Honeywell WideBand TL-2055 User Manual
Honeywell WideBand TL-2055 User Manual

Honeywell WideBand TL-2055 User Manual

Portable, explosion-proof ir test lamp

Advertisement

User Manual
Portable, Explosion-Proof
WideBand™ IR Test Lamp
Model TL-2055
Used for Testing Honeywell Analytics Model FS24X and
FS18X Detectors
FM Approved for Class I, Div. 1 & 2 Hazardous Areas

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the WideBand TL-2055 and is the answer not in the manual?

Questions and answers

Summary of Contents for Honeywell WideBand TL-2055

  • Page 1 User Manual Portable, Explosion-Proof WideBand™ IR Test Lamp Model TL-2055 Used for Testing Honeywell Analytics Model FS24X and FS18X Detectors FM Approved for Class I, Div. 1 & 2 Hazardous Areas...
  • Page 2: Notices And Trademarks

    In no event is Honeywell liable to anyone for any indirect, special or consequential damages. The information and specifications in this document are subject to change without notice.
  • Page 3 Entsorgungsanlagen gegeben werden. RAEE. Per ulteriori informazioni sullo Um weitere Informationen zum Recycling smaltimento di questo prodotto dieses Produkts zu erhalten wenden Sie contattare l’ente locale preposto, il sich an Ihre Kommunalbehörde, Ihren distributore o il produttore. Lieferanten oder den Hersteller. HONEYWELL...
  • Page 4: About This Product

    Optical Fire and Flame Detectors only and will NOT test other manufacturers’ IR flame detectors. Other manufacturers’ IR Test Lamps should not be used to test Honeywell Analytics Detectors because Honeywell Analytics Detectors are designed to REJECT pulsing test lights as false alarm sources. This indoor/outdoor Test Lamp is powered by rechargeable batteries.
  • Page 5: Symbol Definitions

    It may also be used to alert against unsafe practices. CAUTION: Symbol on the equipment refers the user to the product manual for additional information. The symbol appears next to required information in the manual. HONEYWELL...
  • Page 6: General Description

    The WideBand™ IR Test Lamp is designed for use in Class , Div. 1 & 2 Area Classification indoors or outdoors. • The TL-2055 is used ONLY to test Honeywell Analytics Model FS24X, and FS18X Multi-Spectrum Fire Detectors “end-to-end”. • It is powered by a rechargeable, long-life, more capacity, “memory- free”...
  • Page 7 Notes: 1. Battery Recharging – Recharge the internal battery pack with Honeywell Analytic’s Part No. PSU-15 100 – 240 VAC wall charger (see above) that includes worldwide interchangeable receptacle plugs. A fully charged battery pack should test typically up to 20 Detectors.
  • Page 8 CAUTION: Avoid looking directly into the Test Lamp when it is operating! The TL-2055 Test Lamp will only test the Honeywell Analytics FS24X and FS18X Detectors. This Test Lamp will not calibrate or change the configuration of the Detectors in test. It generates modulated radiant spectral energy in a broad band of IR wavelengths causing the Detector to ALARM.
  • Page 9: Maintenance

    Test Lamp will turn on. e. Allow 3 to 4 hours for complete charging. Use ONLY the wall charger supplied by Honeywell Analytics. Maintenance: 1. Make certain that the Test Lamp is fully charged before each use.
  • Page 10 Degrees of protection provided by enclosures (IP code) EN 60529 +A2 2013 Explosive Atmospheres – Part 31: Equipment dust EN60079-31 2013 ignition protection by enclosure “t” 60067-0 2011 60079-1 2014 60079-31 2013 60529 2013 60079-0 2012 60079-1 2014 60079-31 2014 60529 +A2 2013 HONEYWELL...
  • Page 11: Spare Parts

    Spare Parts: • Battery Pack, 12 VDC P/N: PW-3123-0005 • 110/220 VAC Wall Charger P/N: PSU-15 • IR Gold-plated Reflector Lamp P/N: LAMP-3135-0002 NOTE: This specification subject to change without notice. HONEYWELL...
  • Page 12 Channel Partner: sales@norrscope.com 1998M0900 Rev. D © 2018 Honeywell International Inc.

Table of Contents