Table of Contents 1. Notes on This Manual .......................... 1 1.1 Scope of Validity .......................... 1 1.2 Target Group ..........................1 1.3 Symbols Used ..........................1 2. Safety ..............................3 2.1 Appropriate Usage ........................3 2.2 PE Connection and Leakage Current ..................4 3.
Page 3
7.2 RCR wiring ..........................45 7.3 SG ready wiring and setting .......................46 7.4 Reactive Function Setting ......................47 8. Firmware Upgrading .......................... 51 9. Operation ............................56 9.1 Control Panel ..........................56 9.2 Function Tree ..........................57 10. Maintenance ............................. 58 10.1 Alarm List ..........................58 10.2 Troubleshooting and Routine Maintenance ................
Notes on This Manual 1.1 Scope of Validity This manual describes the assembly, installation, commissioning, maintenance and troubleshooting of the following model (s) of products: H3-5.0-Smart H3-6.0-Smart H3-8.0-Smart H3-9.9-Smart H3-10.0-Smart H3-12.0-Smart H3-15.0-Smart AC3-5.0-Smart AC3-6.0-Smart AC3-8.0-Smart AC3-9.9-Smart AC3-10.0-Smart AC3-12.0-Smart AC3-15.0-Smart Note: Please keep this manual where it will be accessible at all times. 1.2 Target Group This manual is for homeowners/ purchaser/ qualified electricians.
Page 5
Danger! Before electrical connections, please make sure that the inverter switch and all switches connected to the inverter are set to "OFF", otherwise electric shock may occur! Ensure that the inverter is undamaged and all cables are voltage free before performing electrical work.
2. Safety 2.1 Appropriate Usage H3/AC3 Smart series inverters are designed and tested in accordance with international safety requirements. However, certain safety precautions must be taken when installing and operating this inverter. The installer must read and follow all instructions, cautions and warnings in this installation manual.
or equipment damage. Before connecting the inverter to the power distribution grid, contact the local power distribution grid company to get appropriate approvals. This connection must be made only by qualified technical personnel. Do not install the equipment in adverse environmental conditions such as in close proximity to flammable or explosive substances;...
3. Introduction 3.1 Basic Features H3/AC3 Smart series are high-quality inverters which can convert solar energy to AC energy and store energy into battery. The inverter can be used to optimize self-consumption, store in the battery for future use or feed-in to public grid. Work mode depends on PV energy and user’s preference.
Page 9
This diagram is an example for an application in which neutral is separated from the PE in the distribution box. For countries such as China, Germany, the Czech Republic, Italy, etc, please follow local wiring regulations.
Page 10
• Work modes: Work modes Description Priority: load>battery>grid Self-use The energy produced by the PV system is used to optimize self-consumption. The (with PV Power) excess energy is used to charge the batteries, then exported to gird. When no PV is supplied, the battery will discharge for local loads first. Battery will Self-use charge when excess generation from other generation sources is detected.
3.2 Dimensions 3.3 Terminals of inverter Item Description Item Description DC Switch Meter COMM/DONGLE Antenna EPS/GRID Grounding Screw Note: Only authorized personnel are permitted to set the connection.
Export Control AC inrush current [A] 15A@0.5ms Max. output fault current [A] 150A@0.5ms Max. output over current protection [A] THDI <3%@rated power AC INPUT Max. AC power [VA] 6000 7200 9600 12000 12000 14400 16000 Rated grid voltage 400V/230Vac; 380V/220Vac, 3L/N/PE (AC voltage range) [V] Rated grid frequency [Hz] 50/60Hz, ±5Hz...
Anti-islanding protection Output short protection Leakage Current Protection Insulation Resistor Detection Over Voltage category III (AC side), II (DC side) Reverse connect protection Over-current protection /Over-temperature protection DC/AC Surge Protection Type II (PV)/Type II (AC) AFCI protection optional DC switch 4.6 General Data DIMENSION AND WEIGHT Dimensions (W*H*D) [mm]...
5. Installation 5.1 Check for Physical Damage Make sure the inverter is intact during transportation. If there is any visible damage, such as cracks, please contact your dealer immediately. 5.2 Packing List Open the package and take out the product, please check the accessories first. The packing list shown as below.
5.3 Mounting • Installation Precaution Make sure the installation site meets the following conditions: Not in direct sunlight. Not in areas where highly flammable materials are stored. Not in potential explosive areas. Not in the cool air directly. Not near the television antenna or antenna cable. Not higher than altitude of about 2000m above sea level.
Page 17
• Mounting Steps Tools required for installation: Manual wrench; Electric drill (drill bit set 8mm); Crimping pliers; Stripping pliers; Screwdriver. Installation angle requirements: ● Do not tilt the energy storage forward, horizontally, upside down, backward and sideways. Installation space requirements: When installing energy storage, ensure that there are no other equipment and flammable and explosive materials around, and reserve enough space to ensure the installation heat dissipation and safety isolation requirements.
Page 18
Before drilling holes, please ensure the distance between the machine and nearby objects. Drill holes with electric drill, make sure the holes are at least 50mm deep and 8mm wide, and then tighten the expansion tubes. CAUTION Please pay attention to safety when using the tools. Unsafe use of the drilling tools may cause damage to the body.
Page 19
Insert the expansion tubes into the holes and tighten them. Install the bracket with the expansion screws. Match the inverter with wall bracket Mount the inverter to the bracket. Secure the inverter with the M5 screw and washer.
6.2 PV Connection (For H3 Smart Only) Step 1: PV String Connection NOTE Note! Please choose a suitable external DC switch if the inverter does not have a built-in DC switch. WARNING Warning! PV module voltage is very high and within a dangerous voltage range, please comply with the electric safety rules when connecting.
Page 22
Step 2: PV Wiring • Turn off the DC switch. • Choose 12 AWG wire to connect the PV module. • Trim 6mm of insulation from the wire end. • Separate the DC connector (PV) as below. NOTICE When making PV terminals, please make sure that the copper cores of PV positive and PV negative terminals and the copper cores on the inverter can be inserted, and use a multimeter to measure whether the positive and negative terminals are correct, otherwise the machine may not work normally or individual strings may not work.
• Unlock the DC connector DANGER Before separating the DC connector, make sure that there is no current on the DC connector. You can measure it with current clamp or disconnect the DC switch, otherwise serious safety accidents may occur. Make sure that the power cable connected to the inverter is connected vertically and that the vertical length is greater than 30 cm.
- Separate the connectors by hand. 6.4 Grid Connection Step 1: Grid String Connection H3/AC3 Smart series inverters are designed for three-phase grid. Per voltage range is 220/230/240V; frequency is 50/60Hz. Other technical requests should comply with the requirement of the local public grid.
WARNING WARNING! A micro-breaker for max output overcurrent protection device shall be installed between inverter and grid, and the current of the protection device is referred to the table above, any load SHOULD NOT be connected with the inverter directly. Step 2: Grid Wiring •...
Use the crimping pliers to press the ground cable into the ground terminal, screw the ground screw with screwdriver as shown below: 6.6 Installation Instructions 1) Dimension of stripping line Dimension of stripping line outside machine...
Page 27
2) Wiring Precautions 3) Seal accessory option A. Ø18: The recommended outer diameter of the cable is 17.5-18.5mm. B. Ø21: The recommended outer diameter of the cable is 19-21mm. C. Ø6: When the four wire system is used, the special hole for the ground wire is recommended to be applicable to the outer diameter of the cable.
6.7 Installation steps for 5-core wire Thread the stripped wire into the lock nut and the main body in turn. (the flexible wire needs to be riveted to the insulated terminal) First, insert the EPS end cable into the EPS end of the rubber core. After the cable is in place through the perspective hole, tighten the screw using an S2.5 hexagon wrench with a torque of 2.5±0.1N·m.
Page 29
Insert the main body into the rubber core and hear the "click" sound. Seal plugin to main body. Tighten the nut with an open-ended wrench. (torque 10.0±0.1N·m, Complete the installation)
Page 30
Inserted Open the latch. Align the female end with the male end in the anti-stay position. After the male and female insert the card point into the tracks lot, press the lock. Tighten the screws with the S2.5 hexagon wrench with a torque of 2.5±0.1Nm. Installation completed.
6.8 RJ45 connection The machine has three RJ45 terminals, which are meter, Ethernet, and RCR functions The definition of meter port pin is as follows: The definition of Ethernet port pin is as follows: The definition of DRM port pin is as follows: RJ45 Wiring Installation Procedure Insert the network cable into the wire-locking nut, sealing plug and mainbody in turn.
Page 32
Tighten the connector mainbody by the open-ended wrench into the RJ45 panel mount connector with a torque 1.2±0.2N·m. Insert the sealing plug into the main body of RJ45 cable end connector. Tighten the connector's nut by the open-ended wrench with a torque 1.2±0.2N·m.
6.9 Antenna Connection Tighten the Antenna's nut by the open-ended wrench with a torque 1.2±0.3N·m. 6.10 COM connection Introduction to COM port: The COM port mainly includes EMS485, Meter485, WIFI485, Estop port, two relay output ports, two parallel ports and a toggle switch, +12V and corresponding relay output signals. The ripple control function is described below.
Page 34
DY OUT: The machine has two DY OUT interfaces, with two internal contacts of relays hat can drive loads of 230VAC1A/50VDC0. 5A, and can be used for powering on and starting heat pumps. PARA port RJ45: Used for parallel communication, it is necessary to set the DIP switch to the ON state during parallel operation.
Page 35
And use a screwdriver to crimp the wire, screwing torque 1.2+/-0.1N·m. Arrange the core line, the rubber core area must not appear to ride the line. The rubber core is loaded into the main body and accompanied by a"click"sound. Install the plug into the main body and plug the holes without wires with a plug. Lock wire nut screwed onto the body, torque 2.5+/-0.1N-m, then complete installation.
6.11 Electrical Connection Communication Device Installation (Optional) H3/AC3 Smart series inverters are available with multiple communication options such as WiFi-, GPRS-, LAN- or 4G-Dongle, RS485 and Smart meter with an external device. Operating information like output voltage, current, frequency, fault information, etc., can be monitored locally or remotely via these interfaces.
Page 37
Configuration: Note: The module is powered on and started, please wait for one minute to start the WiFi Config. Web Configuration. Step 1: Connect your mobile device with Smart WiFi. The SSID of the Smart WiFi is ‘W-xxxxx’ and the password is ‘mtmt2020’.
Page 38
APP Configuration: Step 1: Open the APP, click "Local Distribution Network" on the login page. Then click “Wifi Config”.
Page 39
Or sign in app, click on the “me” page. Then click “WiFi Config”. Step 2: Please scan the "SN" on the collector. Step 3: Connect your mobile device with Smart WiFi. The SSID of the Smart WiFi is ‘W-xxxxx’ and the password is ‘mtmt2020’.
Page 40
RS485 RS485 is a standard communication interface which can transmit the real time data from inverter to PC or other monitoring devices. Meter The inverter has integrated export limitation functionality. To use this function, a power meter must be installed. For Meter installation, please install it on the grid side. Note: •...
Export control setting: Settings On-Grid Parm Export Control xxxxxW The electricity meter is connected as follows: Meter connection: Meter Connection Diagram...
Page 42
Insert L1/L2/L3/N wires and RS485A/B cable into the meter. Please refer to the meter wiring diagram on side of meter itself. Insert L1/L2/L3/N wires, CT and RS485A/B cable into the meter. Please refer to the meter wiring diagram on side of meter itself. Notes: The 2,5,8 of the CT meter are connected to the three live wires L1, L2, and L3 respectively.
Page 43
The transformation ratio setting of a CT meter needs to be consistent with the transformation ratio of a CT meter. The transformation ratio setting method. for a CT meter is as follows: The address of the second meter is 2. Please ensure that the address is 2, otherwise the communication of the first meter will be affected, and the output and monitoring data of the inverter will be affected.
Page 44
• • BMS is used to communicate with the battery for data exchange, please use the network cable configured for the battery to communicate the communication distance should not exceed 10m. - Insert one side of CAT 7 cable into the first inverter's CAN port and the other side into the next inverter’s CAN port.
Page 45
Introduction to the function of unbalanced load: If the load of each phase in the household load is different, and the power of each phase output by the inverter is the same, there will be one phase output and one phase input. In order to avoid this situation, the unbalanced load can be turned on.
6.12 EPS Connection (Non-parallel State) Common loads description Under EPS mode, if need to connect the inductive load on EPS port, please ensure that the instantaneous power of the load at startup is lower than the maximum power of the EPS mode. Below table shows some conventional and reasonable loads for you reference.
6.14 Inverter Start-Up Please refer to the following steps to start up the inverter. Ensure the inverter fixed well. Make sure all the DC wirings and AC wirings are completed. Make sure the meter is connected well. Make sure the battery is connected well. Make sure the external EPS contactor is connected well (if needed).
7. Main function implementation 7.1 Drm wiring DRM0 setting Settings Feature Parm DRM0 Enable/Disable DRM supports several demand response modes by configuring control signals as below. Asserted by Mode Requirement shorting pins DRM0 DRM0 Operate the disconnecting device, under Australian safety regulations. DRM1 DRM1 DRM0...
Switching state Output active power (%Pn) No contact closed 100% Several contacts closed 100% Contact DRM1 to +3.3V Contact DRM2 to +3.3V Contact DRM3 to +3.3V Contact DRM4 to +3.3V Immediate OFF Contact Drm0 to 3.3V AC Max.Chr power limit to 4.2kw under Vde4105 Safty 7.3 SG ready wiring and setting SG Ready •...
Configure SG ready power management settings * SgReadyFunction: Disable/Enable sgready function. * RestartTime: Interval between two launches of sgready. * SgReadyStartPower: when the feed-in power exceeded the set value, the heat pump starts operation. * SgReadyStopPower: When the feed-in power is less than the set value, the heat pump stops operation.
Page 51
Step2: Enter SN of Inverter Step3: Click Here Step4: Click Safety-Reactive, Select the Reactive Power Mode Enable button.
Page 52
1. Fixed PF Over If you want set the fix PF over, Find the Reactive PowerControl Mode dropdown menu and select the FixedPFOver option; Set fixed PF parameters according to your needs, with a default value of 1; 2. Fixed PF Under If you want set the fix PF Under, Find the Reactive PowerControl Mode dropdown menu and select the FixedPFUnder option;...
Page 53
4. Fixed Q If you want set the fix Q, Find the Reactive PowerControl Mode dropdown menu and select the FixedQ option; Set fixedQ parameters according to your needs; 5. Q and U function setting If you want set the Q and U, Find the Reactive PowerControl Mode dropdown menu and select the Qu;...
8. Firmware Upgrading User can upgrade inverter's firmware via a U-disk. • Safety check Please ensure the inverter is steadily powered on. Inverter must keep the battery on through whole procedure of upgrading. Please prepare a PC and make sure the size of U-disk is under 32G, and the format is fat 16 or fat 32. CAUTION Caution! Please DO NOT apply USB3.0 U-disk on inverter USB port, the inverter USB port only support for...
Page 55
• local upgrading: USB Upgrade Operation Guide (Apply to H3 Smart) Introduction: The inverter is a high-tech integrated system with a CPU controller, which requires maintenance and upgrade. The upgrade is easy to operate with by end user or installer, upgrade files will be provided by manufacturer, please prepare everything ready before performing this upgrade.
Page 56
2) Install the USB disk on your laptop, open it and create a folder named‘update’ 3) Create another three separate subfolders named ‘manager’ ‘master’ ‘slave’under ‘update’ folder. 4) Put the upgrade file into corresponding folder as shownbelow * Formate fo the file name: Model_Firmware type_Vx_xx File names example: U:\update\master\H3 Smart_Master_Vx_xx...
Page 57
4. Only turn on DC breaker (make sure PV voltage is above 120V) wait for 10 seconds, the inverter screen will show as below: 5. If you want to upgrade the inverter firmware, click “up” or “down” to choose the targeted firmware, then click “enter”...
Page 58
6. Remove the USB disk after upgrade completed. Follow the procedure blew and click the option to view the version: Menu -> About -> Inv Ver 7. Turn on AC &DC breaker. If you updated the HMI, long press the “enter” and click “set” to turn on the inverter.
9. Operation 9.1 Control Panel Object Name Function LCD screen Display the information of the inverter. Red: The inverter is in fault mode. Indicator LED Blue: The inverter is normally connected to the battery. Green: The inverter is in normal state. Up button: Move cursor to upside or increase value.
10. Maintenance This section contains information and procedures for solving possible problems with the inverters and provides you with troubleshooting tips to identify and solve most problems that can occur. 10.1 Alarm List Fault Code Solution Grid is lost. Grid Lost Fault •...
Page 62
Battery current high detected by software. SW Bat Cur Fault • Disconnect PV, grid and battery, then reconnect. • Or seek help from us, if not go back to normal state. The isolation is failed. • Please check if the insulation of electric wires is damaged. Iso Fault •...
Page 63
Battery current high detected by hardware. HW Bat Cur Fault • Disconnect PV, grid and battery, then reconnect. • Or seek help from us, if not go back to normal state. The communication between master and manager is fail. SCI Fault •...
Page 64
The grid relay keeps open or close. Grid Relay Fault • Disconnect PV, grid and battery, then reconnect. • Or seek help from us, if not go back to normal state. The communication between master and slave is fail. RDSP SPI Fault •...
10.2 Troubleshooting and Routine Maintenance • Troubleshooting Please check the fault message on the System Control Panel or the fault code on the inverter information panel. If a message is displayed, record it before doing anything further. Attempt the solution indicated in table above. If your inverter information panel is not displaying a fault light, check the following to make sure that the current state of the installation allows for proper operation of the unit: Is the inverter located in a clean, dry, adequately ventilated place?
11. Decommissioning 11.1 Dismantling the Inverter Disconnect the inverter from DC (for H3 Smart only) Input and AC output. Wait for 15 minutes for the inverter to fully de-energize. Disconnect communication and optional connection wirings. Remove the inverter from the bracket. Remove the bracket if necessary.
Page 68
The copyright of this manual belongs to FOXESS CO., LTD. Any corporation or individual should not plagiarize, partially or fully copy (including software, etc.), and no reproduction or distribution of it in any form or by any means is permitted. All rights reserved. FOXESS CO., LTD.