In the event of malfunctions or damage, switch off the supply voltage immediately and send the device to BLOCK Transformatoren-Elektronik GmbH for inspection. The device does not contain any service parts. If an internal fuse blows, there is most likely an internal defect in the appliance.
Page 5
CAUTION Do not touch the housing during operation or shortly after switching off. Hot surfaces can cause injuries. BLOCK Transformatoren-Elektronik GmbH Max-Planck-Straße 36-46 29.01.2025 / FRAN Phone +49 4231 678-0 Fax +49 4231 678-177 •...
Extended remote transmission of input voltage, set rated currents and current output currents Sum signalling contact for simple remote diagnostics Push-in direct connection technology LED signalling and on/off/reset button per channel BLOCK Transformatoren-Elektronik GmbH Max-Planck-Straße 36-46 29.01.2025 / FRAN Phone +49 4231 678-0 Fax +49 4231 678-177 •...
Page 8
All capacities were determined experimentally under nominal load. The tasks are guide values, possible line capacitances depend on the installation situation. The power supply unit must be able to supply the required current without the output voltage dropping below 18V. BLOCK Transformatoren-Elektronik GmbH Max-Planck-Straße 36-46 29.01.2025 / FRAN...
1. The next channel is switched on as soon as the output current of the previous channel is below the set nominal value or the previous output has been switched off, but not before 50 ms. BLOCK Transformatoren-Elektronik GmbH Max-Planck-Straße 36-46 29.01.2025 / FRAN...
The signal output S3 serves as an active 24V collective fault signal and indicates that at least one output has been switched off due to overcurrent. An internal device fault is also signalled by S3. BLOCK Transformatoren-Elektronik GmbH Max-Planck-Straße 36-46 29.01.2025 / FRAN...
S2. (500 ms high pulse, every 3 seconds) This pulse is sent until the PLC has successfully queried the updated status via a new Manchester-coded telegram. BLOCK Transformatoren-Elektronik GmbH Max-Planck-Straße 36-46 29.01.2025 / FRAN...
If the PLC sends the coded pulse sequence via the signal input S1, the circuit breaker synchronises to the auxiliary clock of the PLC and sends the current on/off and error states via the signal output S2. Coding of the status bits sent by the circuit breaker BLOCK Transformatoren-Elektronik GmbH Max-Planck-Straße 36-46 29.01.2025 / FRAN...
S2 before starting to send the telegram or to generate a telegram at least every 3 se- conds to query the status. 6.7.3 Max. Jitter for data transmission The following absolute jitter is permitted depending on the selected clock cycle: BLOCK Transformatoren-Elektronik GmbH Max-Planck-Straße 36-46 29.01.2025 / FRAN Phone +49 4231 678-0 Fax +49 4231 678-177 •...
"Active High" (+24V). As soon as at least one output channel has triggered or a device defect has been detected, or signal output switches to "Active Low" (0V). This signal output is short-circuit- proof and can be loaded up to max. 20mA. BLOCK Transformatoren-Elektronik GmbH Max-Planck-Straße 36-46 29.01.2025 / FRAN...