100-5013V
EURV-ABSS - INTELLIGENT PLATFORM SLAVE SOUNDER
GENERAL DESCIPTION
This device is a 32 tones platform sounder that emits a selected acoustic signal when the remote output of the intelligent-analogue
detector, installed on it, is activated by the control panel in case of a fire condition.
As a slave sounder this device does not need any addressing as is usually done for other analogue devices.
TONE AND VOLUME SELECTION
If you want to change the pre-set tone and volume settings you must change the settings on the DIP switches under the detector's
adaptor base of the platform sounder.
DIP switches are not directly reachable and the front adaptor base must be disassembled for performing this operation:
1. Unscrew the front base at the two points indicated in figure 1:
Figure 1
2.
Slide off a bit the
front base from the sounder
block; be careful not to put too much effort on the
connecting cables in order to avoid to torn
them off!
DIP switch is pictured in figure 2.
3. Switch over the switches using preferably the tip of a small screwdriver:
Choose the volume output level according to the environment and referring to table 1; select the
appropriate DIP switches settings (refer to figure 3).
Choose the system alarm tone from those shown on table 2 and select the appropriate DIP switch
settings (refer to figure 3).
4. Reinstall the front base onto the back sounder.
INSTALLATION STEPS
1. Feed loop cable ends through rear opening on the platform sounder assembly.
2. Fix the assembly securely either to a rear electrical box or directly to the ceiling surface.
For mounting hole positions (figure 4) use suitable round or dome crosshead screw with
narrow shank (e.g. 6 mm) screwdriver.
VOLUME OPTIONS*
Table 1
LOW - 89dB
A + B
4.5mA
MEDIUM - 91dB
A + D
5.5mA
HIGH - 94dB
C + B
9.5mA
* All sound measurements were made without the detector fitted.
EUROTECH FIRE SYSTEMS LTD - 19/20 Stratfield Park - Elettra Avenue - Waterlooville
Hampshire - PO7 7XN - United Kingdom
xxxx/xx
Figure 2
Figure 3
Figure 4
www.eurotechfire.com
SOUNDER CABLING
Terminate the loop wiring to the base terminals; please refer to figure 5's cabling scheme.
Optional remote alarm indicator cabling can be performed, but remember not to overload the detector's remote output, since the
sounder is already power supplied by it! Refer to the specific detector instructions and specifications about this important
point!
REMOTE
ALARM (+)
LOOP IN (+)
LOOP IN (-)
TECHNICAL SPECIFICATIONS
Voltage range
15 - 40Vdc
Max current load
9.5mA
Max volume @ 1m*
94dBA
32 tone range
440 - 2900Hz
Temp range
-20° to 70°C
Humidity range
5 to 95%RH
+44 (0) 203 141 0999
Figure 5
LOOP OUT (+)
REMOTE
ALARM (-)
SHIELD
LOOP OUT (-)
L20-ALBS32-1A00 (v2.0)