Download Print this page

Inovonics EN5061 Installation And Operation Manual

Surface mount locator

Advertisement

Quick Links

EN5061 Surface Mount Locator
Installation and Operation Manual
1 Overview
When deployed as part of an Inovonics mobile duress system, EN5061
surface mount locators help determine the location of mobile duress
pendants for improved emergency response. When a mobile duress
pendant is activated, the alarm is sent through the Inovonics EchoStream
system, and a Bluetooth® message is simultaneously sent to any locators
within range. Every locator that hears the message then delivers the
Bluetooth signal strength information to the Inovonics mobile duress
application, which determines location based on the highest signal strength
received, and distributes location notifications per predefined user
parameters.
1.1
Inovonics Contact Information
For product and installation videos visit us at
www.inovonics.com/videos or use the QR
code below.
If you have any problems with this procedure, contact Inovonics technical
services:
• E-mail: support@inovonics.com.
• Phone: (800) 782-2709; (303) 939-9336.
1.2 EN5061 Surface Mount Locator
B
Figure 1 EN5061 surface mount locator
A Power LED B Mounting screws
6.26.23 357-00075-01 Rev A © Inovonics, 2023 - www.inovonics.com
A
B
2 Installation and Startup
2.1 Installation Notes
• These products are designed to be maintained by professional
security technicians from Inovonics factory-trained partners.
• Products are tested for indoor use.
• All products should be manually tested weekly.
2.2 Install the EN5061 Surface Mount Locator
Note: Surface mount locators must be registered with the site prior to
removal from packaging and mounting. Refer to the Inovonics Mobile
Duress User Manual for registration instructions, and contact Inovonics
technical services if you require training.
Installation of the EN5061 requires a metal 4" square, 2 1/8" deep (or
greater) cut-in box be pre-installed in the wall. For EN5061 installation, the
box must have mounting screw-holes at diagonally opposite positions, with
one in the upper left and one in the lower right.
Inovonics recommends the Southwire 4" square box, part number 52171-3/
4-1, for new construction, and the Southwire 4" old work cut-in, part number
52181-OW, for retrofit installations.
Power cabling for either 12-24VAC 50/60 Hz or 12-24VDC must be present
and routed to the inside of the cut-in box, with stripped pigtails per local
electrical code. Each EN5061 consumes 670mW maximum.
1. Install the cut-in box per manufacturer's instructions and local building
and electrical codes.
Note: If installed five feet or lower on the wall, orient the unit with the arrow
embossed on the inside of the cover facing up; if installed above five feet
on the wall, orient the unit with the arrow facing down.
2. Connect power cabling to either power terminal pair.
Figure 2 Connect power cabling
• If using DC power, make sure to connect cabling to positive and
negative, as indicated above the terminals.
Note: If you are planning to daisy chain the power, you can use the second
pair of screw terminals to attach to the power cable to the next unit.
3. Use the supplied tamper-resistant Torx 8-32-3/4" flat head screws to
mount the EN5061 in the cut-in box.
• Mount the EN5061 with the arrow embedded on the back side of the
cover pointing up.
• Be careful not to overtighten screws or flex cover.
4. Apply power.
5. Ensure the surface mount locator's power LED lights solid green.
+
Power terminal
-
pair 1
+
Power terminal
pair 2
-

Advertisement

loading
Need help?

Need help?

Do you have a question about the EN5061 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Inovonics EN5061

  • Page 1 A Power LED B Mounting screws mount the EN5061 in the cut-in box. • Mount the EN5061 with the arrow embedded on the back side of the cover pointing up. • Be careful not to overtighten screws or flex cover.
  • Page 2 2015/863. FCC ID: HCQBWA02. IC: 2309A-BWA02. HVIN: 00070-04. Note: Inovonics supports recycling and reuse whenever possible. Please recycle these parts using a certified electronics recycler. 4 Regulatory Compliance 4.1 Television and Radio Interference This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules.