6.4.12 To connect the electricity meters ........ 18 for basic and advanced usage 6.4.13 To connect the safety thermostat (normally closed ▪ Format: Digital files on https://www.daikin.eu. Use the search contact) ............... 18 function to find your model. 6.4.14 Smart Grid..............19 ▪...
▪ A subset of the latest technical data is available on the regional Daikin website (publicly accessible). WARNING ▪ The full set of the latest technical data is available on the Daikin Business Portal (authentication required). Electrical wiring MUST be in accordance with the...
Sealing rings for shut-off valves (space heating water ≥600 circuit) Sealing rings for field-supplied shut-off valves (domestic hot water circuit) "No glycol" tag (to attach to the field piping near the filling (mm) point) Installation manual EPVX10+14S18+23A Daikin Altherma 4 H F 4P773386-1B – 2025.01...
Handle with care. ▪ When the user interface panel is removed, make sure it does not drop. 2× 6 Rotate the switch box. 3 Remove the front plate. EPVX10+14S18+23A Installation manual Daikin Altherma 4 H F 4P773386-1B – 2025.01...
4 Adjust the height of the leveling feet to compensate for floor irregularities. The maximum allowed deviation is 1°. ≤1° 3× NOTICE Do NOT tilt the unit forwards: 1° 1° 0° Installation manual EPVX10+14S18+23A Daikin Altherma 4 H F 4P773386-1B – 2025.01...
Deformed pipes can cause the unit to malfunction. setting, the maximum LWT setpoint will also be reduced by Delivered as accessory: 5°C to allow stable control towards the setpoint. EPVX10+14S18+23A Installation manual Daikin Altherma 4 H F 4P773386-1B – 2025.01...
Expansion vessel (recommended) NOTICE Install air purge valves at all local high points. 5.2.2 To connect the recirculation piping Prerequisite: Only required if you need recirculation in your system. Installation manual EPVX10+14S18+23A Daikin Altherma 4 H F 4P773386-1B – 2025.01...
Optionally, you can install normally closed valves (located indoors construction MUST comply with applicable near the piping entry/exit points). These valves can prevent that all legislation. water from the indoor piping is drained when the freeze protection EPVX10+14S18+23A Installation manual Daikin Altherma 4 H F 4P773386-1B – 2025.01...
▪ Maximum running current and/or inrush current of Choose which terminal pins to use for which connected component is >0.3 A component. X42M Installation manual EPVX10+14S18+23A Daikin Altherma 4 H F 4P773386-1B – 2025.01...
4 18]. closed Changeover to "6.4.10 To connect the changeover to Smart Meter Contact Smart Grid meter contact. source" [ 4 18]. external heat source external heat Grid" [ 4 19]. "6.4.14 Smart control EPVX10+14S18+23A Installation manual Daikin Altherma 4 H F 4P773386-1B – 2025.01...
Page 12
(field supply, see This is a Field IO input connection. addendum book optional "6.3 Field IO connections" [ 4 10]. equipment) [13] Field IO (External outdoor sensor) [5.22] Ambient sensor Installation manual EPVX10+14S18+23A Daikin Altherma 4 H F 4P773386-1B – 2025.01...
The output of the backup heater depends on the wiring and the selection in the user interface. Make sure that the power supply matches the selection in the user interface. Installation manual EPVX10+14S18+23A Daikin Altherma 4 H F 4P773386-1B – 2025.01...
Page 15
To be used instead of the factory-mounted wire harness (with connector X21YA). F1B Overcurrent fuse (field supply) Q1DI Earth leakage circuit breaker (field supply) Q1L Thermal protector backup heater [5.5] Backup heater Specifications of wiring components EPVX10+14S18+23A Installation manual Daikin Altherma 4 H F 4P773386-1B – 2025.01...
X42M NOTICE Wiring is different for a NC (normally closed) valve and a NO (normally open) valve. Installation manual EPVX10+14S18+23A Daikin Altherma 4 H F 4P773386-1B – 2025.01...
Pump runs when there is a request from the main zone. ▪ C/H pump ext. add.: Pump runs when there is a request from the additional zone. ▪ [4.6] Schedule EPVX10+14S18+23A Installation manual Daikin Altherma 4 H F 4P773386-1B – 2025.01...
▪ The safety thermostat is automatically resettable. ▪ The safety thermostat has a maximum temperature variation rate of 2°C/min. ▪ There is a minimum distance of 2 m between the safety thermostat and the 3‑way valve. Installation manual EPVX10+14S18+23A Daikin Altherma 4 H F 4P773386-1B – 2025.01...
The related settings in case of Smart Grid meter are as follows: ▪ [13] Field IO (Smart Meter Contact) ▪ [5.25.1] Operation mode (Smart Meter Contact) ▪ [5.30] Smart meter limit EPVX10+14S18+23A Installation manual Daikin Altherma 4 H F 4P773386-1B – 2025.01...
4 13]. electrical wiring to the indoor ▪ Wires: 0.5 mm² ▪ This is a Field IO input connection. See "6.3 Field IO connections" [ 4 10]. Low voltage Smart Grid meter Installation manual EPVX10+14S18+23A Daikin Altherma 4 H F 4P773386-1B – 2025.01...
Configuration wizard – Overview ▪ Date Depending on your unit type and the selected settings, some steps ▪ Clock format (24 hours or AM/PM) will not be visible. ▪ Time EPVX10+14S18+23A Installation manual Daikin Altherma 4 H F 4P773386-1B – 2025.01...
▪ 2: auto SH reduced/DHW on: When a heat pump failure occurs, space heating is reduced but domestic hot water is still available. Installation manual EPVX10+14S18+23A Daikin Altherma 4 H F 4P773386-1B – 2025.01...
Select this value in case of connection to multi-zoning wired Related settings: controls, wired room thermostats (EKRTWA) or wireless room thermostats (EKRTR1, EKRTRB) [10.14] Additional zone 2/4 Set: ▪ Heating setpoint mode: ▪ Fixed ▪ Weather dependent Installation manual EPVX10+14S18+23A Daikin Altherma 4 H F 4P773386-1B – 2025.01...
▪ Hysteresis (select value) To define a weather-dependent curve [10.19] Configuration wizard Define the weather-dependent curve using two setpoints (b, c). Example: The configuration wizard is finished! EPVX10+14S18+23A Installation manual Daikin Altherma 4 H F 4P773386-1B – 2025.01...
[3.10] Bizone kit installed The following table describes how to fine-tune the weather- dependent curve of a zone: [3.11] Undercooling setpoint [3.12] Overheating setpoint [4] Domestic hot water [4.12] Hysteresis Installation manual EPVX10+14S18+23A Daikin Altherma 4 H F 4P773386-1B – 2025.01...
[5] Settings ▪ In the installation manuals (outdoor unit and indoor unit) or in the installer reference guide [5.1] Forced defrost ▪ In the Daikin e-Care app [5.2] Quiet operation [5.5] Backup heater NOTICE First operation. The first time the unit starts in heating or [5.6] Capacity shortage...
Service Manual ESIE22-02 "Systems using The indoor unit is properly mounted. R290 refrigerant" (available on https://my.daikin.eu). The following field wiring has been carried out according Checklist during commissioning to this document and the applicable legislation: ▪...
Page 29
The compressor of Daikin Altherma 4 heat pumps is shipped in a locked state. During commissioning, it must be unlocked via the Digital Key function on the Daikin e-Care app and on the user interface of the indoor unit. Daikin Altherma 4...
When the commissioning process is completed, the valve. unit is ready to operate. Turn fully open and leave fully Turn fully open and leave fully open. open. Installation manual EPVX10+14S18+23A Daikin Altherma 4 H F 4P773386-1B – 2025.01...
1 Download the latest user interface software (available on https://my.daikin.eu; search via the Software Finder). 2 Put the software on a USB-stick (must be formatted as FAT32). Entering maintenance mode can take up to ~15 minutes. The unit is finishing 3 Power OFF the unit.
Stop button is NOT available 1 Switch to installer mode. in early versions of the user interface software. Instead, 5678 to stop the function. Installation manual EPVX10+14S18+23A Daikin Altherma 4 H F 4P773386-1B – 2025.01...
If these limits are reached the actuator test will continue and activate that component again when the limitations allow its operation. ▪ [7.1.1] Booster heater test ▪ [7.1.2] Bivalent test ▪ [7.1.3] Tank Boiler test EPVX10+14S18+23A Installation manual Daikin Altherma 4 H F 4P773386-1B – 2025.01...
Page 34
▪ The underfloor heating screen is used as home screen until the finish of the program. 4 Tap Stop to stop the underfloor heating screed dryout. Installation manual EPVX10+14S18+23A Daikin Altherma 4 H F 4P773386-1B – 2025.01...
▪ Show the user what to do for the maintenance of the unit. my.daikin.eu). Technical data A subset of the latest technical data is available on the regional Daikin website (publicly accessible). The full set of the latest technical data is available on the Daikin Business Portal (authentication required). EPVX10+14S18+23A...
Page 38
Shut-off valve – Normally closed Shut-off valve NO Shut-off valve – Normally open Smart Grid PV power pulse Smart Grid photovoltaic power meter pulse meter Space cooling/heating Space cooling/heating Installation manual EPVX10+14S18+23A Daikin Altherma 4 H F 4P773386-1B – 2025.01...
Page 39
3N~, 50 Hz, 400 V AC 1N~, 50 Hz, 230 V AC 1N~, 50 Hz, 230 V AC 3~, 50 Hz, 230 V AC 2~, 50 Hz, 230 V AC 4D152933B (1/2) EPVX10+14S18+23A Installation manual Daikin Altherma 4 H F 4P773386-1B – 2025.01...
Page 40
2 core 1 mm² Max. load: 0.1 A - 230 V AC Bizone mixing kit A30P X44M -t° %H2O 3 core 0.75 mm² Voltage: 12 V DC 4D152933B (2/2) Installation manual EPVX10+14S18+23A Daikin Altherma 4 H F 4P773386-1B – 2025.01...
Page 44
4P773386-1 B 00000005 4P773386-1B 2025.01...