Carrier WeatherMaster 50GCQM04 Installation Instructions Manual
Carrier WeatherMaster 50GCQM04 Installation Instructions Manual

Carrier WeatherMaster 50GCQM04 Installation Instructions Manual

Single package rooftop heat pump with puron (r-410a) refrigerant
Table of Contents

Advertisement

Quick Links

CONTENTS
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . 1
DIMENSIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Rated Indoor Airflow . . . . . . . . . . . . . . . . . . . . . . . . . . 2
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Jobsite Survey . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Step 1 - Plan for Unit Location . . . . . . . . . . . . . . . . 7
Step 3 - Inspect Unit . . . . . . . . . . . . . . . . . . . . . . . . . 7
Step 4 - Provide Unit Support . . . . . . . . . . . . . . . . . 7
• ALTERNATE UNIT SUPPORT (IN LIEU OF CURB OR
Step 5 - Field Fabricate Ductwork . . . . . . . . . . . . . . 9
Step 6 - Rig and Place Unit . . . . . . . . . . . . . . . . . . . 9
Ductwork (when required) . . . . . . . . . . . . . . . . . . 10
Step 8 - Install Outside Air Hood . . . . . . . . . . . . . . 11
OPTION)
and Line . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
• CONVENIENCE OUTLETS
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53500312-01
Installation Instructions
Page
Printed in U.S.A.
Form 50GCQ-4-6-02SI
Single Package Rooftop Heat Pump
with Puron
®
EconoMi$er X (Factory Option) . . . . . . . . . . . . . . . .30
Controller Options . . . . . . . . . . . . . . . . . . . . . . . . . . .41
Smoke Detectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Step 13 - Install Accessories . . . . . . . . . . . . . . . . .42
Step 14 - Fan Speed Set Up . . . . . . . . . . . . . . . . . .43
Typical Unit Piping . . . . . . . . . . . . . . . . . . . . . . . . . . .45
Pre-Start and Start-Up . . . . . . . . . . . . . . . . . . . . . . . .46
START-UP CHECKLIST . . . . . . . . . . . . . . . . . . . . CL-1

SAFETY CONSIDERATIONS

Improper
installation,
maintenance, or use can cause explosion, fire, electrical shock or
other conditions which may cause personal injury or property
damage. Consult a qualified installer, service agency, or your
distributor or branch for information or assistance. The qualified
installer or agency must use factory-authorized kits or accessories
when modifying this product. Refer to the individual instructions
packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses and work gloves. Use
quenching cloths for brazing operations and have a fire
extinguisher available. Read these instructions thoroughly and
follow all warnings or cautions attached to the unit. Consult local
building codes and appropriate national electrical codes (in USA,
ANSI/NFPA70, National Electrical Code (NEC); in Canada, CSA
C22.1) for special requirements.
It is important to recognize safety information. This is the safety-
alert symbol
. When you see this symbol on the unit and in
instructions or manuals, be alert to the potential for personal
injury.
Pg 1
WeatherMaster
50GCQM04-06
(R-410A) Refrigerant
adjustment,
alteration,
6-21
Replaces: 50GCQ-4-6-01SI
®
service,

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the WeatherMaster 50GCQM04 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Carrier WeatherMaster 50GCQM04

  • Page 1: Table Of Contents

    WeatherMaster ® 50GCQM04-06 Single Package Rooftop Heat Pump with Puron ® (R-410A) Refrigerant Installation Instructions CONTENTS EconoMi$er X (Factory Option) ....30 • SYSTEM COMPONENTS Page •...
  • Page 2: Model Number Nomenclature And

    Understand the signal words DANGER, WARNING, CAUTION, MODEL NUMBER NOMENCLATURE AND and NOTE. These words are used with the safety-alert symbol. DIMENSIONS DANGER identifies the most serious hazards which will result in See Fig. 1 for 50GCQ model number nomenclature. See Fig. 2 on severe personal injury or death.
  • Page 3 Position: 9 10 11 12 13 14 15 16 17 18 Example: Unit/Series/Model Packaging & Seismic Compliance 50GCQ – Packaged Rooftop Heat Pump 0 = Standard 1 = LTL Refrig. Systems Options M = Two Stage Cooling Electrical Options A = None C = Non-Fused Disconnect (NFD) Cooling Tons D = Thru-The-Base Connections (TTB)
  • Page 4 Fig. 2 — 50GCQ 04-06 Unit Dimensional Drawing...
  • Page 5 Fig. 2 — 50GCQ 04-06 Unit Dimensional Drawing (cont)
  • Page 6 Fig. 2 — 50GCQ 04-06 Unit Dimensional Drawing (cont)
  • Page 7: Installation

    Prepare bottom condensate drain connection to suit planned INSTALLATION condensate line routing (refer to Step 10 for details) Jobsite Survey Rig and place unit Complete the following checks before installation. Install outdoor air hood Consult local building codes and the NEC (National Electri- Install condensate line trap and piping Code) ANSI/NFPA 70 special...
  • Page 8 ROOF CURB NOTES: POWER WIRING CONTROL WIRING ACCESSORY CONVENIENCE CONNECTOR PKG. ACC. GAS CONNECTION TYPE GAS FITTING ACCESSORY # 1. ROOFCURB ACCESSORY IS SHIPPED DISASSEMBLED. FITTING FITTING OUTLET WIRING CONNECTOR 2. INSULATED PANELS: 25.4 [1"] THK. POLYURETHANE FOAM, 44.5 [1-3/4] # DENSITY. 14"...
  • Page 9: Slab Mount (Horizontal Units Only)

    FOR UNITS WITH ACCESSORY ELECTRIC HEATERS All installations require a minimum clearance to combustible sur- faces of 1-in. (25 mm) from duct for first 12-in. (305 mm) away from unit. Outlet grilles must not lie directly below unit discharge. WARNING PERSONAL INJURY HAZARD Failure to follow this warning could cause personal injury.
  • Page 10: Step 7 - Convert To Horizontal And Connect

    "B" DETAIL "A" 36"- 54" PLACE ALL SEAL STRIP IN PLACE REQUIRED (914-1371) BEFORE PLACING UNIT ON ROOF CURB. SPREADER BARS DUCT END "C" "A" SEE DETAIL "A" DIMENSIONS MAX WEIGHT UNIT 50GCQ-04 74.5 1890 36.0 33.5 50GCQ-05 74.5 1890 35.4 41.5 1055...
  • Page 11: Step 8 - Install Outside Air Hood

    discarded. Save the aluminum filter for use in the power exhaust Step 8 — Install Outside Air Hood hood assembly. ECONOMIZER HOOD AND TWO-POSITION DAMPER The indoor coil access panel will be used as the top of the HOOD PACKAGE REMOVAL AND SETUP FACTORY hood.
  • Page 12: Step 9 - Units With Hinged Panels Only

    The piping for the condensate drain and external trap can be com- pleted after the unit is in place. See Fig. 16. NOTE: If the alternate bottom drain is not used check the drain plug for tightness prior to setting the unit on the roof curb. DIVIDER MINIMUM PITCH 1˝...
  • Page 13: Units With Factory-Installed Non-Fused

    on contactors, #2ga AWG (copper only) per pole on optional dis- connect or HACR, and 4/0 AWG (copper only, see Fig. 17) per Units Without Single Point Box, Disconnect or HACR Option pole on terminal or fuse blocks on units with single point box (see Equip Fig.
  • Page 14: All Units

    Measure from the tip of the shaft to the top surface of the Turn the handle to the OFF position with red arrow pointing black pointer; the measurement should be 3.75 to 3.88 in. (95 at OFF. to 99 mm). Install the handle on to the painted cover horizontally with the Tighten the locking screw to secure the shaft to the NFD.
  • Page 15: Convenience Outlets

    Provide a ground fault and short circuit over-current protection de- vice (fuse or breaker) per NEC Article 440 (or local codes). Refer to unit informative data plate for MOCP (Maximum Over-Current Protection) device size. NOTE: Units ordered with factory installed HACR do not need an additional ground fault and short circuit over-current protective device unless required by local codes.
  • Page 16: Hacr Amp Rating

    Mount the weatherproof cover to the backing plate as shown in Fig. 26. Remove two slot fillers in the bottom of the cover to permit service tool cords to exit the cover. Check for full closing and latching. GFCI RECEPTACLE COVER - WHILE-IN-USE NOT INCLUDED WEATHERPROOF...
  • Page 17: Units Without Thru-Base Connections

    This device can be a thermostat (field-supplied) or a SystemVu™ discard the “L” bracket, but retain the washer head screws controller (available as factory-installed option for use on a Carrier and the gasket (located between the “L” bracket and the con-...
  • Page 18: Heat Anticipator Settings

    Locate the thermostat accessory on a solid wall in the conditioned For wire runs up to 50 ft (15 m), use no. 18 AWG (American Wire space to sense average temperature in accordance with the ther- Gage) insulated wire [35°C (95°F) minimum]. For 50 to 75 ft (15 mostat installation instructions.
  • Page 19: Commercial Defrost Control

    COMMERCIAL DEFROST CONTROL On 50GCQ units equipped with electro-mechanical controls or the optional factory-installed RTU Open controller the Defrost Con- trol Board (DFB) coordinates thermostat demands for supply fan control, 1 or 2 stage cooling, 2 stage heating, emergency heating and defrost control with unit operating sequences.
  • Page 20 Table 3 — 50GCQ Defrost Board I/O and Jumper Configurations POINT NAME TYPE OF I/O CONNECTION PIN NUMBER UNIT CONNECTION NOTES INPUTS G Fan DI, 24 vac P2-3 CTB-G Y1 Cool 1 DI, 24 vac P2-5 CTB-Y1 Y2 Cool 2 DI, 24 vac P2-4 CTB-Y2...
  • Page 21: Electric Heaters

    Table 5 — DIP Switch Positions · · · · · · · · · 30 minutes 60 minutes 90 minutes 120 minutes Fan Delay (factory default) Shorting the jumpers for a period of 5 to 20 seconds bypasses the remaining continuous run period and places the unit in a Forced Defrost mode.
  • Page 22: Low-Voltage Control Connections

    LOW-VOLTAGE CONTROL CONNECTIONS CONTROL AND POWER WIRING DIAGRAMS Pull the low-voltage control leads from the heater module — VIO Figures 41-47 are typical control and power wiring diagrams. and BRN (two of each if a two-circuit heater module is installed; identify for circuit #1) —...
  • Page 23 Fig. 41 — Typical Control Wiring Diagram, Electro-Mechanical with W7220 (50GCQ 04-06 208-230/3/60 Unit Shown)
  • Page 24 Fig. 42 — Typical Control Wiring Diagram, Electro-Mechanical with W7220 (50GCQ 04-06 460, 575/3/60 Unit Shown)
  • Page 25 Fig. 43 — Typical Control Wiring Diagram, with SystemVu™ Controller (50GCQ 04-06 208-230, 460, 575/3/60 Unit Shown)
  • Page 26 Fig. 44 — Typical Control Wiring Diagram, with RTU Open Controller (50GCQ 04-06 208-230/3/60 Unit Shown)
  • Page 27 Fig. 45 — Typical 50GCQ 04-06 Power Wiring Diagram, 208-230/3/60 Unit Shown...
  • Page 28 Fig. 46 — Typical 50GCQ 04-06 Power Wiring Diagram, 460, 575/3/60 Unit Shown...
  • Page 29 Fig. 47 — Typical 50GCQ 04-06 Power Wiring Diagram, 208-230V Unit with SystemVu™ Controller Shown...
  • Page 30: Economi$Er X (Factory Option)

    Electrical EconoMi$er X (Factory Option) • Rated Voltage — 20 to 30 Vac RMS, 50/60 Hz The EconoMi$er X system is an expandable economizer control ® system, which includes a W7220 economizer module (controller) • Transformer — 100 va maximum system input with an LCD and keypad (see Fig.
  • Page 31: Economizer Module Wiring Details

    Relative Humidity Table 7 — Economizer Module - Right Hand Terminal Blocks 5% to 95% RH non-condensing LABEL TYPE DESCRIPTION ECONOMIZER MODULE WIRING DETAILS Top Right Terminal Blocks Use Fig. 49 and Tables 6 and 7 to locate the wiring terminals for AUX2 I 24 vac IN The first terminal is not used.
  • Page 32: Co2 Sensor Wiring

    To use the keypad when working with menus: Table 8 — HH57AC081 Sensor Wiring Terminations • Press the ▲ (Up arrow) button to move to the previous TERMINAL TYPE DESCRIPTION menu. NUMBER LABEL • Press the ▼ (Down arrow) button to move to the next S-BUS menu.
  • Page 33: Setup And Configuration

    SETUP AND CONFIGURATION Before being placed into service, the W7220 Economizer module IMPORTANT: Table 10 illustrates the complete hierarchy. must be set up and configured for the installed system. Your menu parameters may be different depending on your configuration. IMPORTANT: During setup, the economizer module is For example if you do not have a DCV (CO ) sensor, then live at all times.
  • Page 34 Table 10 — W7220 Menu Structure* PARAMETER PARAMETER MENU PARAMETER DEFAULT RANGE AND NOTES VALUE INCREMENT † ECONO AVAIL YES/NO FIRST STAGE COOLING DEMAND (Y1–IN) YES = economizing available; the system can use outside air for free cooling when required ECONOMIZING YES/NO FIRST STAGE COOLING RELAY OUTPUT...
  • Page 35 Table 10 — W7220 Menu Structure* (cont) PARAMETER PARAMETER MENU PARAMETER DEFAULT RANGE AND NOTES VALUE INCREMENT † MECH COOL ON 0, 1, or 2 Displays stage of mechanical cooling that is active. HEAT STAGES ON Displays the stage of heat pump heating that is active. STATUS FAN SPEED LOW or HIGH...
  • Page 36 Table 10 — W7220 Menu Structure* (cont) PARAMETER PARAMETER MENU PARAMETER DEFAULT RANGE AND NOTES VALUE INCREMENT † ERV OAT SP †† 32°F 0 to 50°F ENERGY RECOVERY VENTILATOR UNIT OUTDOOR AIR increment by 1 TEMPERATURE SETPOINT Only displayed when AUX1 O = ERV EXH1 SET 0 to 100% Exhaust fan set point for single speed units.
  • Page 37 Table 10 — W7220 Menu Structure* (cont) PARAMETER PARAMETER MENU PARAMETER DEFAULT RANGE AND NOTES VALUE INCREMENT † STG3 DLY 2.0h 0 min, 5 min, COOLING STAGE 3 DELAY 15 min, then Delay after stage 2 cool has been active. Turns on second stage of 15 min intervals.
  • Page 38 Table 10 — W7220 Menu Structure* (cont) PARAMETER PARAMETER MENU PARAMETER DEFAULT RANGE AND NOTES VALUE INCREMENT † DA SYLK T ERR DISCHARGE AIR S-BUS SENSOR ERROR Discharge air sensor has failed or become disconnected - check wiring then replace sensor if the alarm continues. OA SENS T ERR OUTSIDE AIR TEMPERATURE SENSOR ERROR Outdoor air temperature sensor has failed or become disconnected -...
  • Page 39 Enthalpy Settings When the OA temperature, OA humidity and OA dew point are all below the selected boundary, the economizer sets the econo- When the OA temperature, enthalpy and dew point are below the mizing mode to YES, economizing is available. respective setpoints, the Outdoor Air can be used for economiz- ing.
  • Page 40 Standard or Single Speed Fan Operation The W (heating mode) is not controlled by the W7220 but it re- quires the status to know where to position the OA damper for FAN TYPE = 1SPEED is not used on 50GCQ units. minimum position for the fan speed.
  • Page 41: Checkout

    2SP H/C and 3 Speed Fan Operation FAN TYPE = 2SP H/C and FAN TYPE = 3SPEED are not used CAUTION on 50GCQ units. Failure to follow this caution may result in damage to CHECKOUT equipment. Be sure to allow enough time for compressor startup and shutdown between checkout tests so that you do Inspect all wiring connections at the economizer module’s termi- not short-cycle the compressors.
  • Page 42: Completing Return Air Smoke Sensor Installation

    Units equipped with factory-optional Return Air smoke detectors Step 12 — Adjust Factory-Installed Options require a relocation of the sensor module at unit installation. See SMOKE DETECTORS Fig. 54 for the as-shipped location. Smoke detector(s) will be connected at the Unit Control Board (UCB), at terminals marked “Smoke Shutdown.”...
  • Page 43: Step 14 - Fan Speed Set Up

    Unit Without Economizer or Economizer 2 Position Damper 2 Position Damper Fig. 56 — EconoMi$er ® IV Wiring Step 14 — Fan Speed Set Up UNITS WITH ELECTRO-MECHANICAL CONTROLS The Fan Speed set up controls are located on the lower section of the Unit Control Board (UCB).
  • Page 44: Units With Systemvu™ Controls

    ESP in. wg Factory Setting: Calculator 9.0 V 1500 Field Setting: 1625 Record field setting here 1750 1875 2000 Switch Range: 2125 10.0 2250 4.1 - 7.5 2375 6.9 - 8.7 2500 7.7 - 10.0 Field Accessories: Economizer * Overlap in A, B, C switch range 1 Stage E Heat designed for maximum field adjustment potential.
  • Page 45: Typical Unit Piping

    ESP in. wg Calculator 1301 1477 1639 1788 1925 2054 2174 2289 1500 1381 1544 1699 1843 1976 2101 2220 2332 1625 1463 1615 1763 1902 2031 2152 2268 2378 1750 1548 1688 1828 1962 2087 2206 2318 1875 2025 2146 2262 2372...
  • Page 46: Pre-Start And Start-Up

    Check Valve C Open (www.hvacpartners.com). Check Valve D Closed © 2021 Carrier Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Catalog No. 04-53500312-01 Printed in U.S.A. Form 50GCQ-4-6-02SI...
  • Page 47: Preliminary Information

    START-UP CHECKLIST 50GCQ 04-06 Single Package Rooftop Heat Pump Units (Remove and use for job file) NOTE: To avoid injury to personnel and damage to equipment or property when completing the procedures listed in this start-up checklist, use good judgment, follow safe practices, and adhere to the safety considerations/information as outlined in preced- ing sections of this Installation Instruction document.
  • Page 48 © 2021 Carrier Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Catalog No. 04-53500312-01 Printed in U.S.A. Form 50GCQ-4-6-02SI Pg CL-2 6-21 Replaces: 50GCQ-4-6-01SI...