MINI-SPLIT INSTALLATION
AND MAINTENANCE MANUAL
WM6H424ZMI
WM9H424ZMI
WM12H424ZMI
WM18H424ZMI
WM24H424ZMI
950-0285
HEAT PUMP
SZ12H424ZMO
SZ18H424ZMO
SZ24H424ZMO
SZ9H424ZMO
SZ9H424ZMO
April 18, 2022

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the WM6H424ZMI and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Sea Breeze WM6H424ZMI

  • Page 1 International Refrigeration Products, Inc. MINI-SPLIT INSTALLATION AND MAINTENANCE MANUAL HEAT PUMP WM6H424ZMI SZ9H424ZMO WM9H424ZMI SZ9H424ZMO WM12H424ZMI SZ12H424ZMO WM18H424ZMI SZ18H424ZMO WM24H424ZMI SZ24H424ZMO 950-0285 April 18, 2022...
  • Page 2: Table Of Contents

    TABLE OF CONTENTS NOTE TO INSTALLER ........................2 INSTALLER SUPPLIED ITEMS ..................... 3 PARTS INCLUDED WITH UNIT ..................... 3 ITEMS FOR CONSIDERATION ..................... 3 UNIT INSTALLATION ........................5 Indoor installation ........................6 Outdoor Installation ........................9 Main Power Wiring ........................11 Controls Wiring ........................
  • Page 3: Note To Installer

    Installation and Maintenance Manual Report shipping damage to carrier IMMEDIATELY. Check units and box exterior for damage. NOTE TO INSTALLER This manual is to aid the qualified HVAC contractor in the installation and maintenance of this mini-split system. Please read and understand these instructions prior to installing the unit, failure to comply with these instructions may result in improper installation, operation and maintenance, possibly resulting in fire, electrical shock, property damage, personal injury or death.
  • Page 4: Installer Supplied Items

    INSTALLER SUPPLIED ITEMS The following items are necessary for the installation of the ductless mini splits.  Refrigerant line set: Flared connection only, suitable for R410A with both lines insulated, max length for connection see page 4 or specification pages 17 to 20. ...
  • Page 5 EXCEEDED. Determine how the lineset piping, wiring and condensate hose is to be run. Installation (CONT’D). Indoor / Outdoor Unit Max Line Set Run Max Vertical Lift Line Sizes 1/4” Liquid – 3/8” Suction WM6H424ZMI / SZ9H424ZMO 82 Feet 33 Feet 1/4” Liquid – 3/8” Suction WM9H424ZMI / SZ9H424ZMO 82 Feet 33 Feet 1/4”...
  • Page 6: Unit Installation

    Installation (CONT’D). Wall Bracket: Mounting the outdoor unit on the wall is common; this allows mounting the outdoor unit closer to the indoor unit and also for a convenient installation. We offer wall brackets (Our Catalog# BR-440L for up to 440 lbs.) as an accessory. UNIT INSTALLATION CAUTION! Follow Instructions, failure to follow instructions may cause possible malfunction and void any warranty.
  • Page 7: Indoor Installation

    Choose an area where the wall is plumb and determine how to best run the unit interconnects. 5” from wall 5” from wall Optimum 8 ft plus from floor ALL VIEWED FROM FRONT SIDE For model: WM6H424ZMI For models: WM9H424ZMI, WM12H424ZMI 950-0285 - 6 - April 18, 2022...
  • Page 8 For models: WM18H424ZMI, WM24H424ZMI Ensure no obstacles to airflow are directly in front of the unit, for a minimum of 12 ft for 9,000 / 12,000 Btu/h units and 16 ft. for 18,000 / 24,000 Btu/h units. Do not install the indoor unit in areas exposed to high humidity (RH of 80% plus), direct sunlight, direct heat from stoves or other devices.
  • Page 9 Installation (CONT’D) Step 5 Prepare Unit Line Set Connections Rotate refrigerant line stubs set gently through 90° (if mounting on an outside wall). For other line set configurations align the stubs as required. Condensate Hose Hose connection is sized to accept a 5/8'' OD or 1/2'' ID clear plastic hose to then extend to building drain. Connect it to the gray condensate line coming from the indoor unit.
  • Page 10: Outdoor Installation

    (CONT’D) Step 6 Install unit on mounting bracket. Feed the line set stubs/condensate hose/wiring connections through the 3'' hole. Installation can be made easier by lifting the indoor unit and inserting a cushioning material (spacer) between indoor unit and the wall. Hook the top of the indoor unit to the top of the bracket (2 or 3 places) and once hooked, gently let it swing down and then push the lower portion of the indoor unit against the bracket until it snaps into the bracket.
  • Page 11 Installation (CONT’D) ● If the drain joint comes with a rubber seal (see Fig. A), do the following: 1. Fit the rubber seal on the end of the drain joint that will connect to the outdoor unit. 2. Insert the drain joint into the hole in the base pan of the unit. 3.
  • Page 12: Main Power Wiring

    Installation (CONT’D) Step 10 Evacuation After connecting the indoor and outdoor units, evacuate the air from the line set and the indoor unit. Gauges can now be attached to the service port - SERVICE PORTS HAVE A 5/16” CONNECTION TO GAUGES.
  • Page 13: Wiring Diagram

    Installation (CONT’D). Outdoor Unit Wiring Diagram is located on the inside of the wire cover on the right side. Valve Cover Wiring Diagram Green wire for GND Note: 1. When connecting terminals wire color is not important, except green, which should always be used for GND. 2.
  • Page 14: Refrigerant Charge

    60 ft. 70 ft. 80 ft. 90 ft 100 ft 120 ft 140 ft 160 ft 0.161 0.81 1.61 3.22 4.03 5.64 7.25 8.86 WM6H424ZMI 0.161 0.81 1.61 3.22 4.03 5.64 7.25 8.86 WM9H424ZMI 0.161 0.81 1.61 3.22 4.03 5.64 7.25...
  • Page 15: Unit Start Up

    UNIT START UP The system can now be opened to allow the refrigerant charge in the outdoor unit to be released into the line set. The service valves require a 5 mm Allen wrench to undo the valve stems. Remove brass caps from the service valves.
  • Page 16: Pressure Curves

    PRESSURE CURVES NOTE: After installation, the pressure reading should be as indicated below. Take from the service port, the pressure under the outdoor temperature should match the charts readings. Cooling Chart Outdoor Temperature It is recommended to record and charge when the outdoor temperature is within the chart temperatures. 950-0285 - 15 - April 18, 2022...
  • Page 17: Heating Chart

    Heating Chart outdoor Temperature It is recommended to record and charge when the outdoor temperature is within the chart temperatures. 950-0285 - 16 - April 18, 2022...
  • Page 18: Technical Specifications

    TECHNICAL SPECIFICATIONS 6,000 and 9,000 BTU Units 246-0005, 246-0500 246-0001, 246-0500 Sea Breeze+ Indoor / Outdoor WM6H424ZMI, SZ9H424ZMO WM9H424ZMI, SZ9H424ZMO AHRI Reference Number Power supply Ph-V-Hz 208/230V, 1Ph, 60Hz 208/230V, 1Ph, 60Hz 187-253 187-253 Voltage range Capacity Btu/h 6000 (2500~11800)
  • Page 19 246-0005, 246-0500 246-0001, 246-0500 Sea Breeze+ Indoor / Outdoor WM6H424ZMI, SZ9H424ZMO WM9H424ZMI, SZ9H424ZMO Model ZKFP-13-8-4 ZKFP-13-8-4 Input Indoor fan motor 0.25 0.15 Speed (Hi/Mi/Lo) r/min 1100/810/690 1150/990/750 Indoor air flow (Hi/Mi/Lo) 247/176/141 291/194/153 Indoor noise level (Hi/Mi/Lo) dB(A) 38.5/33/20.5 40/34/23.5...
  • Page 20: 12,000, 18,000 & 24,000 Btu Units

    12,000, 18,000 & 24,000 BTU Units 246-0002, 246-0501 246-0003, 246-0502 246-0004, 246-0503 Sea Breeze+ Indoor / Outdoor WM12H424ZMI, WM18H424ZMI, WM24H424ZMI, SZ12H424ZMO SZ18H424ZMO SZ24H424ZMO AHRI Reference Number Ph-V- Power supply 208/230V, 1Ph, 60Hz 208/230V, 1Ph, 60Hz 208/230V, 1Ph, 60Hz 187-253 187-253...
  • Page 21 246-0002, 246-0501 246-0003, 246-0502 246-0004, 246-0503 Sea Breeze+ Indoor / Outdoor WM12H424ZMI, WM18H424ZMI, WM24H424ZMI, SZ12H424ZMO SZ18H424ZMO SZ24H424ZMO Model ZKFP-13-8-4 ZKFP-58-8-1-5 ZKFP-58-8-1-5 Input Indoor fan motor 0.38 0.25 0.38 Speed (Hi/Mi/Lo) r/min 1250/950/750 1120/950/700 1200/1080/600 Indoor air flow (Hi/Mi/Lo) 291/194/153 531/459/382...
  • Page 22: Troubleshooting

    TROUBLESHOOTING Indoor Unit Error Code Display Display INFORMATION Defrost – Normal operation Active clean – Normal operation Filter replacement reminder (power on display for 15 seconds) Freeze protection under 46ºF – Normal operation Forced cooling – Normal operation AP mode of WiFi connection Remote switched off EH 00/EH 0A Indoor unit EEPROM parameter error...
  • Page 23: The Importance Of Deep Vacuum

    THE IMPORTANCE OF DEEP VACUUM The purpose of a vacuum pump is to remove moisture and air from an A/C-R system. Modern systems are built tighter and charges are more critical. That means these systems have a greater sensitivity to moisture and other contaminants, making thorough evacuation more important than ever before.
  • Page 24: Warranty

    WARRANTY International Refrigeration Products warrants the accompanying split air conditioner or heat pump system to be free of defects in material and workmanship for the applications specified in the operation manual and installation manual for a period of two (2) year on parts and seven (7) years on compressor, valid from the date of original retail purchase in the United States or Canada.