Kenmore 33124 - Power Miser 12 Owner's Manual page 11

Potable water heating only not suitable for space heating
Table of Contents

Advertisement

Installation
Instructions
(cont'd)
B. Rigid metal conduit,
intermediate
metal conduit,
or elec-
trical
metallic
tubing
may be used for the grounding
means
if conduit
or tubing
is terminated
in fittings
approved for grounding.
C. Flexible metal conduit
or flexible metallic tubing
shall be
permitted
for grounding
if all the following conditions
are
met:
1. The length in any ground return path does not exceed
6 feet.
2. The circuit conductors
contained
therein are .protected
by overcurrent
devices rated at 20 amperes or less.
3. The
conduit
or tubing
is terminated
in fittings
approved for grounding.
For complete
grounding
details and all allowable excep-
tions,
refer
to the latest
edition
of the National
Electrical Code.
4. A standard ½" conduit opening has been made in the water
heater junction box for the conduit connection.
5. Use wire nuts and connectthe
power supply wiring to the
wires inside the water heater s junction box.
6. The water heater must be electrically "grounded"
by the
installer. A g_reenground screw has been provided on the
water heater s junction
box. Connect ground wire to this
location.
7. Replace the wiring junction cover using the screw provided.
CONDUIT
, WIRE NUTS
GREEN
GROUND
SCREW
11