Cutler-Hammer Digitrip 520M Instructions Manual

Cutler-Hammer Digitrip 520M Instructions Manual

Trip units for use only in cutler-hammer magnum and magnum ds circuit breakers
Table of Contents

Advertisement

I.L. 70C1037H03
Instructions for Digitrip Models 220, 520, 520i, 520M,
520Mi, 520MC and 520MCi Trip Units for use only in
Cutler-Hammer Magnum and Magnum DS Circuit Breakers

Table of Contents

1.1 Protection ............................................................... 4
1.2 Mode of Trip and Status Information ........................ 4
1.3 Installation and Removal .......................................... 4
1.3.1 Installation of the Trip Unit ............................ 4
1.3.2 Rating Plug Installation ................................ 4
1.3.3 Trip Unit/Rating Plug Removal ...................... 5
1.4 Wiring ..................................................................... 6
1.5 Plexiglass Cover ..................................................... 6
(520M & 520MC Models only) ................................. 6
1.6.1 Auxiliary Power ............................................ 6
1.6.2 Ground Alarm .............................................. 6
1.6.3 Ground Fault Trip ......................................... 6
1.6.4 Ground Fault Alarm ...................................... 6
1.7 Display Feature (520M family only) ......................... 7
1.8 Standards ............................................................... 7
Magnum Circuit Breakers ........................................ 7
2.1 General ................................................................... 7
2.2 Low Energy Trip Actuator ........................................ 8
2.3 Ground Fault Protection .......................................... 8
2.3.1 General ........................................................ 9
2.3.2 Residual Sensing ......................................... 9
2.3.3 Source Ground Sensing ............................... 9
2.3.4 Zero Sequence Sensing ............................... 9
2.3.6 Ground Fault Settings .................................. 9
or equal to 3200A) ................................................. 10
than 3200A) .......................................................... 10
3.0 Principles of Operation .......................................... 10
3.1 General ................................................................. 10
3.2 Trip and Operation Indicators ................................. 15
3.3 Making Current Release ........................................ 15
3.4 Zone Interlocking (520 family only) ........................ 15
4.0 Protection Settings ............................................... 20
4.1 General ................................................................. 20
4.2 Long Delay Current Setting ................................... 20
4.3 Long Delay Time Setting ....................................... 20
4.4 Short Delay Current Setting ................................... 21
4.5 Short Delay Time Setting ...................................... 21
4.6 Instantaneous Current Setting ............................... 21
4.7 Ground Fault Current Setting ................................. 22
4.8 Ground Fault Time Delay Setting .......................... 22
4.9.2 Remote Master Computer .......................... 23
5.0 Test Procedures .................................................... 24
Effective 2/2/2001
Courtesy of NationalSwitchgear.com
5.1 General ................................................................. 24
5.2 When to Test ........................................................ 24
5.3 Functional Field Testing ........................................ 24
5.3.1 Field Test Kit ............................................... 24
5.3.2 Handheld Functional Test Kit ...................... 25
5.3.2.2 Test Procedure ................................ 25
5.3.2.3 Currents .......................................... 25
5.3.2.4 Batteries ......................................... 25
Trip Units - Primary Injection ................................. 25
5.4.1 Code Requirements ................................... 25
5.4.2 Standards Requirements ............................ 25
5.4.3 General Test Instructions ........................... 25
6.0 Battery ................................................................. 26
6.1 General ................................................................. 26
6.2 Battery Check ....................................................... 26
6.3 Battery Installation and Removal ........................... 27
(Sensor Ratings and Rating Plugs) ................. 10, 27
8.0 Record Keeping .................................................... 28
9.0 References ............................................................ 28
9.2 Time-Current Curves .............................................. 28
Appendix A Zone Interlocking Examples ....................... 32
Appendix B Troubleshooting Guide ................................ 34
Connection Diagram .............................................. 36
WARNING
DO NOT ATTEMPT TO INSTALL OR PERFORM
MAINTENANCE ON EQUIPMENT WHILE IT IS
ENERGIZED. DEATH OR SEVERE PERSONAL INJURY
CAN RESULT FROM CONTACT WITH ENERGIZED
EQUIPMENT. ALWAYS VERIFY THAT NO VOLTAGE IS
PRESENT BEFORE PROCEEDING. ALWAYS FOLLOW
SAFETY PROCEDURES. CUTLER-HAMMER IS NOT
LIABLE FOR THE MISAPPLICATION OR
MISINSTALLATION OF ITS PRODUCTS.
WARNING
OBSERVE ALL RECOMMENDATIONS, NOTES, CAU-
TIONS, AND WARNINGS RELATING TO THE SAFETY
OF PERSONNEL AND EQUIPMENT. OBSERVE AND
COMPLY WITH ALL GENERAL AND LOCAL HEALTH
AND SAFETY LAWS, CODES, AND PROCEDURES.
I.L. 70C1037H03
Page 1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Digitrip 520M and is the answer not in the manual?

Questions and answers

Summarization of Contents

Digitrip Trip Unit Overview and Features
Protection Functions and Status Indicators
Details the protection functions, trip modes, and status indicators of Digitrip units.
Installation, Wiring, and Accessories
Covers unit installation, wiring, plexiglass cover, and optional modules like Ground Alarm.
Magnum Circuit Breaker Operation and Ground Fault Protection
Low-Energy Trip Actuator and Current Sensing
Explains the low-energy trip actuator and the role of current sensors in breaker operation.
Ground Fault Protection Schemes
Details different sensing modes for ground fault protection.
Digitrip Operation Principles and Zone Interlocking
Trip Indicators and Making Current Release
Details trip indicators, operation status, and the making current release function.
Zone Interlocking Functionality Explained
Explains the Zone Selective Interlocking (ZSI) feature and its application.
Digitrip Protection Settings Configuration
Long Delay and Short Delay Settings
Covers settings for Long Delay and Short Delay current and time parameters.
Instantaneous and Ground Fault Settings
Details settings for Instantaneous and Ground Fault protection functions.
INCOM Communication Setup
Instructions for configuring INCOM communications for 520MC models.
Digitrip Trip Unit Testing Procedures
General Testing Precautions and Scheduling
Safety warnings and guidelines for testing trip units before or during operation.
Functional Field Testing Methods
Procedures for performing functional tests using approved test kits.
Ground Fault Performance Testing Requirements
Details on code requirements and general instructions for ground fault testing.
Trip Unit Battery and Testing Procedures
Battery Function, Checks, and Replacement
Explains the role of the battery, how to check its status, and replacement.
Current Test Connections
Diagrams for conducting single phase current tests with the breaker removed.
Frame Ratings, Rating Plugs, and Record Keeping
Battery Installation and Removal
Step-by-step guide for replacing the 3-volt lithium cell battery.
Frame Ratings and Rating Plug Selection
Defines frame ratings and the basis for choosing rating plugs and trip unit settings.
Record Keeping and Technical References
Trip Function Record Keeping Forms
Forms and guidelines for recording trip function settings and operation.
Time-Current Curve References
Lists time-current curve references for specific trip unit models.
Appendices: Interlocking, Troubleshooting, and Diagrams
Appendix A: Zone Interlocking Examples
Illustrates zone interlocking scenarios and coordination examples.
Appendix B: Troubleshooting Guide
Provides a guide to diagnose and resolve common issues with the trip unit.
Appendix C: Breaker Master Connection Diagram
Shows the typical master connection diagram for circuit breakers and trip units.

Table of Contents