Gas Piping - Kenmore 3314 - Power Miser 12 Owner's Manual

For potable water heating only, not suitable for space heating, not for use in mobile homes
Table of Contents

Advertisement

DRAFT HOOD
DRAFT HOOD
VENT
DRAFT
HOOD
VENT
TO OUTDOORS
OR
CHIMNEY
Be sure vent
pipe is properly
connected
to prevent
escape
of
dangerous
flue gases
which
could
cause
deadly
asphyxiation.
Chemical
vapor
corrosion
of the flue
and vent
system
may
occur
if air for combustion
contains
certain
chemical
vapors.
Spray
can
propellants,
cleaning
solvents,
refrigerator
and air
conditioner
refrigerants,
swimming
pool
chemicals,
calcium
and sodium
chloride,
waxes,
bleach
and
process
chemicals
are typical
compounds
which
are potentially
corrosive.
Gas Piping
FIGURE17.
The vent
pipe from the water
heater
must be no less than
the
diameter
of the draft hood outlet
on the water
heater
and must
slope upward
at least 1/4 inch per linear foot (21 mm per meter).
See Figure
18.
TO
CHIMNEY
FIGURE 18.
All vent gases
must be completely
vented
to the outdoors
of the
structure
(dwelling).
Install
only the draft
hood
provided
with
the new water
heater
and no other
draft hood.
\lent pipes must be secured
at each joint with sheet metal screws.
There
must
be a minimum
of 6 inches
(153
mm)
clearance
between
single
wall vent
pipe
and any combustible
material.
Fill and seal any clearance
between
single
wal! vent pipe and
combustible
material
with
mortar
mix,
cement,
or other
noncombustible
substance.
For other
than
single
wall, follow
vent
pipe
manufacturer's
clearance
specifications.
To insure
a tight fit of the vent
pipe in a brick chimney,
seal around
the
vent pipe with mortar
mix cement.
,
Flue
gases
may
escape
if vent
pipe is not connected.
Do not store
corrosive
chemicals
in vicinity of water heater.
Chemical
corrosion
of flue
and
vent
system
can
cause
serious
injury or death.
.
Contact
a qualified
installer
or
service
agency,
Breathing carbon monoxide can cause brain damage
or death. Always read and understand instruction manual
Failure
to have
required
clearances
between
vent
piping
and
combustible
material
will result
in a fire hazard.
Fire and Explosion
Hazard
Do not use water
heater
with
any
gas
other
than
the
gas
shown on the rating plate.
Excessive
pressure
to gas
control valve can cause serious
injury or death.
Turn
off
gas
lines
during
installation.
Contact
qualified installer
or
service agency,
Make
sure
the gas
supplied
is the same
type
listed
on the
model
rating
plate.
The
inlet gas
pressure
must
not exceed
14 inch water
column
(3.5kPa)
for natural
and propane
gas
(UP.) gas.
The minimum
inlet gas pressure
listed
on the rating
plate
is for the purpose
of input adjustment.
If the gas control
valve
is subjected
to pressures
exceeding
1/2 pound
per square
inch (3.5kPa),
the damage
to the gas control
valve
could result
in a fire or explosion
from
leaking
gas.
if the main gas line shutoff
serving
al! gas appliances
is used,
also
turn
"OFF"
the gas
at each
appliance.
Leave
all gas
appliances
shut
"OFF"
until
the water
heater
installation
is
complete.
A gas line of sufficient
size
must
be run to the water
heater.
Consult
the current
edition
of National
Fuel
Gas Code ANSI
Z223.1/NFPA
54 and your
gas supplier
concerning
pipe size.
There
must be:
A readily
accessible
manual
shut off valve
in the gas supply
line serving
the water
heater,
and
*
A drip leg (sediment
trap)
ahead
of the gas control
valve
to
help
prevent
dirt and foreign
materials
from
entering
the
gas control
valve.
*
A flexible
gas connector
or a ground joint union between
the
shut off valve and control
valve to permit
servicing
of the unit.
Be sure to check
al! the gas piping for leaks before
lighting
the
water
heater.
Use a soapy water
solution,
not a match or open
flame.
Rinse off soapy
solution
and wipe
dry.
The
minimum
inlet gas pressure
shown
on the rating
plate
is
that which
will permit
firing
at the rated input.
16

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Power miser 12153.331444153.331544

Table of Contents