1 System Connection Diagram with Indicator Device Shunt Diodes © Pertronic Industries Ltd 0017 FH1_FR1 Technical Manual Iss 2.0 20240522...
  • Page 24: Figure 7-3: Installing Shunt Diodes In Heat Detectors

    Figure 7-3: Installing Shunt Diodes in Heat Detectors Indicating Manual Call-Point Figure 7-4: Installing Shunt Diodes in Manual Call Points © Pertronic Industries Ltd 0017 FH1_FR1 Technical Manual Iss 2.0 20240522...
  • Page 25: Product Codes

    Description of Changes Author Issue 1.0 July 2013 First Issue Not Released Issue 1.1 Aug 2013 To cover both models Changes to cover both FH1 and FR1 models. Added zone loading examples. Issue 1.2 Mar 2016 Minor changes Miscellaneous changes for 1.3 Specification;...
  • Page 26: Pertronic Sales And Technical Support

    PERTRONIC SALES AND TECHNICAL SUPPORT New Zealand Pertronic Industries Limited Head Office, Wellington Auckland 17 Eastern Hutt Road 3 Gloucester Park Road Wingate Onehunga Lower Hutt Auckland 1061 Phone +64 4 5673229 Phone +64 9 633 0226 sales@pertronic.co.nz auckland@pertronic.co.nz tech@pertronic.co.nz...