TABLE OF CONTENTS NOTE TO INSTALLER ........................2 INSTALLER SUPPLIED ITEMS ..................... 3 PARTS INCLUDED WITH UNIT ..................... 3 ITEMS FOR CONSIDERATION ..................... 3 UNIT INSTALLATION ........................5 Indoor installation ........................6 Outdoor Installation ........................9 Main Power Wiring ........................11 Controls Wiring ........................
Installation and Maintenance Manual Report shipping damage to carrier IMMEDIATELY. Check units and box exterior for damage. NOTE TO INSTALLER This manual is to aid the qualified HVAC contractor in the installation and maintenance of this mini-split system. Please read and understand these instructions prior to installing the unit, failure to comply with these instructions may result in improper installation, operation and maintenance, possibly resulting in fire, electrical shock, property damage, personal injury or death.
INSTALLER SUPPLIED ITEMS The following items are necessary for the installation of the ductless mini splits. Refrigerant line set: Flared connection only, suitable for R410A with both lines insulated, max length for connection see page 4 or specification pages 17 to 20. ...
Page 5
EXCEEDED. Determine how the lineset piping, wiring and condensate hose is to be run. Installation (CONT’D). Indoor / Outdoor Unit Max Line Set Run Max Vertical Lift Line Sizes 1/4” Liquid – 3/8” Suction WM6H424ZMI / SZ9H424ZMO 82 Feet 33 Feet 1/4” Liquid – 3/8” Suction WM9H424ZMI / SZ9H424ZMO 82 Feet 33 Feet 1/4”...
Installation (CONT’D). Wall Bracket: Mounting the outdoor unit on the wall is common; this allows mounting the outdoor unit closer to the indoor unit and also for a convenient installation. We offer wall brackets (Our Catalog# BR-440L for up to 440 lbs.) as an accessory. UNIT INSTALLATION CAUTION! Follow Instructions, failure to follow instructions may cause possible malfunction and void any warranty.
Choose an area where the wall is plumb and determine how to best run the unit interconnects. 5” from wall 5” from wall Optimum 8 ft plus from floor ALL VIEWED FROM FRONT SIDE For model: WM6H424ZMI For models: WM9H424ZMI, WM12H424ZMI 950-0285 - 6 - April 18, 2022...
Page 8
For models: WM18H424ZMI, WM24H424ZMI Ensure no obstacles to airflow are directly in front of the unit, for a minimum of 12 ft for 9,000 / 12,000 Btu/h units and 16 ft. for 18,000 / 24,000 Btu/h units. Do not install the indoor unit in areas exposed to high humidity (RH of 80% plus), direct sunlight, direct heat from stoves or other devices.
Page 9
Installation (CONT’D) Step 5 Prepare Unit Line Set Connections Rotate refrigerant line stubs set gently through 90° (if mounting on an outside wall). For other line set configurations align the stubs as required. Condensate Hose Hose connection is sized to accept a 5/8'' OD or 1/2'' ID clear plastic hose to then extend to building drain. Connect it to the gray condensate line coming from the indoor unit.
(CONT’D) Step 6 Install unit on mounting bracket. Feed the line set stubs/condensate hose/wiring connections through the 3'' hole. Installation can be made easier by lifting the indoor unit and inserting a cushioning material (spacer) between indoor unit and the wall. Hook the top of the indoor unit to the top of the bracket (2 or 3 places) and once hooked, gently let it swing down and then push the lower portion of the indoor unit against the bracket until it snaps into the bracket.
Page 11
Installation (CONT’D) ● If the drain joint comes with a rubber seal (see Fig. A), do the following: 1. Fit the rubber seal on the end of the drain joint that will connect to the outdoor unit. 2. Insert the drain joint into the hole in the base pan of the unit. 3.
Installation (CONT’D) Step 10 Evacuation After connecting the indoor and outdoor units, evacuate the air from the line set and the indoor unit. Gauges can now be attached to the service port - SERVICE PORTS HAVE A 5/16” CONNECTION TO GAUGES.
Installation (CONT’D). Outdoor Unit Wiring Diagram is located on the inside of the wire cover on the right side. Valve Cover Wiring Diagram Green wire for GND Note: 1. When connecting terminals wire color is not important, except green, which should always be used for GND. 2.
UNIT START UP The system can now be opened to allow the refrigerant charge in the outdoor unit to be released into the line set. The service valves require a 5 mm Allen wrench to undo the valve stems. Remove brass caps from the service valves.
PRESSURE CURVES NOTE: After installation, the pressure reading should be as indicated below. Take from the service port, the pressure under the outdoor temperature should match the charts readings. Cooling Chart Outdoor Temperature It is recommended to record and charge when the outdoor temperature is within the chart temperatures. 950-0285 - 15 - April 18, 2022...
Heating Chart outdoor Temperature It is recommended to record and charge when the outdoor temperature is within the chart temperatures. 950-0285 - 16 - April 18, 2022...
TROUBLESHOOTING Indoor Unit Error Code Display Display INFORMATION Defrost – Normal operation Active clean – Normal operation Filter replacement reminder (power on display for 15 seconds) Freeze protection under 46ºF – Normal operation Forced cooling – Normal operation AP mode of WiFi connection Remote switched off EH 00/EH 0A Indoor unit EEPROM parameter error...
THE IMPORTANCE OF DEEP VACUUM The purpose of a vacuum pump is to remove moisture and air from an A/C-R system. Modern systems are built tighter and charges are more critical. That means these systems have a greater sensitivity to moisture and other contaminants, making thorough evacuation more important than ever before.
WARRANTY International Refrigeration Products warrants the accompanying split air conditioner or heat pump system to be free of defects in material and workmanship for the applications specified in the operation manual and installation manual for a period of two (2) year on parts and seven (7) years on compressor, valid from the date of original retail purchase in the United States or Canada.