Unico M3036B 1 Series Installation Manual

Air handler unit

Advertisement

Quick Links

The information on the following pages is to help the in-
staller save time, provide the best possible installation and
ensure continuous trouble-free operation.
These instructions apply to the Unico M-Series air han-
dler units. For heat pump coils, refer to Bulletin 30-24 for
additional instructions. Installation instructions for the air
distribution system are covered in Bulletin 30-05. Before
beginning any installation a detailed system layout must
be done in accordance with the System Sizing and Layout
Procedure, Bulletin 40-40 and the Component Layout In-
structions, Bulletin 40-30.
Do not attempt to install or startup unit without first read-
ing and understanding the appropriate sections in this
manual.
Before operating, be sure the unit is properly grounded.
Installation should be in accordance with all local codes
and regulations and with the National Board of Fire Un-
derwriters regulations. In case of conflict, local codes take
precedence.
All electrical wiring should be in accordance with the lat-
est edition of the National Electrical Code and all local
codes and regulations. The unit is safety certified to UL
1995 and listed with ETL.
Always install a secondary drain pan when an overflow of
condensate could cause damage.
This manual does not always include the latest revision
letter when referring to UPC part numbers. Refer to the
latest Price List and Spec Sheets for the current UPC re-
vision letter. For example, in UPC-00x the 'x' indicates
the latest revision.
The Unico System is a complete indoor comfort system
that includes an indoor air handling unit and small duct
system. The air handler and duct system were designed to
operate together to provide the proper airflow in every in-
stallation. The conditioned air is supplied through a series
of 2-inch ducts as a stream of air that entrains and mixes
the room air. This process of aspiration produces a more
even temperature distribution in the room.
The Unico 'M' Modular Series air-handling units consist
of various modules that are easily latched together. The
modules can be arranged in a vertical-up-flow, vertical-
counter-flow and horizontal-flow configuration. They can
be combined as a heating-only, cooling-only, or heating
and cooling air handler unit. See Fig. 1.

Advertisement

loading
Need help?

Need help?

Do you have a question about the M3036B 1 Series and is the answer not in the manual?

Questions and answers

Summarization of Contents

GENERAL
SCOPE
Defines the applicability and scope of the installation instructions.
NOTICE TO INSTALLER AND EQUIPMENT OWNER
Important instruction for installers and owners to retain the manual.
GENERAL PRECAUTIONS AND SAFETY TIPS
Provides essential safety guidelines and precautions for installation.
PART NUMBERS
Explains how to refer to the latest revision letters for part numbers.
UNIT ASSEMBLY
Anti-Frost Switch Wires
Routing and connecting anti-frost switch wires during module assembly.
Fastening Modules Together
Describes the process of connecting and securing air handler modules.
Horizontal Installations
Specific considerations for assembling modules in a horizontal configuration.
VERTICAL INSTALLATIONS
Vertical Plenum Module
Details the use and installation of the vertical plenum module.
ASSEMBLING THE AHU FOR VERTICAL UPFLOW
Heating-Only Systems
Specific assembly steps for heating-only configurations in vertical setups.
MOUNTING
Horizontal Platform Mounting
Describes mounting the unit on a platform for horizontal installations.
Horizontal Suspended Mounting
Details the process of suspending the unit from the ceiling or rafters.
Vertical Mounting
Guidance on mounting vertical units on platforms or floors.
PIPING
Condensate Lines
Instructions for installing and pitching condensate drain lines with traps.
Refrigerant Connections
Details on connecting liquid and vapor refrigerant lines to the coils.
Expansion Valve Installation
Steps for installing the thermostatic expansion valve for refrigerant coils.
WIRING
ST2 Control Box
Wiring instructions specific to the ST2 control box option.
EC1/EC2 Control Box
Wiring details for EC1 and EC2 control box options.
Ventilation Speed Mode
How to set and control ventilation fan speed using the thermostat.
STARTUP
Sequence of Operation
Describes how the system operates under different modes (cooling, heating, ventilation).
CHARGING THE SYSTEM
Superheat Method
Procedure for measuring superheat to verify refrigerant system charge.