Installation Instructions - Honeywell HP400ULM Product Installation Document

Access control power supply/charger with power distribution controller

Advertisement

– Each PTC protected output rated 2.5A @ 23C with a maximum of 2.0A @ 49C.
– Automatic Yellow LED status indication of activated PTC.
– Test push button lights Yellow LED's to verify their operation.
– Red LED for power on indication.
Fire Alarm Control Panel Input
– Polarity reversing input.
– Normally open (NO) or normally closed (NC) supervised input with 2.2K Ohm (EOL) resistor.
– Engineering Reset (Optional) normally open (NO) or normally closed (NC) input with 2.2 K Ohm (EOL) resistor.
Alarm Outputs
– Alarm outputs are Fail Safe
– When FACP activation occurs dry contacts activated.
– Green LED indication when FACP is activated.
– Dry contacts output for power failure to the HPMOM6.
Board Dimensions: 5.3" L x 3.5" W x 1.0" H (13.46 cm L x 8.89 cm W x 2.54 cm H).

3 Installation Instructions

1.
Mounting
The power supply should be installed in accordance with all Governing National Electrical and Local Codes. Mount the
power supply securely in the desired location using the four (4) mounting holes.
2.
Power Supply Input Connection
Before connecting power review the entire wiring diagram for correct installation (see Fig. 1). With the AC power
disconnected, connect 120VAC to the Fuse Block as follows; L=Black (HOT), N=WHITE (Neutral), G=GREEN
(Ground). Select the output voltage 12VDC or 24VDC using Jumper J1 of the Power Board J1 OFF=12VDC, J1
ON=24VDC. Voltage is Factory set and Re-Adjusting will void Warranty.
3.
Output Connections
There are 6 outputs selectable together as Switched Normally Open (NO) or Switched Normally Closed (NC). There are 2
possible output type connections in either case connect device negative to Neg terminal on HPMOM6.
1.) For Fail Safe operation connect device positive to DC STANDBY OUTPUT (+) on HPMOM6. DC power is
present in normal condition and will switch OFF when the FACP is triggered. Fail Safe operation devices such as
Magnetic Locks should be connected to this output.
2.) For Fail Secure operation connect device positive to DC ALARM OUTPUT (+) on HPMOM6. DC power is not
present in normal condition and will switch ON when the FACP is triggered. Fail Secure operation devices such as
Door Strikes should be connected to this output.
4.
Fire Alarm Interface
Normally Open (NO), Normally Closed (NC) input or polarity reversal (Rev. Volt) input from the FACP are available to
trigger the HPMOM6 operation. Connect the positive (+) and negative (-) from the FACP to the "REV. VOLT" terminals
observing polarity, (polarity is referenced in alarm condition) or connect the NO or NC from the FACP output to the
"FIRE INTRFC" terminals. Install the 2.2K Ohm (EOL) resistor provided at the FACP as shown in Fig 1 to supervise this
connection.
5.
Engineering Reset Input
This option is available when the jumper JL is removed. This will cause the HPMOM6 to latch upon receiving an alarm
condition from the FACP. With this option in place and when the FACP resets, the unit will only reset by activating the
"RESET" circuit.
a) JL ON will cause the unit to follow the status of the FACP. Connect 2.2K Ohm resistor to the "RESET"