Download Print this page

Eurotech sygno-fi SYG-BS-B Install Sheet

Wireless sounder vad/base black white flash

Advertisement

Quick Links

Sygno-fi Wireless Sounder VAD Base Black (White Flash)
WARNINGS AND LIMITATIONS
Our devices use high quality electronic components and plastic materials that are
highly resistant to environmental deterioration. However, after 10 years of continu-
ous operation, it is advisable to replace the devices in order to minimize the risk of
reduced performance caused by external factors. Ensure that this device is only
used with compatible control panels. Detection systems must be checked, serviced
and maintained on a regular basis to confirm correct operation. Smoke sensors may
respond differently to various kinds of smoke particles, thus application advice
should be sought for special risks. Sensors cannot respond correctly if barriers exist
between them and the fire location and may be affected by special environmental
conditions. Refer to and follow national codes of practice and other internationally
recognized fire engineering standards. Appropriate risk assessment should be
carried out initially to determine correct design criteria and updated periodically.
Use only in Sygno-fi fire detection and alarm systems.
WARRANTY
All devices are supplied with the benefit of a limited 3 years warranty relating to
faulty materials or manufacturing defects, effective from the production date indicat-
ed on each product. This warranty is invalidated by mechanical or electrical damage
caused in the field by incorrect handling or usage. Product must be returned via
your authorized supplier for repair or replacement together with full information on
any problem identified. Full details on our warranty and product's returns policy can
be obtained upon request.
SYG-BS-B
Sygno-fi Wireless Sounder Base Black
SYG-BSB-23W-B
0051
22
*
DoP-SYG-BS
**
**
DoP-SYG-BSB-23W
Eurotech Fire Systems Ltd
19/20 Stratfield Park
Elettra Avenue
Waterlooville
Hampshire
PO7 7XN
United Kingdom
* SYG-BS-B
** SYG-BSB-23W-B
EN 54-3:2001+ A1:2002 + A2:2006
EN 54-25:2008
SYG-BSB-23W-B
EN 54-23:2010
Type A - for indoor use only
SYG-BSB-23W-B
C3-15 & O4.6-15 (white / high power)
C3-10 (white / low power)
8504
22
**
DoPUK-SYG-BS
DoPUK-SYG-BSB-23W

Advertisement

loading
Need help?

Need help?

Do you have a question about the sygno-fi SYG-BS-B and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Eurotech sygno-fi SYG-BS-B

  • Page 1 Ensure that this device is only used with compatible control panels. Detection systems must be checked, serviced Eurotech Fire Systems Ltd and maintained on a regular basis to confirm correct operation. Smoke sensors may...
  • Page 2 Sound diffuser Picture 1 All pictures are for product in black variant. Shown white for illustrative purpose only EUROTECH FIRE SYSTEMS LTD - 19/20 Stratfield Park - Elettra Avenue - Waterlooville www.eurotechfire.com Hampshire - PO7 7XN - United Kingdom enquiry@eurotechfire.com...
  • Page 3 DEPLOYMENT PROCEDURE The general applicable procedure for the deployment of these products is the following: 1) Select a location for the base sounder. See LOCATION SELECTION. 2) Unbox the base sounder product from its packaging. 3) Detach the battery cover from the base sounder. See BATTERY COVER. 4) Detach the wall installation plate from the device.
  • Page 4 Always install the battery cover, since it is a vital part of the anti-tampering feature. Make sure the battery cover is safely fixed, blocked and closed. EUROTECH FIRE SYSTEMS LTD - 19/20 Stratfield Park - Elettra Avenue - Waterlooville www.eurotechfire.com Hampshire - PO7 7XN - United Kingdom enquiry@eurotechfire.com...
  • Page 5 WALL INSTALLATION PLATE To detach / reinstall the wall plate to the base sounder refer to the following picture: Picture 4 Make sure that the sound diffuser cone printed on the wall plate corresponds to the acoustic alarm signal outlet of the base sounder. Drill templates on the wall plate are highlighted in the following picture: Picture 5 +44 (0) 203 141 0999...
  • Page 6 3) Insert the two supplied batteries into their device’s lodgments. Ensure that the batteries are installed properly, with their polarities matching the indications on the device. EUROTECH FIRE SYSTEMS LTD - 19/20 Stratfield Park - Elettra Avenue - Waterlooville www.eurotechfire.com Hampshire - PO7 7XN - United Kingdom enquiry@eurotechfire.com...
  • Page 7 LINKING - WAKE-UP “Wake-up” linking consists in associating one or more child devices to the Sygno-fi system altogether in a single operation. Wake-up is performed either through the SygNEX software or the SYG-W2W / SYG-CEM keyboard-screen interface; it CANNOT be done through SYG-EM devices.
  • Page 8 High * Medium-High Medium-Low Table 3 EN 54-3 approved volume Visual emission power level Switch configuration High Table 4 EUROTECH FIRE SYSTEMS LTD - 19/20 Stratfield Park - Elettra Avenue - Waterlooville www.eurotechfire.com Hampshire - PO7 7XN - United Kingdom enquiry@eurotechfire.com...
  • Page 9 Tone number Main tone designation Main tone pattern description DIP switches Silent No sound 11111 Warble Tone 800Hz for 500ms, then 1000Hz for 500ms 11101 Continuous tone 970Hz continuous tone 01011 Slow Whoop (Dutch) 500-1200Hz for 3500ms, then off for 500ms 10101 German DIN tone 1200-500Hz swept every 1000ms (1Hz)
  • Page 10 00110 800Hz continuous 10111 800Hz continuous 10011 800Hz continuous 01000 2900Hz continuous 00011 800Hz continuous 10000 Table 6 EUROTECH FIRE SYSTEMS LTD - 19/20 Stratfield Park - Elettra Avenue - Waterlooville www.eurotechfire.com Hampshire - PO7 7XN - United Kingdom enquiry@eurotechfire.com...
  • Page 11 FIXING THE BASE SOUNDER To fix the base sounder to the wall plate insert and fix the supplied screws in the holes highlighted in the following picture: Picture 7 HOST DETECTOR / PLASTIC COVER INSTALLATION If a detector is hosted, follow the setup instructions on its installation manual. Make sure the detector’s OWN battery cover is installed to avoid tamper detection events.
  • Page 12 5) Check that a normal condition persists (i.e. test smoke can stagnate in a detector’s smoke chamber causing the alarm to be triggered again). Local safety standards may require you to test these devices on a regular basis. EUROTECH FIRE SYSTEMS LTD - 19/20 Stratfield Park - Elettra Avenue - Waterlooville www.eurotechfire.com Hampshire - PO7 7XN - United Kingdom enquiry@eurotechfire.com...
  • Page 13 TECHNICAL SPECIFICATIONS * Specification Value Communication range with SYG-W2W, SYG-CEM or SYG-EM 200 m (in open space) network devices Wireless frequency band 868 MHz Number of wireless channels Radiated power 14 dBm (25 mW) Operating temperature range -10 °C to 55 °C Maximum humidity (non condensing) 95% RH Certified IP rating (EN 54)
  • Page 14 6 m coverage diameter, 4.24 m x 4.24 m (18 O1.7-6 (EN 54-23) ) square coverage Table 12 Ceiling Mounted Device Demonstration EUROTECH FIRE SYSTEMS LTD - 19/20 Stratfield Park - Elettra Avenue - Waterlooville www.eurotechfire.com Hampshire - PO7 7XN - United Kingdom enquiry@eurotechfire.com...

This manual is also suitable for: