SENSORWORX SWX-201-B Installation & Operation Instructions

SENSORWORX SWX-201-B Installation & Operation Instructions

Wireless ceiling mount occupancy sensor

Advertisement

MODEL NUMBERS
DESCRIPTION
WIRELESS CEILING MOUNT SENSOR, PIR, 360° SMALL MOTION,
SWX-201-B
BATTERY POWERED
CEILING SENSOR TRIM RING FOR MOUNTING TO SINGLE GANG
SWX-299-JP
MUDRING, HANDY BOX, OR 4" OCTAGON BOX
OVERVIEW
The SENSORWORX
wireless ceiling mount occupancy sensor is a simple, yet reliable
®
battery powered control solution. Preferred by contractors for their flexible mounting
methods, SENSORWORX wireless sensors greatly reduce total installation time and
wireless pairing fuss. Requiring just a few seconds per device, SENSORWORX wireless
sensors can be linked to one or more wireless load controllers (such as the SWX-851
wireless wall switch, or a SWX-950 series wireless power pack). Additionally, these
sensors can be configured to work in applications with other wireless or wired ceiling,
corner, or hallway sensors to provide extended coverage in large or irregularly shaped
spaces. As with all SENSORWORX products, the latest passive infrared technology and
digital signal processing techniques are used to provide unmatched occupant detection
performance and energy savings.
BASIC OPERATION
Sensors detect movement in the infrared energy that radiates from occupants as
they move within the device's field-of-view. Once occupancy is detected, the sensor
immediately signals a wirelessly linked load controller (e.g. power pack) to switch on or
dim up the connected lighting. At regular intervals, the sensor will retransmit its latest
occupancy status such that the load controller can keep lights on for occupants during
brief periods of inactivity, while returning the space to an energy saving lights off (or dim)
state once no longer occupied.
FEATURES
Pairs in Seconds with Wireless
Ã
Controllers
Passive Infrared (PIR) Detection
Ã
360° Small Motion Coverage
Ã
Pattern
10 Year Battery Life Design
Ã
DETAILED OPERATION
By default, every ~60 seconds the sensor transmits whether or not occupancy was detected during the previous period.
Ã
Referred to as the sensor's "heartbeat", this period can be reduced to ~30 seconds although this will decrease expected battery life.
Ã
If a sensor transmitted "unoccupied" at its last heartbeat, any new occupancy detection event will be transmitted immediately.
Ã
If a sensor transmitted "occupied" at its last heartbeat, new occupancy events will only be transmitted at the heartbeat interval, thus conserving battery life.
Ã
The wirelessly linked wall switch load controller and/or power pack maintains a master time delay that is reset every time a linked sensor reports occupancy. Lights will be switched
Ã
off once all linked sensors have continously reported unoccupied for the duration of the time delay.
Compact Size and Matte Finish
Ã
Four Contractor Friendly Mounting
Ã
Methods
Mounting Nipple Attachment with
Ã
Integrated Hole Saw
Convenient Test Modes
Ã
CEILING MOUNT
OCCUPANCY SENSOR
INSTALLATION & OPERATION INSTRUCTIONS
SPECIFICATIONS
ELECTRICAL & WIRELESS
BATTERY TYPE
Requires one CR123(A) Lithium Battery
BATTERY LIFE
Designed for 10 Year Life
(under default settings)
Non-Volatile Memory (saves all
settings regardless of battery state)
Blink Warning @10% Life
RANGE
80' line of site w/o obstruction (walls)
40' with obstruction (walls/floors)
FREQUENCY
915 MHz ISM Band
WIRELESS LINKING
Simple 3 sec. Push Button Process
SECURITY
All Wireless Data is Encrypted
ENVIRONMENTAL
OPERATING TEMP
32°F to 122°F (0°C to 50°C)
RELATIVE HUMIDITY
0-95% Non-Condensing,
Indoor Use Only
CODE COMPLIANCE
These sensors can be used to meet
ASHRAE 90.1, IECC, & Title 24 energy
code requirements.
WIRELESS
PHYSICAL
SIZE
4.00" Diameter x 1.25" H
(10.16 x 3.17 cm)
WEIGHT
4.75 oz
COLOR
White
LED INDICATION
Motion Detection (when in Test Mode)
Wireless Linking (Pairing)
OPERATION
OPERATING MODES
Occupancy & Vacancy Modes
Configured on Linked Controller
COMPATIBLE LOAD CONTROLLERS
SWX-851 Wall Switch
SWX-950 Series Power Packs
WIRELESS TEST MODE
Button Toggles On/Off
Wirelessly Linked Loads
COVERAGE TEST MODE
White LED Illuminates Upon Detected
Occupancy
TIME DELAY OPTIONS
Configured at Load Controller(s)
1, 5, 10, 15, 20, 30 min.

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the SWX-201-B and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for SENSORWORX SWX-201-B

  • Page 1 SENSORWORX wireless sensors greatly reduce total installation time and Blink Warning @10% Life LED INDICATION wireless pairing fuss. Requiring just a few seconds per device, SENSORWORX wireless RANGE Motion Detection (when in Test Mode) sensors can be linked to one or more wireless load controllers (such as the SWX-851 80’...
  • Page 2 APPLICATIONS SMALL SPACES For control of small spaces like a private office, a single sensor linked to a wireless wall switch controller (SWX-851) is recommended (see diagram on right). Linking additional sensors is also an option if necessary. Switching from a second location (e.g. 3-way) is achieved by linking a remote wireless wall switch to the wireless switch controller.
  • Page 3: Installation Instructions

    COMPATIBLE WIRELESS DEVICES The below chart lists the devices that can be used in a SENSORWORX wireless application. Note that sensors and remote switch & dimmer devices are transmit only devices and therefore must be linked to a load controller for switching or dimming of lighting.
  • Page 4 WALL SWITCH POWER PACK WIRELESS SENSOR WALL SWITCH POWER PACK SWX-851 SWX-851 HOLD PRESS ONCE FOR 3 SEC SWX-201-B HOLD FOR 3 SEC SWX-950 SWX-950 HOLD PRESS ONCE FOR 3 SEC CONFIGURATION SENSOR HEARTBEAT TIME The period between transmissions of a wireless sensor is referred to as the sensor’s “heartbeat”. For best battery life performance, it is recommended that the default heartbeat time of 1 minute be used.
  • Page 5: Testing And Troubleshooting

    3. Afin de se conformer aux exigences d’exposition RF FCC / ISED, cet appareil doit être installé pour fournir au moins 20 cm de séparation du corps humain en tout temps SENSORWORX | 2a Research Parkeway, Wallingford CT 06492 Five-Year Limited Warranty.

This manual is also suitable for:

Swx-299-jpSwx-401-bSwx-402-b

Table of Contents