Block PC-0724-800-0I1 Manual

Economy smart with io-link multi-channel circuit breaker
Hide thumbs Also See for PC-0724-800-0I1:

Advertisement

Quick Links

MANUAL
ECONOMY SMART with IO-LINK
PC-0724-800-0I1
PM-0724-400-0I1
Multi-channel circuit breaker
IO-LINK
BLOCK Transformatoren-Elektronik GmbH
Max-Planck-Straße 36-46
27283 Verden
Germany
Phone +49 4231 678-0
Fax +49 4231 678-177
info@block.eu
block.eu

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the PC-0724-800-0I1 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Block PC-0724-800-0I1

  • Page 1 MANUAL ECONOMY SMART with IO-LINK PC-0724-800-0I1 PM-0724-400-0I1 Multi-channel circuit breaker IO-LINK BLOCK Transformatoren-Elektronik GmbH Max-Planck-Straße 36-46 Phone +49 4231 678-0 Fax +49 4231 678-177 • 27283 Verden Germany info@block.eu • block.eu •...
  • Page 2: Table Of Contents

    Charging capacitive loads .................. 14 Communication ....................15 Process data and parameters ............... 16 Process data ....................16 5.1.1 PC-0724-800-0I1 ........................16 5.1.2 PM-0724-400-0I1 ........................19 5.2 Acyclic I/O data IO-LINK ..................22 Acyclical I/O data of the circuit breaker ..............23 5.3.1...
  • Page 3: Order Data

    The following table shows the ordering data for ECONOMY SMART circuit-breakers with IO-LINK. Table 1: Order numbers Variant Input voltage Channels PC-0724-800-0I1 24 Vdc PM-0724-400-0I1 24 Vdc BLOCK Transformatoren-Elektronik GmbH Max-Planck-Straße 36-46 Phone +49 4231 678-0 13.12.2024 / FRAN Fax +49 4231 678-177 • 27283 Verden Germany info@block.eu Subject to technical changes •...
  • Page 4: General Information

    In the event of malfunctions or damage, switch off the supply voltage immediately and send the device to BLOCK Transformatoren-Elektronik GmbH for inspection. The device does not contain any service parts. If an internal fuse blows, there is most likely an internal defect in the appliance.
  • Page 5 CAUTION Do not touch the housing during operation or shortly after switching off. Hot surfaces can cause injuries. BLOCK Transformatoren-Elektronik GmbH Max-Planck-Straße 36-46 Phone +49 4231 678-0 13.12.2024 / FRAN Fax +49 4231 678-177 •...
  • Page 6: Product Description

    IO-LINK interface and individual outputs can be specifically switched on or off. The status of the respective out- put is displayed via a multi-colored LED. Figure 1: Electronic circuit breaker BLOCK Transformatoren-Elektronik GmbH Max-Planck-Straße 36-46 Phone +49 4231 678-0 13.12.2024 / FRAN Fax +49 4231 678-177 •...
  • Page 7: System Structure

    Abbildung 2: Systemaufbau Note: Deviating wiring can lead to the destruction of the modules. The IO-LINK cable must not exceed a maximum length of 20 m. BLOCK Transformatoren-Elektronik GmbH Max-Planck-Straße 36-46 Phone +49 4231 678-0 13.12.2024 / FRAN Fax +49 4231 678-177 •...
  • Page 8: Tripping Characteristic

    The level of the short-circuit current depends on the current limita- tion of the supplying power supply unit and the line resistance. A characteristic curve describes this behavior in Figure 3. Figure 3: Tripping characteristic BLOCK Transformatoren-Elektronik GmbH Max-Planck-Straße 36-46 Phone +49 4231 678-0 13.12.2024 / FRAN Fax +49 4231 678-177 •...
  • Page 9: Dimensioning

    V 1.0 ECONOMY SMART with IO-LINK Dimensioning The dimensioning of the circuit breakers is shown in Figure 4. Figure 4: Dimensioning and assembly BLOCK Transformatoren-Elektronik GmbH Max-Planck-Straße 36-46 Phone +49 4231 678-0 13.12.2024 / FRAN Fax +49 4231 678-177 •...
  • Page 10: Mounting

    A standard tool, such as a slotted screwdriver, is required for removal. The device can be detached from the top- hat rail by pressing down the fastening and lifting the underside of the device. Figure 5: Mounting on the top-hat rail BLOCK Transformatoren-Elektronik GmbH Max-Planck-Straße 36-46 Phone +49 4231 678-0 13.12.2024 / FRAN...
  • Page 11 V 1.0 ECONOMY SMART with IO-LINK To ensure cooling by natural convection, the distances to neighboring appliances must be observed. Figure 6: Convection cooling and distances BLOCK Transformatoren-Elektronik GmbH Max-Planck-Straße 36-46 Phone +49 4231 678-0 13.12.2024 / FRAN Fax +49 4231 678-177 •...
  • Page 12: Connections And Signaling

    Current selector switch 1 – 10A Push-button incl. status display See chapter 3.1 IO-LINK interface 0,2 – 2,5 mm² (24…12 AWG) BLOCK Transformatoren-Elektronik GmbH Max-Planck-Straße 36-46 Phone +49 4231 678-0 13.12.2024 / FRAN Fax +49 4231 678-177 • 27283 Verden Germany info@block.eu...
  • Page 13: Commissioning

    ECONOMY SMART with IO-LINK 4. Commissioning The PC-0724-800-0I1 and PM-0724-400-0I1 circuit breakers initialize themselves automatically by applying the supply voltage to the IN DC 24V+ terminal or by establishing the IO-LINK connection. Functional operation is only possible by applying the 24 V supply voltage to IN+.
  • Page 14: On/Off And Reset" Button

    64,8 53,3 53,3 41,5 83,3 81,3 71,3 109,5 306,6 222,8 122,8 112,8 BLOCK Transformatoren-Elektronik GmbH Max-Planck-Straße 36-46 Phone +49 4231 678-0 13.12.2024 / FRAN Fax +49 4231 678-177 • 27283 Verden Germany info@block.eu Subject to technical changes • block.eu •...
  • Page 15: Communication

    18V. Communication The PC-0724-800-0I1 and PM-0724-400-0I1 circuit breakers communicate according to the IO-LINK standard V1.1. An IO-LINK master in version V1.1 is required for communication with the circuit breaker. The circuit brea- kers operate in COM 3 mode (230.4 kB) and exchange 9 bytes or 13 bytes of process data with the master per...
  • Page 16: Process Data And Parameters

    Unsigned Integer 16 Table 7: Process data current channel 1 Byte 4 Description Data type 09 Current Channel 1 Unsigned Integer 8 BLOCK Transformatoren-Elektronik GmbH Max-Planck-Straße 36-46 Phone +49 4231 678-0 13.12.2024 / FRAN Fax +49 4231 678-177 • 27283 Verden Germany info@block.eu...
  • Page 17 Unsigned Integer 8 Tabelle 12: Process data Current Channel 6 Byte 9 Description Data type 14 Current Channel 6 Unsigned Integer 8 BLOCK Transformatoren-Elektronik GmbH Max-Planck-Straße 36-46 Phone +49 4231 678-0 13.12.2024 / FRAN Fax +49 4231 678-177 • 27283 Verden Germany info@block.eu...
  • Page 18 21 Over Current Channel 22 Over Current Chan- nel 6 23 Over Current Chan- nel 7 24 Over Current Chan- nel 8 BLOCK Transformatoren-Elektronik GmbH Max-Planck-Straße 36-46 Phone +49 4231 678-0 13.12.2024 / FRAN Fax +49 4231 678-177 • 27283 Verden Germany info@block.eu...
  • Page 19: Pm-0724-400-0I1

    02 Collective Message >90% 03 Collective Message > 100% 04 Collective Message HW-FUSE 05 Collective Message Local Off 06 Input Voltage Alarm 07 Reserved BLOCK Transformatoren-Elektronik GmbH Max-Planck-Straße 36-46 Phone +49 4231 678-0 13.12.2024 / FRAN Fax +49 4231 678-177 •...
  • Page 20 Unsigned Integer 8 Tabelle 22: Process data Current Channel 4 Byte 7 Description Data type 12 Current Channel 4 Unsigned Integer 8 BLOCK Transformatoren-Elektronik GmbH Max-Planck-Straße 36-46 Phone +49 4231 678-0 13.12.2024 / FRAN Fax +49 4231 678-177 • 27283 Verden Germany info@block.eu...
  • Page 21 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 21 Tripped Channel 1 22 Tripped Channel 2 23 Tripped Channel 3 24 Tripped Channel 4 BLOCK Transformatoren-Elektronik GmbH Max-Planck-Straße 36-46 Phone +49 4231 678-0 13.12.2024 / FRAN Fax +49 4231 678-177 •...
  • Page 22: Acyclic I/O Data Io-Link

    IO-LINK inter- face and system specification Detailed Device String IO-LINK inter- Status face and system specification BLOCK Transformatoren-Elektronik GmbH Max-Planck-Straße 36-46 Phone +49 4231 678-0 13.12.2024 / FRAN Fax +49 4231 678-177 • 27283 Verden Germany info@block.eu Subject to technical changes •...
  • Page 23: Acyclical I/O Data Of The Circuit Breaker

    601-608 eBreaker Status 8 Bit Status 609-616 eBreaker Com- 8 Bit ON / OFF / RESET mand BLOCK Transformatoren-Elektronik GmbH Max-Planck-Straße 36-46 Phone +49 4231 678-0 13.12.2024 / FRAN Fax +49 4231 678-177 • 27283 Verden Germany info@block.eu Subject to technical changes •...
  • Page 24: Pm-0724-400-0I1

    601-604 eBreaker Status 8 Bit Status 609-612 eBreaker Com- 8 Bit ON / OFF / RESET mand BLOCK Transformatoren-Elektronik GmbH Max-Planck-Straße 36-46 Phone +49 4231 678-0 13.12.2024 / FRAN Fax +49 4231 678-177 • 27283 Verden Germany info@block.eu Subject to technical changes •...
  • Page 25: Coding Of The Circuit Breaker Status

    Switched Off, local Switched off, local 5.3.4 Coding of the circuit breaker currents The coding of the tripping currents of the PC-0724-800-0I1 (index 310-318) and the PM-0724-400-0I (index 310 - 313) is shown in Table 29. Tabelle 29: eBreaker Current Dec. Value...
  • Page 26: Coding Of The Circuit Breaker Type

    V 1.0 ECONOMY SMART with IO-LINK 5.3.5 Coding of the circuit breaker type The coding of the type of the Pc-0724-800-0I1 (index 69) and the PM-0724-400-0I1 (index 69) is shown in Table Table 30: eBreaker Type Dec. Value Description Remark...
  • Page 27: Coding Of The Circuit Breaker Command

    Channel 7 On RESET Channel 7 Reset Channel 8 Off Channel 8 On RESET Channel 8 Reset 1) PM-0724-400-OI1 BLOCK Transformatoren-Elektronik GmbH Max-Planck-Straße 36-46 Phone +49 4231 678-0 13.12.2024 / FRAN Fax +49 4231 678-177 • 27283 Verden Germany info@block.eu Subject to technical changes •...
  • Page 28: Coding For Resetting The Circuit Breaker Trip Counter

    Channel 5 Reset Trip Counter RESET Channel 6 Reset Trip Counter RESET Channel 7 Reset Trip Counter RESET Channel 8 Reset Trip Counter PM-0724-400-OI1 BLOCK Transformatoren-Elektronik GmbH Max-Planck-Straße 36-46 Phone +49 4231 678-0 13.12.2024 / FRAN Fax +49 4231 678-177 • 27283 Verden Germany info@block.eu...