SENSORWORX SWX-401-B Manual

Wireless wideview & hallway occupancy sensor

Advertisement

Catalog Number:
WIRELESS
WIDEVIEW & HALLWAY
OCCUPANCY SENSOR
BATTERY POWERED
OVERVIEW
The SENSORWORX
wireless wide view and hallway occupancy sensors are a
®
simple, yet reliable battery powered control solution. Preferred by contractors for
their flexible mounting methods, SENSORWORX wireless sensors greatly reduce
total installation time and wireless pairing fuss. Requiring just a few seconds per
device, SENSORWORX wireless sensors can be linked to one or more wireless
load controllers (such as the SWX-851 wireless wall switch, or a SWX-950
series wireless power pack). Additionally, these sensors can be configured to work
in applications with other wireless or wired ceiling, corner, or hallway sensors
to provide extended coverage in large or irregularly shaped spaces. As with all
SENSORWORX products, the latest passive infrared technology and techniques
are used to provide unmatched occupant detection performance and energy
savings. Additionally, wideview units are available with an integrated microphone
to provide overlapping passive acoustic detection for rooms with obstructions or
where occupant motion is limited.
BASIC OPERATION
Sensors detect movement in the infrared energy that radiates from occupants as
they move within the device's field-of-view. Once occupancy is detected, the sensor
immediately signals a wirelessly linked load controller (e.g. power pack) to switch
on or dim up the connected lighting. If equipped with passive dual technology (PIR/
Acoustic), the units microphone is then also enabled to further enhance detection
while the lights are on. At regular intervals, the sensor will retransmit its latest
occupancy status such that the load controller can keep lights on for occupants
during brief periods of inactivity, while returning the space to an energy saving
lights off (or dim) state once no longer occupied.
Date:
Project:
FEATURES
Pairs in Seconds with Wireless Controllers
Ã
Passive Infrared (PIR) Detection
Ã
Passive Dual Technology (PIR/Acoustic) Detection (Optional)
Ã
Wide View or Hallway (Long Range) Coverage Pattern Options
Ã
Compact Size and Matte Finish
Ã
Five Contractor Friendly Mounting Methods
Ã
Mounting Nipple Attachment with Integrated Hole Saw
Ã
Convenient Test Mode
Ã
SPECIFICATIONS
ELECTRICAL & WIRELESS
BATTERY TYPE
Requires one CR123(A) Lithium Battery
BATTERY LIFE
PIR Model - Designed for 10 yr.
Dual Tech. Models - Designed for 5 yr.
Non-Volatile Memory (saves all
settings regardless of battery state)
Blink Warning @10% Life
RANGE
80' line of site w/o obstruction (walls)
40' with obstruction (walls/floors)
FREQUENCY
915 MHz ISM Band
WIRELESS LINKING
Simple 3 sec. Push Button Process
SECURITY
All Wireless Data is Encrypted
ENVIRONMENTAL
OPERATING TEMP
32°F to 122°F (0°C to 50°C)
RELATIVE HUMIDITY
0-95% Non-Condensing,
Indoor Use Only
CODE COMPLIANCE
These sensors can be used to meet
ASHRAE 90.1, IECC, & Title 24 energy
code requirements.
PHYSICAL
SIZE
2.875" H x 2.75" W x 3.25"D
(7.30 x 6.98 x 8.25 cm)
WEIGHT
4.75 oz.
COLOR
White
LED INDICATION
Occupant Detection (in Test Mode only)
Wireless Linking (Pairing)
OPERATION
OPERATING MODES
Occupancy & Vacancy Modes -
Configured on Linked Controller
COMPATIBLE LOAD CONTROLLERS
SWX-851 Wall Switch
SWX-950 Series Power Packs
WIRELESS TEST MODE
Button Toggles On/Off
Wirelessly Linked Loads
COVERAGE TEST MODE
LED Blinks to Indicate Occupancy
TIME DELAY OPTIONS
Configured at Load Controller(s)
1, 5, 10, 15, 20, 30 min.
1
PAGE

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the SWX-401-B and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for SENSORWORX SWX-401-B

  • Page 1 SPECIFICATIONS their flexible mounting methods, SENSORWORX wireless sensors greatly reduce total installation time and wireless pairing fuss. Requiring just a few seconds per device, SENSORWORX wireless sensors can be linked to one or more wireless ELECTRICAL & WIRELESS PHYSICAL load controllers (such as the SWX-851 wireless wall switch, or a SWX-950...
  • Page 2: Ordering Info

    ORDERING INFO WIDE VIEW 120° MODEL NUMBER DESCRIPTION ° SWX-401-B Wireless Wide View 120 Sensor, PIR, Battery Powered SWX-421-B ° Wireless Dual Technology Wideview 120 Sensor, PIR/Acoustic, Battery Powered SWX-402-B Wireless Hallway Sensor, PIR, Battery Powered APPLICATIONS A single wireless wide view sensor provides an excellect soltion for a medium sized space like a conference room or small classroom. However, multiple wireless sensors can be easily linked to the same load controller(s) to provide coverage for larger spaces like an open office or large classroom.
  • Page 3: Operation Notes

    LOCKING 3-POSITION Replacement batteries are available at most retailers or home centers where batteries are à TILT ADJUSTMENT sold or from SENSORWORX. INSTALLATION OPTIONS SENSOR & MOUNTING WITH CHASE NIPPLE TOP INSTALLATION...
  • Page 4: Compatible Wireless Devices

    COMPATIBLE WIRELESS DEVICES The below chart lists the devices that can be used in a SENSORWORX wireless application. Note that sensors and remote switch & dimmer devices are transmit only devices and therefore must be linked to a load controller for switching or dimming of lighting.
  • Page 5 Le présent appareil est conforme aux CNR d’Industrie Canada applicables aux appareils radio exempts de licence. L’exploitation est autorisée aux deux conditions suivantes : (1) l’appareil ne doit pas produire de brouillage, et (2) l’utilisateur de l’appareil doit accepter tout brouillage radioélectrique subi, même si le brouillage est susceptible d’en compromettre le fonctionnement. SENSORWORX | 2a Research Parkway, Wallingford CT 06492 Five-Year Limited Warranty 203.678.4224 | sensorworx.com...

This manual is also suitable for:

Swx-421-bSwx-402-b

Table of Contents