Chase Installations - Desa ICBO# 3507 Owner's Operation And Installation Manual

42" and 50" wood burning masonry fireplace
Table of Contents

Advertisement

VenTing inSTallaTion
Continued
Storm
Collar
Flashing
Cone
Nail Only
Outer
Perimeter
of Flashing
Underlap
Shingles
at Bottom
Figure 13 - Flashing Installation
Installing Flashing on a Metal Roof
When installing the flashing on a metal roof, it is
required that putty tape be used between the flash-
ing and the roof. The flashing must be secured to
the roof using #8 x 3/4" screws and then sealed
with roof coating to prevent leakage through the
screw holes. A roof coating must also be applied
around the perimeter of the flashing to provide a
proper seal.
Storm Collar Installation (SC2-1)
Place storm collar over pipe and slide down until
it is snug against the open edge of the flashing (see
Figure 14). Apply waterproof caulk around the
perimeter of the collar to provide a proper seal.
Chimney
Pipe
Storm
Collar
Figure 14 - Storm Collar
Terminations/Spark Arrestor
The fireplace system must be terminated with the
listed round top or chase terminations. In any case,
refer to the installation instructions supplied with
the termination.
10
Overlap
Shingles Top
and Sides Only
Waterproof
Caulk
Flashing
www.desatech.com
CAUTION: Do not seal open-
ings on the rooftop flashing. Fol-
low the installation instructions
provided with the termination
being used.
Stainless
Inner Flue
Pipe
Secure
Termination
to Outer
Pipe with 3
Screws
Overlap
Shingles (Top and Sides
of Flashing Base)
Figure 15 - Termination

CHASE INSTALLATIONS

Instructions for chase installations are included
with the chase style termination chosen. In a
multiple chase installation, be sure to provide
adequate distance between terminations to prevent
smoke spillage from one termination to another.
We suggest that terminations be separated at least
24" center to center and stacked at a vertical height
difference of 18" (see Figure 16, page 11).
Note: If a decorative shroud is to be installed,
contact the manufacturer for specifications.
4" Min.
4" Min.
Figure 16 - Multiple Chase Installation
RTL-10D
Level of
Flue Gas
Outlet
Waterproof
Caulking
Storm
Collar
Flashing
Underlap
Shingles
18"
Min.
Typ.
109493-01K