AIR CONDITIONER (MULTI TYPE) Installation Manual Indoor Unit Model name: For commercial use Pour usage commercial Para uso comercial High-Wall Type MMK-UB0301HP-UL MMK-UB0361HP-UL English Installation Manual Français Manuel d’Installation Español Manual de Instalación 113085010 5 01_IM_1130850105_EN.indd 1 01_IM_1130850105_EN.indd 1 19/9/2567 BE 14:15 19/9/2567 BE 14:15...
Installation Manual Please read this Installation Manual carefully before installing the Air Conditioner. • This Manual describes the installation method of the indoor unit. • For installation of the outdoor unit, follow the Installation Manual attached to the outdoor unit. ADOPTION OF NEW REFRIGERANT This Air Conditioner uses R454B an environmentally friendly refrigerant.
Page 3
Installation Manual Generic Denomination: Air Conditioner Definition of Qualified Installer or Qualified Service Person The air conditioner must be installed, maintained, repaired and removed by a qualified installer or qualified service person. When any of these jobs is to be done, ask a qualified installer or qualified service person to do them for you.
Page 4
Installation Manual Definition of Protective Gear When the air conditioner is to be transported, installed, maintained, repaired or removed, wear protective gloves and ‘Safety’ work clothing. In addition to such normal protective gear, wear the protective gear described below when undertaking the special work detailed in the table below.
Installation Manual Warning indications on the air conditioner unit Warning indication Description WARNING WARNING ELECTRICAL SHOCK HAZARD ELECTRICAL SHOCK HAZARD Disconnect all remote electric power supplies Disconnect all remote electric power supplies before servicing. before servicing. WARNING WARNING Moving parts. Moving parts.
Installation Manual PRECAUTIONS FOR SAFETY • Ensure that all Local, National and International regulations are satisfied. • Read this “PRECAUTIONS FOR SAFETY” carefully before Installation. • The precautions described below include the important items regarding safety. Observe them without fail. •...
Installation Manual • Do not touch the aluminium fin of the unit. You may injure yourself if you do so. If the fin must be touched for some reason, first put on protective gloves and safety work clothing, and then proceed. •...
Installation Manual Installation • Install the air conditioner securely in a location where the base can sustain the weight adequately. If the strength is not enough, the unit may fall down resulting in injury. • Follow the instructions in the Installation Manual to install the air conditioner. Failure to follow these instructions may cause the product to fall down or topple over or give rise to noise, vibration, water leakage or other trouble.
Page 9
Installation Manual • Connect grounding wire. (grounding work) Incomplete grounding causes an electric shock. • Do not connect grounding wires to gas pipes, water pipes, and lightning conductor or telephone grounding wires. • After completing the repair or relocation work, check that the grounding wires are connected properly.
Page 10
Installation Manual • If the fan grille is damaged, do not approach the outdoor unit but set the circuit breaker to the OFF position, and contact a qualified service person to have the repairs done. Do not set the circuit breaker to the ON position until the repairs are completed.
Page 11
Installation Manual CAUTION New refrigerant air conditioner installation • This Air Conditioner uses R454B an environmentally friendly refrigerant. • The characteristics of R454B refrigerant are; easy to absorb water, oxidizing membrane or oil. Accompanied with the new refrigerant, refrigerating oil has also been changed.
Installation Manual ACCESSORY PARTS Part name Q’ty Shape Usage Installation Manual This manual Hand over to customers Owner’s Manual Hand over to customers Installation plate — Wireless remote controller — Batteries size AAA — Remote controller holder — Mounting screw —...
Installation Manual SELECTION OF INSTALLATION PLACE WARNING • Install the air conditioner at enough strong place to withstand the weight of the unit. If the strength is not enough, the unit may fall down resulting in injury. CAUTION • Do not install the air conditioner in a location subject to a risk of exposure to a combustible gas. If a combustible gas leaks and stays around the unit, a fire may occur.
Installation Manual Installation diagram of Indoor unit For the rear left, bottom left and left piping Packing material Wall Split Hook Installation plate SPACER Hook Split out 2 pieces of SPACER from indoor unit packing material, insert between the indoor unit and wall to tilt the indoor unit for better operation.
Installation Manual Wireless remote controller • A place where there are no obstacles such as a curtain that may block the signal from the indoor unit. Hook • Do not install the remote controller in a place exposed to direct sunlight or close to a heating source, such as a stove.
Page 16
Installation Manual Installation of eletrical cover 2 holes type REQUIREMENT In case of group control, electrical cover 1 hole type need to change to electrical cover 2 holes type. • Step to remove the electrical cover 1 hole. 1) The electical cover 1 hole can be removed by removing the screw securing the electical cover 1 hole and them pulling out the electical cover 1 hole.
Installation Manual CUTTING A HOLE AND MOUNTING INSTALLATION PLATE Cutting a hole When the installation plate is directly mounted on the wall In case of installing the refrigerant pipes from the rear: 1. Securely fit the installation plate onto the 1.
Installation Manual PIPING AND DRAIN HOSE INSTALLATION Piping and drain hose forming * Since dewing results in a machine trouble, make sure to insulate both connecting pipes. (Use polyethylene foam as insulating material.) Rear right Rear left Bottom left Left Bottom right Right...
Page 19
Installation Manual How to remove the drains cap Clip the drain cap by needle-nose pliers and pull out. Drain cap How to fix the drains cap 1) Insert hexagonal wrench (dia. 0.2″ (4 mm)) in a centre head. Drain cap 2) Firmly insert drains cap.
Page 20
Installation Manual q In case of bottom right or bottom left piping • After scribing slits of the front panel with a knife or a marking-off pin, cut them with a pair of nippers or an equivalent tool. Slit q Left-hand connection with piping Bend the connecting pipe so that it is laid within 1.7″...
Installation Manual INDOOR UNIT FIXING DRAINAGE 1. Pass the pipe through the hole in the wall, 1. Run the drain hose sloped downwards. and hook the indoor unit on the installation NOTE plate at the upper hooks. 2. Swing the indoor unit to right and left to •...
Installation Manual REFRIGERANT PIPING Refrigerant Piping Permissible Piping Length and Height Difference 1. Use copper pipe with 0.03″ (0.8 mm) or more thickness. (In case pipe size is dia. They vary according to the outdoor unit. 5/8″ (15.9 mm), with 0.04″ (1.0 mm) For details, refer to the Installation Manual or more.) attached to the outdoor unit.
Installation Manual * In case of flaring for R454B with the Piping with outdoor unit conventional flare tool, pull it out • Shape of valve differs according to the outdoor approx. 0.02″ (0.5 mm) more than unit. that for R22 to adjust to the specified For details of installation, refer to the Installation flare size.
Installation Manual ELECTRICAL CONNECTION WARNING REQUIREMENT • For power supply wiring, strictly conform to 1. Use predefined wire and connect them the Local Regulation in each country. certainly. Keep the connecting terminal • Run the refrigerant piping line and control freefrom external force.
Page 25
Installation Manual Power supply wire Recommended wire diameter and wire length for power supply wire. Wire size: 2 × AWG12 Power supply wiring Up to 164′1″ (50 m) Ground 1 × AWG12 or thicker q Electric characteristics Voltage Range (V) MOCP Model Power Supply...
Page 26
Installation Manual <In the case of combining with outdoor units of Super Modular Multi System u series (SMMS-u)>> Uv line and Uc line (L2, L3, L4) AWG20 (Up to 1640’5” (500 m)) Wire size : (2-core shield wire, non-polarity) AWG18 to AWG16 (Up to 3280’10”...
Installation Manual [Communication line] (L1+L2+L3) = Up to 6561’8” (2000 m) Central control device U3 U4 (L4) = Up to 328’1” (100 m) U3 U4 U3 U4 U3 U4 <Other than U series> Outdoor unit U5 U6 U5 U6 U5 U6 (SMMS-i) (SMMS-e) (MiNi SMMS)
Page 28
Installation Manual Max. number of connectable indoor units, and communication type Unit type Outdoor unit U series U series U series U series Indoor unit U series U series U series U series ...
Installation Manual Address setup Set up the addresses as per the Installation Manual supplied with the outdoor unit. Wired remote controller wiring • As the wired remote controller wire has non-polarity, there is no problem if connections to indoor unit terminal blocks A and B are reversed.
Installation Manual Wiring Connection Power supply terminal block How to connect the power supply wiring Terminal block for communication/remote and control wiring controller wiring The power supply wire and the control wire can be Screw connected without removing the front panel. Terminal cover Earth screw REQUIREMENT...
Page 31
Installation Manual Wiring connection for flow selector unit How to connect the wiring of flow selector unit Connect the power supply wire and the communication wire supplied with the flow selector unit to the indoor unit. 1. Remove the air inlet grille. Open the air inlet grille upward and pull it toward you.
Installation Manual APPLICABLE CONTROLS A wired remote controller is necessary for this function. This function cannot be operate with a wireless remote controller. REQUIREMENT CAUTION When the unit is used for the first time, it takes Set only the “Code(DN)ˮ shown in the following a while for the remote controller to recognize table: Do not set any other “Code(DN)ˮ.
Page 33
Installation Manual After finishing setting the data of the item SET DATA Detection temp shift value code (DN), press [ Set/Fix] 0000 No shift “Continue?” is displayed. 0001 +1.8°F (+1°C) 0002 +3.6°F (+2°C) (Factory setting) 0003 +5.4°F (+3°C) 0004 +7.2°F (+4°C) 0005 +9°F (+5°C)
Installation Manual Cancelling swing Group control In a group control, a remote controller can control up to maximum 8 or 16 units. (Depending on the outdoor unit.) • The wired remote controller only can control a group control. The wireless remote controller is unavailable for this control.
Installation Manual TEST RUN A wired remote controller is necessary for this function. This function cannot be operate with a wireless remote controller. Before test run Execute a test run • Before turning on the power supply, carry out Use the remote controller to check operations.
Page 36
Installation Manual In the “Field setting menu” screen, press ] or [ ] to select “Test mode”, and then press [ Set/Fix] Test mode is set, and returns to the “Field setting menu” screen. Press the Return] button 2 times, to open screen (2).
Page 37
Installation Manual In case of wireless remote controller (Forced test operation is performed in a different way.) REQUIREMENT • For the operation procedure, be sure to follow the Owner’s Manual. • Finish the forced cooling operation in a short time because it applies excessive strength to the air conditioner.
Installation Manual TROUBLESHOOTING A wired remote controller is necessary for this function. This function cannot be operate with a wireless remote controller. Confirmation and check Check code When an error occurs in the air conditioner, the check code and the indoor unit number flash on Indoor unit number the display of the remote controller.
Installation Manual Check method On the wired remote controller, central control remote controller and the interface P.C. Board of the outdoor unit (I/F), a check display LCD (Remote controller) or 7-segment display (on the outdoor interface P.C. Board) to display the operation is provided. Therefore the operation status can be known. Using this self-diagnosis function, a trouble or position with error of the air conditioner can be found as shown in the table below.
Page 40
Installation Manual Check code Wireless remote controller Wired Sensor block display of Judging Outdoor unit 7-segment display Check code name remote receiving unit device controller Auxiliary code Operation Timer Ready Flash display 00: Header is not detected Outdoor header units quantity trouble 02: Two or more header units 01: Outdoor unit of other line connected...
Installation Manual WARNINGS ON REFRIGERANT LEAKAGE Check of Concentration Limit NOTE 2 The room in which the air conditioner is to be The standards for minimum room volume are as installed requires a design that in the event of follows. refrigerant gas leaking out, its concentration will (1) No partition (shaded portion) not exceed a set limit.
Installation Manual CONFIRMATION OF INDOOR UNIT SETUP Prior to delivery to the customer, check the address and setup of the indoor unit, which has been installed in this time and fill the check sheet (Table below). Data of four units can be entered in this check sheet. Copy this sheet according to the No.
Page 46
144/9 MOO 5, BANGKADI INDUSTRIAL PARK, TIVANON ROAD, TAMBOL BANGKADI, AMPHUR MUANGPATHUMTHANI, PATHUMTHANI 12000, THAILAND 1130850105 01_IM_1130850105_EN.indd 45 01_IM_1130850105_EN.indd 45 19/9/2567 BE 14:15 19/9/2567 BE 14:15...