SENSORWORX SWX-401-1 Installation & Operation Instructions

Low voltage wideview & hallway sensors

Advertisement

MODELS
MODEL #
PIR
ACOUSTIC
SWX-401-1
SWX-411-1
SWX-421-1
SWX-431-1
SWX-402-1
SWX-412-1
ADDITIONAL UNIT OPTIONS
- AR: Isolated Auxiliary Relay
FEATURES
Digital Passive Infrared (PIR) Detection
Ã
Passive Acoustic Detection (Optional)
Ã
Wide View (120°) or Hallway (Long Range) Coverage Pattern Options
Ã
Compact Size and Matte Finish
Ã
Five Contractor Friendly Mounting Methods
Ã
Mounting Nipple Attachment with Integrated Hole Saw
Ã
Convenient Test Mode and Adjustable Time Delays
Ã
Optional Ambient Light Override (Photocell)
Ã
OVERVIEW
Sensors detect movement in the infrared energy that radiates from occupants as they
move within the devices field-of-view. Once occupancy is identified the sensor signals a
connected power/relay pack to switch on the connected lighting. If equipped with passive
dual (PIR/Acoustic) technology, the unit's microphone is then also enabled to further
enhance detection while the lights are on. An internal timer is set to keep lights on
during brief periods of inactivity, and is reset every time occupancy is signaled by either
the passive infrared or acoustic detection technologies. Additionally, optional daylight
detection is available that will turn off controlled lighting whenever there is sufficient
ambient light in the space.
WIDEVIEW & HALLWAY SENSORS
PHOTOCELL
LENS TYPE
WIDEVIEW
WIDEVIEW
WIDEVIEW
WIDEVIEW
HALLWAY
HALLWAY
- HE: Humid Environment
LOW VOLTAGE
INSTALLATION & OPERATION INSTRUCTIONS
SPECIFICATIONS
ELECTRICAL
OPERATING VOLTAGE
12-24 VAC/VDC
CURRENT DRAW
2mA (PIR models)
16mA (Dual Tech. models)
18mA (Dual Tech. w/ Photoclell models)
OUTPUT
Logic High VDC (Occupied Mode)
RECOMMENDED POWER PACK
SENSORWORX (e.g., SWX-900)
ISOLATED RELAY RATING
1A @ 30 VDC/VAC
ENVIRONMENTAL
OPERATING TEMP
32° to 122°F (0° to 50°C) - Standard
-40° F/C (with -HE option)
RELATIVE HUMIDITY
0-95% Non-Condensing,
Indoor Use Only
ROHS COMPLIANT
APPLICATIONS
A single sensor may provide sufficient coverage in many spaces, however, multiple
low voltage sensors can be easily wired together to provide improved coverage for
large or irregular shaped spaces.
Classrooms
Large Offices
Ã
Ã
Open Areas
Conference Rooms
Ã
Ã
PHYSICAL
SIZE
2.875" H x 2.75" W x 3.25"D
(7.30 x 6.98 x 8.25 cm)
WEIGHT
4.75 oz.
COLOR
White
OPERATION
TIME DELAYS
30 sec. to 30 min.
10 Minute Default
5 sec.Test Mode
CODE COMPLIANCE
Sensors can be used to meet
ASHRAE 90.1, IECC, & Title 24
energy code requirements
Hallways/Corridors
Ã
1
PAGE

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the SWX-401-1 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for SENSORWORX SWX-401-1

  • Page 1 SWX-412-1 • • HALLWAY OPERATION RECOMMENDED POWER PACK TIME DELAYS SENSORWORX (e.g., SWX-900) ADDITIONAL UNIT OPTIONS 30 sec. to 30 min. ISOLATED RELAY RATING 10 Minute Default - AR: Isolated Auxiliary Relay - HE: Humid Environment 1A @ 30 VDC/VAC 5 sec.Test Mode...
  • Page 2: Coverage Pattern

    COVERAGE PATTERN PASSIVE INFRARED (PIR) TOP VIEW 8 ft Mount 18.2 SIDE VIEW WIDE VIEW 120° Small Motion Large Motion Small motion (e.g., hand movements) detection up to 40 ft (12.19 m) Ã Large motion (e.g., walking) detection up to 70 ft (21.34 m) Ã...
  • Page 3 WIRING CONT. MULTIPLE SENSOR WIRING LOW VOLTAGE SENSOR CLASS 2 CLASS 1 WIRING WIRING LOAD LOW VOLTAGE POWER PACK SENSOR * CAP UNUSED BLACK OR YELLOW WIRE LOW VOLTAGE SENSOR SEPARATE OCCUPANCY ZONE & OCCUPANCY + ON/OFF PHOTOCELL ZONE During occupied state, photocell output (blue wire) will turn lights off if ambient light level surpasses threshold and back on if level drops. Ã...
  • Page 4: Installation Options

    INSTALLATION OPTIONS LOCKING 3-POSITION TILT ADJUSTMENT PROGRAMMING CHASE NIPPLE & LOCK NU SENSOR & MOUNTING WITH CHASE NIPPLE TOP INSTALLATION BUTTON TO CEILING TILE OR 1/2” K MOUNTING RECOMMENDED CHASE NIPPLE LOCK NUT BRACKET SERRATED END FOR CUTTING THROUGH CEILING TILE ALTERNATE CHASE NIPPLE REAR INSTALLATION REAR POSITION...
  • Page 5: Configuration Settings

    CONFIGURATION SETTINGS FUNCTION #2 - TIME DELAY CONFIGURATION The length of time after the last occupancy event that the sensor will stay in the occupied state. CHANGING TIME DELAY SETTINGS:  FUNCTION #2 - TIME DELAY SETTINGS SETTING # DESCRIPTION 1. Read through the Time Delay Settings list on the right and note the number of the desired time delay setting (e.g., default is 4 = 10 minutes).
  • Page 6: Photocell Configuration

    25 fc (default) 35 fc 50 fc 75 fc 100 fc SENSORWORX | 2a Research Parkway, Wallingford, CT 06492 Five-Year Limited Warranty. 203.678.4224 | www.sensorworx.com Complete Warranty Terms Located at: sensorworx.com/warranty © 2021 BLP Technologies, Inc. All rights reserved. INS400 | REV 001–211122...

This manual is also suitable for:

Swx-411-1Swx-421-1Swx-431-1Swx-402-1Swx-412-1

Table of Contents