Download Print this page

Detectortesters Solo 330 Dispenser Procedure

For smoke, heat, co and multi-sensor detectors emea region

Advertisement

Quick Links

FUNCTIONAL TEST
PROCEDURES
For Smoke, Heat, CO and
Smoke
multi-sensor detectors
Heat
Clear
EMEA Region
Menu
Status
detectortesters.com

Advertisement

loading
Need help?

Need help?

Do you have a question about the Solo 330 Dispenser and is the answer not in the manual?

Questions and answers

Summary of Contents for Detectortesters Solo 330 Dispenser

  • Page 1 FUNCTIONAL TEST PROCEDURES For Smoke, Heat, CO and Smoke multi-sensor detectors Heat Clear EMEA Region Menu Status detectortesters.com...
  • Page 2: Smoke Detectors

    Smokesabre-100-xxx > Smoke Detectors To carry out a functional test of a smoke detector, use a solution from Detectortesters. IMPORTANT - Solo aerosols are optimised for use with the Solo330/332 dispenser Use XTR2, Testifire (1000 or 2000 series) or Solo365 with the appropriate non- and are silicone-free.
  • Page 3 IMPORTANT - Before any work begins on the fire detection system, all necessary To carry out a functional test of CO detectors use Detectortesters model Testifire persons should be notified that the fire system is to undergo maintenance and that (2000 series) with the CO capsule TC3 or the SoloC3 aerosol can with the Solo330 the system, or part of it, will be temporarily out of service.
  • Page 4 Functional Smoke Testing with Testifire Functional Smoke Testing with Solo 365 1. Press and hold the red power button for 2 seconds 1. Hold the power button until the status indicator LEDs flash slow green 2. Select ‘Smoke’ from the main menu using the up and down arrows on the keypad 2.
  • Page 5 Functional Smoke Testing with Solo330/332 dispenser and aerosols Functional Heat Testing with Testifire 1. Insert the Solo A10s/A10/A5 smoke aerosol can inside the smoke dispenser 1. Press and hold the red power button for 2 seconds 2. Place the dispenser over the detector ensuring seal around the smoke detector 2.
  • Page 6 d) Functional Multi-sensor Testing c) Functional CO Testing Functional Multi-sensor Testing with XTR2 Functional CO Testing with Testifire 2000/2001 Sequential Testing of the Detector’s Sensors 1. Press and hold the red power button for 2 seconds 2. Select ‘CO’ from the main menu using the up and down arrows on the keypad Using XTR2 to carry out a sequential test means that a number of operations (Smoke, Heat and Clearing) can be pre-programmed into the unit before it is reaised to position the cursor...
  • Page 7 Functional Multi-sensor Testing with Testifire IMPORTANT • Testifire 1000/1001 allows for smoke and heat testing • Testifire 2000/2001 allows for smoke, heat and CO testing • XTR2 allows for smoke and heat testing Smoke 1 Smoke 1 Sequential Testing of the Detector’s Sensors Heat Heat 2 Clear...
  • Page 8 Simultaneous Testing of the Detector’s Sensors – this is only possible with Using XTR2 to carry out Sequential/Combined Testing means that a number of Testifire! operations (Smoke, Heat and Clearing) can be pre-programmed into the unit before it is raised up to the detector. This saves time, reduces handling and enables the To illustrate this, instructions for a Simultaneous Smoke, Heat and CO Test: testing of certain multi-sensor detectors.
  • Page 9 e) Functional Smoke Testing – Hard-to-access detectors f) Functional Smoke Testing – Aspirating Smoke Detection (ASD) Systems Functional Smoke Testing with Scorpion Functional ASD System Testing with Scorpion • Install the Scorpion head-unit adjacent to the smoke detector • Wire the head-unit to a conveniently located Scorpion access point •...
  • Page 10 g) Functional Smoke Testing – Aspirating Smoke h) Functional Smoke Testing – Aspirating Smoke Detection (ASD) Systems Detection (ASD) Systems Functional ASD System Testing with XTR2 Functional ASD System Testing with Solo 365 • Power on XTR2 • Power Solo 365 on •...
  • Page 11 AL9 7JE, United Kingdom Tel: +44 (0) 1707 282 760 info@detectortesters.com detectortesters.com As our policy is one of continuous improvement, details of products described within this publication are subject to change without notice. All information provided here is believed to be correct at the time of going to press.