Pertronic SYSTEM SENSOR FL0111E Installation And Maintenance Manual

Advertisement

Quick Links

DESCRIPTION
The FAAST LT Series is part of the Fire Alarm
Aspiration Sensing Technology® (FAAST) family.
FAAST is an advanced fire detection system for use
where early warning and very early warning are a
requirement. The system continuously draws air from
the controlled environment through a series of sampling
holes to monitor the environment for smoke particulate.
The FL01 Series is the stand-alone (relay) version of
the FAAST LT range, connected with the Fire Panel or
other monitoring system using clean-contact relays.
The FL01nnE is available in 3 different models each, 6
models total:
FL0111E - has single channel capability with one
laser smoke detector.
FL0112E - has single channel capability with two
laser smoke detectors in a common
chamber for coincidence detection.
FL0122E - has two channel capability with two laser
smoke detectors in separate chambers,
one detector per channel.
This guide provides information for mounting and basic
installation using the unit's default factory settings.
For more advanced information refer to:
I56-3888-001P FAAST LT PipeIQ Configuration Guide.
SPECIFICATIONS
Environmental Ratings
Temperature:
Relative Humidity:
IP Rating:
Mechanical:
Exterior Dimensions:
Wiring:
Maximum Single Pipe Length: 100m
Maximum Number of Holes:
Pipe Spec (EN54-20 Compliance): to EN61386
Outside Pipe Diameter:
Shipping Weight:
© Pertronic Industries Ltd
FIRE ALARM ASPIRATION SENSING TECHNOLOGY®
INSTALLATION AND MAINTENANCE GUIDE
STAND-ALONE FAAST LT : MODELS FL0111E, FL0112E AND FL0122E
o
o
-10
C to 55
C
10% to 93% (non-cond)
IP65
403 x 356 x 135mm
2
0.5mm
to 2.0mm
(Classes A, B & C)
See Table 1A
(Crush 1, Impact 1, Temp 31)
25mm or 27mm (nom.)
6.5kg (incl. detectors)
1
Colour Code Key: (refer to back page)
Black:
applies to both FL01nn and FL20nn Series
Blue:
refers to Important Settings which should be
verified
Figure 1: Dimensions and Knock-Outs
PARTS LIST
Description
FAAST LT Unit
Mounting Bracket
3-pin Terminal Block
4-pin Terminal Block
2-pin Terminal Block
Ω EOL Resistor
47K
USB Cable
Front Panel Labelling Pack
USB Memory Stick with documents
FAAST Carton Contents Guide
Important Note
Aspirating Smoke Detectors supplied and installed
within the EU must conform to the EU Construction
Products Directive (89/106/EEC) and the related
European Product Standard EN 54-20. FAAST LT has
been tested and certified to ensure that it conforms to
the necessary Standards, but strict adherence to this
i
nstruction guide is advised to ensure that the
installation meets the requirements of the CPD
Directive.
Electrical Characteristics
Voltage Range: 18.5 - 31.5 V
Supply Current: @ 24V
1 Channel:
2 Channel:
Fan Speeds:
2
max
FAAST LT Stand-Alone Installation & Maintenance Guide Iss 1.0, 201701
356 mm
, Nominal = 24V
DC
o
, 25
C - excludes Sounders
DC
170mA (typ), 360mA (max)
270mA (typ), 570mA (max)
Min = 1
Typ = 5
Max=10
44 mm
56 mm
135 mm
Quantity
1
1
6
1
3
2
1
1
1
1
DC

Advertisement

Table of Contents
loading

Summary of Contents for Pertronic SYSTEM SENSOR FL0111E

  • Page 1 See Table 1A Pipe Spec (EN54-20 Compliance): to EN61386 (Crush 1, Impact 1, Temp 31) Outside Pipe Diameter: 25mm or 27mm (nom.) Shipping Weight: 6.5kg (incl. detectors) © Pertronic Industries Ltd FAAST LT Stand-Alone Installation & Maintenance Guide Iss 1.0, 201701...
  • Page 2: Section A : Physical Installation

    OUTER DIMENSION OF UNIT 212 mm 144 mm * Minimum clearance required from hinges to open door = 35 mm. Figure 6: Fasten the mounting bracket to the wall © Pertronic Industries Ltd FAAST LT Stand-Alone Installation & Maintenance Guide Iss 1.0, 201701...
  • Page 3 6: 4 x 4mm, 2 x 5mm Including End Hole 2 x 6mm PLUS 6mm Non-Sensing End Hole 3: 1 x 5mm, 2 x 6mm Including End Hole © Pertronic Industries Ltd FAAST LT Stand-Alone Installation & Maintenance Guide Iss 1.0, 201701...
  • Page 4 POWER AND ALARM CONNECTIONS USB PORT EARTH BAR MOUNT SENSOR COVER POSITION FOR TEST MAGNET POSITION FOR TEST MAGNET Figure 10: Inside the Detector © Pertronic Industries Ltd FAAST LT Stand-Alone Installation & Maintenance Guide Iss 1.0, 201701...
  • Page 5 FAAST LT Conventional Interface (FAAST-LTIF): refer to 0734-FAAST LT Conventional Interface Installation Note Overview: allows stand-alone FAAST detectors to be directly connected to Zone circuits of a Pertronic Loop Responder, F16e or F4 conventional panel. Alarm and Defect conditions are signaled on the...
  • Page 6: External Reset

    Using Default Settings 1. Connect a suitable 24V supply (eg Pertronic AUX24V/1.3PSU-BLK) to pins 1 and 2 on Terminal T1 (refer to Table 2) 2. Check the voltage at the connector. Make sure it is within the required voltage range.
  • Page 7 Check pipe network for breaks or leaks When simultaneous Alerts/Faults occur on the same LED, priority order is: ON (Highest), 1 blink, 2 blinks, 3 blinks (Lowest) © Pertronic Industries Ltd FAAST LT Stand-Alone Installation & Maintenance Guide Iss 1.0, 201701...
  • Page 8 The system alarm response can be tested for functionality using smoke. The choice of smoke source is dependent on the installation but Pertronic industries recommends the use of a Smoke Pen (PN: SMOKEPEN) In all cases the smoke must be present for the duration of the test.
  • Page 9: Laser Safety Information

    The detector contains a Class 1 laser product. Radiation emitted inside the smoke sensor is completely contained within its housings and protective covers during all phases of operation. © Pertronic Industries Ltd FAAST LT Stand-Alone Installation & Maintenance Guide Iss 1.0, 201701...
  • Page 10: Section B : Connecting To Faast Lt From Pipeiq

    Right click the device and select Send Configuration to a new detector or a detector which is being updated ii. b) ii. above. Right click the device and select Get Configuration for an existing detector being maintained © Pertronic Industries Ltd FAAST LT Stand-Alone Installation & Maintenance Guide Iss 1.0, 201701...
  • Page 11: Section C : Configuring Faast Lt In Pipeiq

    (ii) Flow Rate: confirm the flow(s) for each channel to verify they match the calculated values and to identify variations resulting from environmental factors – AHU operation, doors opening and closing, etc. © Pertronic Industries Ltd FAAST LT Stand-Alone Installation & Maintenance Guide Iss 1.0, 201701...
  • Page 12  No: Alarm is set when both the sensors are in the Alarm condition d) Save to implement the changes. To configure the Advanced parameters, refer to Advanced Configurable Parameters © Pertronic Industries Ltd FAAST LT Stand-Alone Installation & Maintenance Guide Iss 1.0, 201701...
  • Page 13 Auxiliary Relay set Select to trigger the activation of the auxiliary relay due to power restart alert on Power Restart Alert: d) Save to implement the changes. © Pertronic Industries Ltd FAAST LT Stand-Alone Installation & Maintenance Guide Iss 1.0, 201701...
  • Page 14 None: Select to specify none of the events FAAST LT Specify the Disable period used by the device Disabling Time: d) Save to implement the changes © Pertronic Industries Ltd FAAST LT Stand-Alone Installation & Maintenance Guide Iss 1.0, 201701...
  • Page 15 Click Apply to implement the changes e) Click OK. The main page appears Note: Click Cancel to return to the main page without implementing changes © Pertronic Industries Ltd FAAST LT Stand-Alone Installation & Maintenance Guide Iss 1.0, 201701...
  • Page 16 - functionality of a FAAST detector with an F16 is limited because of the restrictions of the F16 in Apartment mode BELL FIRE Apartment Bell Brigade Fire Zone Latch Clear Link Link Mode relay relay Smoke Ext BCO Reset Heat © Pertronic Industries Ltd FAAST LT Stand-Alone Installation & Maintenance Guide Iss 1.0, 201701...
  • Page 17: Section D : Monitoring Faast Lt Using Pipeiq

    The Fan 1 speed rate is checked and the change in Flowrate 1 is displayed iii. Click Stop Note: Repeat Steps i. through iii. to set the speed for Channel 2 © Pertronic Industries Ltd FAAST LT Stand-Alone Installation & Maintenance Guide Iss 1.0, 201701...
  • Page 18 Click Monitoring on the left pane. b. Select the device to set the actions. The Actions tab appears on the right pane. c. Click Reset to reset the device © Pertronic Industries Ltd FAAST LT Stand-Alone Installation & Maintenance Guide Iss 1.0, 201701...
  • Page 19  the Report may be saved in one of three formats:  *.pdf  *.xls spreadsheet  *.doc document An xls spreadsheet allows the events to be sorted and edited © Pertronic Industries Ltd FAAST LT Stand-Alone Installation & Maintenance Guide Iss 1.0, 201701...
  • Page 20: Section E : System Test And Commissioning

    Fire signal Alarm thresholds and detector sensitivity settings to give required sampling point sensitivity. • Alarm and Fault delay periods. • Airflow parameters. • any other defined parameters. © Pertronic Industries Ltd FAAST LT Stand-Alone Installation & Maintenance Guide Iss 1.0, 201701...
  • Page 21 The system Alarm response MUST be tested for functionality using smoke the choice of smoke source is dependent on the installation - Pertronic Industries recommends the use of a Smoke Pen (PN: SMOKEPEN). Aerosol smoke is not recommended as it may leave residue inside the pipe...
  • Page 22 Important Settings which should be verified. While all settings are important, many can justifiably remain as the default value, but items in Blue should be checked © Pertronic Industries Ltd FAAST LT Stand-Alone Installation & Maintenance Guide Iss 1.0, 201701...
  • Page 23: Section F : Faast Lt System Validation Form

    Outputs: Alarm Outputs Verified: Yes / No Fault Outputs Verified Yes / No Isolate Function Verified Yes / No Comments: Signatures: Customer: Commissioning Agent: Date: Date: © Pertronic Industries Ltd FAAST LT Stand-Alone Installation & Maintenance Guide Iss 1.0, 201701...